27
CPS3OEM-3M-DEB
5.
TECHNICAL SPECIFICATIONS
Model
CPS3OEM/24-40
CPS3OEM/24-60
Input
Voltage
From 85 to 265VCA single-phase*
*Output power from 85 to 170Vac
90%
75%
Frequency
From 47 to 65Hz
Current intensity 230/115VAC
5,7A/11,5A
9A/14,5A
Power factor
0,9 in rated conditions
Efficiency
> 80% in rated conditions
Input fuses
2 x T15A/250V – 6,3x 32 (F1/F2)
2 x 25A RIT/250V – 6,3x 32 (F1/F2)
Output
Number of outputs
3 separated outputs BAT D, BAT 1 and BAT 2 (integrated distributor)
Each output can be used on its own and supply the entire current.
Total rated current (+/-7%) / Rated
power
40A/1140W
60A/1710W
Load curve
Type of charge selected using internal switch IU or IUoU
(Boost, Absorption, Floating – factory setting).
Type of batteries
See selection wheel setting table
Regulated and filtered output voltage
See selection wheel setting table. The chargers can operate on DC supply.
Regulation tolerance before
distributors and fuses
< 2% (in rated conditions)
Peak-to-peak ripple and noise
< 2% (in rated conditions )
Automotive output fuses mounted in
parallel in the BAT pole -
2 x 25A/32V (F3, F4)
3 x 25A/32V (F3, F4, F5)
Environment
Operating temperature
Rated conditions : from - 10°C to + 65 °C
Cooling
Controlled draft fan at 20% of the rated current of the charger
Relative humidity
Up to 70% (95% with no condensation)
Storage temperature
-20°C to +70°C
Casing
Material
Casing comprises :
•
steel frame and steel front cover
•
polycarbonate clasp
Paintwork
Grey, black matt epoxy coating
Dimensions excluding cable gland
(length, height, depth) / Weight
350 x 270,8 x 123mm / 7,8Kg
Fixing centre distances
329 x 154mm
Fixing screw (wall)
4 M5 round screws
Protection factor
IP22
Board protection
Protected with water-repellent varnish (marine environment)
Standards
CE/EMC marking
NF EN61000-6-1, NF EN61000-6-2, NF EN61000-6-3, NF 61000-6-4
CE/safety marking
NF EN60950, NF EN60335-2-29
Electrical protections
- Against leaking input surges by rupture of VDR (voltage-dependent resistor) (not
covered by warranty)
- Against output polarity reversals by rupture of fuses
- Against output short-circuits and surges
- Against abnormal overheating by cutting off the charger (internal temperature probe
90°C) – Automatic re-start
-
Against output surges (34V
±
5% in 24V)