22
3.2.4.
Cable linking the earth to the installation
The charger's case should be connected to the installation's earthing system in accordance with current
standards governing the relevant application.
To that effect, connect the installation-to-earth cable to the earthing screw located inside the charger (see
chapter “user interface area”).
This cable's cross-section should be at least 2.5mm², type HO7-VK and equipped with an appropriate
terminal.
3.2.5.
Precautions regarding electromagnetic disturbance generated by the appliance
Use shielded cables for all the connections (*). The shielding should be earthed at both the transmitting and
the receiving ends.
Keep cable length and shielding connections down to a minimum.
Route cables as close as possible to conductive parts ("loose" cables or loops should be avoided – cables
should be flattened against conductive parts).
Keep power cables separate from battery cables.
Keep power cables separate from control cables (at least 200mm).
The cables should only supply power to this appliance; any branch-off or short-out intended to power
another appliance are prohibited.
(
*
)
This is a recommendation for installation rather than an obligation. The installing electrician should
decide whether or not to use shielded cable depending on the EMC environment.
3.2.6.
Cabling principle
3.2.6.1.
Cabling type
Parc batterie principal BAT 1
Connexion batteries
(si configuration en chargeur)
23-04-09 N°10350 26A
Entrée AC
AC input
Battery connections
(in case of charger setting)
Eingang AC
Batterieanschluss
(Im Falle von Ladegerät-Konfiguration)
Entrada AC
Conexión baterias
(en caso de configuración cargador)
Ingresso AC
Connessione batterie
(nel caso di configurazione sotto carica)
Principal battery pack BAT 1
HauptBatteriepärke BAT 1
Parque bateria principal BAT 1
Parcho batteria principale
3.2.6.2.
Other type of installation
Refer to appendix 3.
3.3.
S
ELECTION WHEEL AND SWITCH SETTINGS
–
ADJUSTMENT
-
INDICATORS
3.3.1.
Description
The CPS3 chargers are equipped with a selection wheel (RC1) allowing to set up the charger according the
battery type and the application.