PROPER OPERATION Of ThE GLAss-ChEk PRO (CONT.)

TURNINg ThE METER Off

hold the button down for several seconds to turn off the meter. A message will display on the screen notifying you that the 
meter is about to power down. Continue holding the button down until the screen goes blank. If the meter is left unused for 
a period of time, the unit will automatically shut off. To conserve battery life, it is recommended to turn the meter off  
manually when you are finished using it.

guidelines for Most Accurate Results:

• 

hold the meter steady and flat against the test surface during  

measurement

• 

do not touch the glass with your hand while taking the reading

• 

Take readings at the 

bOTTOM CENTER

 of the window for  

best thickness accuracy  (see explanation below)

• 

Take multiple measurements to verify results

• 

Make sure the window being measured is clean

• 

Make sure the two lenses on the back of the GC3001 are clean.  

see Image to the right. --------> 

use only clean compressed air to clean the lenses. Only use a lint 

free cloth if absolutely necessary to clean smudges, fingerprints, etc.

• 

Make sure nothing is touching the far side surface of the window  

during the measurement

• 

It is best to test windows in free air, not resting on a tabletop surface, or 

stacked on other pieces of glass.

         4 OPTIMAL TEST LOCATIONS                  fOR MOST ACCURATE RESULT

Proper Operation of the Glass-Chek ELITE

Page 6

Place the meter at the bottom center of the window to be tested.  Press 

and release

 the POWER button to take a measurement.  Do not hold 

the POWER button down, as this will cause the meter to shut off.  The “TAKING READING” message will be displayed while your 

measurement is being completed.  The “TAKING READING” screen also indicates the remaining battery life, as well as confirms the operating 

MODE the meter is in. 

Turning The Meter Off

Hold the button down for several seconds to turn off the meter.  A message will display on the screen notifying you that the meter is about to 

power down.  Continue holding the button down until the screen goes blank.  If the meter is left unused for a period of time, the unit will 

automatically shut off.  To conserve battery life, it is recommended to turn the meter off manually when you are finished using it.

Guidelines For Most Accurate Results:

• Hold the meter steady and flat against the test surface during measurement 

• Do not touch the glass with your hand while taking the reading 

• Take readings at the 

 of the window for best 

thickness

   accuracy (see explanation below)

• Take multiple measurements to verify results

• Make sure the window being measured is clean

• Make sure the two lenses on the back of the GC3200 are clean.  See Image 

  to the right. --------> 

  Use only clean compressed air to clean the lenses.  Only use a lint

  free cloth if absolutely necessary to clean smudges, fingerprints, etc.

• Make sure nothing is touching the far side surface of the window during the

  measurement

• It is best to test windows in free air, not resting on a tabletop surface, or             

  stacked on other pieces of glass.

BOTTOM CENTER

Above:  Back of GC3200 meter with the two lenses

circled.  Use clean compressed air to clean the

lenses.

At Right:  Incorrect hand placement.

• DO NOT hold the POWER button while taking a measurement.  This will cause

the meter to turn off.  Rest your index finger next to the button as shown above.

• DO NOT touch the glass with your hand while taking readings.  The picture at

right shows the user’s thumb resting on the window while taking a measurement.

This could cause incorrect results for the low-E measurement. 

4 OPTIMAL TEST LOCATIONS

FOR MOST ACCURATE RESULTS

At Left:  Recommended placement of meter:

Hold the meter steady AND FLAT against the glass during measurement.  

The meter should be centered on one of the four edges of the window with the 

bottom edge of the meter placed parallel to the edge of the window (see image 

to the left).  BOTTOM CENTER IS THE PREFERRED LOCATION.  This will 

minimize the effect of a concave (or collapsed) window.  As you move away 

from the edge of a window, many windows will bow inward (concave).  

Because the sensor runs parallel to the bottom edge of the meter, it is 

important to place the bottom edge of the meter along the edge of the window 

as shown.  You can place the meter approximately 1 to 2 inches from the edge 

of the window.

DO NOT touch the glass with your hand or thumb while taking measurements.  

Note the hand placement used in the picture at left.  The user’s thumb is 

resting on the GC3200 without touching the glass being measured.  Also, be 

sure there are no other metallic objects touching the glass.          

DO NOT continue to hold down

the button while taking a 

measurement.  

Place your index finger next to 

the button as shown at left.  

Proper Operation of the Glass-Chek ELITE

Page 6

Place the meter at the bottom center of the window to be tested.  Press 

and release

 the POWER button to take a measurement.  Do not hold 

the POWER button down, as this will cause the meter to shut off.  The “TAKING READING” message will be displayed while your 

measurement is being completed.  The “TAKING READING” screen also indicates the remaining battery life, as well as confirms the operating 

MODE the meter is in. 

Turning The Meter Off

Hold the button down for several seconds to turn off the meter.  A message will display on the screen notifying you that the meter is about to 

power down.  Continue holding the button down until the screen goes blank.  If the meter is left unused for a period of time, the unit will 

automatically shut off.  To conserve battery life, it is recommended to turn the meter off manually when you are finished using it.

Guidelines For Most Accurate Results:

• Hold the meter steady and flat against the test surface during measurement 

• Do not touch the glass with your hand while taking the reading 

• Take readings at the 

 of the window for best 

thickness

   accuracy (see explanation below)

• Take multiple measurements to verify results

• Make sure the window being measured is clean

• Make sure the two lenses on the back of the GC3200 are clean.  See Image 

  to the right. --------> 

  Use only clean compressed air to clean the lenses.  Only use a lint

  free cloth if absolutely necessary to clean smudges, fingerprints, etc.

• Make sure nothing is touching the far side surface of the window during the

  measurement

• It is best to test windows in free air, not resting on a tabletop surface, or             

  stacked on other pieces of glass.

BOTTOM CENTER

Above:  Back of GC3200 meter with the two lenses

circled.  Use clean compressed air to clean the

lenses.

At Right:  Incorrect hand placement.

• DO NOT hold the POWER button while taking a measurement.  This will cause

the meter to turn off.  Rest your index finger next to the button as shown above.

• DO NOT touch the glass with your hand while taking readings.  The picture at

right shows the user’s thumb resting on the window while taking a measurement.

This could cause incorrect results for the low-E measurement. 

4 OPTIMAL TEST LOCATIONS

FOR MOST ACCURATE RESULTS

At Left:  Recommended placement of meter:

Hold the meter steady AND FLAT against the glass during measurement.  

The meter should be centered on one of the four edges of the window with the 

bottom edge of the meter placed parallel to the edge of the window (see image 

to the left).  BOTTOM CENTER IS THE PREFERRED LOCATION.  This will 

minimize the effect of a concave (or collapsed) window.  As you move away 

from the edge of a window, many windows will bow inward (concave).  

Because the sensor runs parallel to the bottom edge of the meter, it is 

important to place the bottom edge of the meter along the edge of the window 

as shown.  You can place the meter approximately 1 to 2 inches from the edge 

of the window.

DO NOT touch the glass with your hand or thumb while taking measurements.  

Note the hand placement used in the picture at left.  The user’s thumb is 

resting on the GC3200 without touching the glass being measured.  Also, be 

sure there are no other metallic objects touching the glass.          

DO NOT continue to hold down

the button while taking a 

measurement.  

Place your index finger next to 

the button as shown at left.  

Above:

 

back of GC3001 meter with the two lenses  

circled. use clean compressed air to clean the lenses.

At Left: Recommended placement of meter:

• 

hold the meter steady ANd fLAT against the glass during measurement.

• 

The meter should be centered on one of the four edges of the window with the 

bottom edge of the meter placed parallel to the edge of the window (see image 

to the left). bOTTOM CENTER Is ThE PREfERREd LOCATION. This will 

minimize the effect of a concave (or collapsed) window. As you move away 

from the edge of a window, many windows will bow inward (concave). 

because the sensor runs parallel to the bottom edge of the meter, it is 

important to place the bottom edge of the meter along the edge of the window 

as shown. you can place the meter approximately 1 to 2 inches from the edge 

of the window.

• 

dO NOT touch the glass with your hand or thumb while taking measurements. 

Note the hand placement used in the picture at left. The user’s thumb is 

resting on the GC3001 without touching the glass being measured. Also, be 

sure there are no other metallic objects touching the glass.

• 

dO NOT continue to hold down the button  

while taking a measurement.

• 

Place your index finger next to the button as shown at left.

 

 

At Right: Incorrect hand placement.

• 

dO NOT hold the POWER button while taking a measurement. This will cause the meter to turn off. Rest your index 

finger next to the button as shown above.

• 

dO NOT touch the glass with your hand while taking readings. The picture at right shows the user’s thumb resting on 

the window while taking a measurement. This could cause incorrect results for the low-E measurement.

Содержание CRL GLASS-CHECK PRO GC3001

Страница 1: ...SS CHEK PRO OPERATING MANUAL crlaurence com C R Laurence Co Inc 2503 E Vernon Ave Los Angeles CA 90058 1 800 421 6144 crlaurence com SEPTEMBER 2020 AVDB3409_09 20 Glass Thickness Meter and Low E Detec...

Страница 2: ...nd warranty information Table of Contents Page 1 Introduction and Table of Contents Page 2 Meter Layout Results Screen Explanation MENU Options Page 3 Navigating the MENU Unit of Measure Results Scree...

Страница 3: ...erating mode for your application Choosing the wrong mode can result In Incorrect measurement results or no results at all Remember If you change the operating mode It will stay In that mode for all f...

Страница 4: ...ter the MENU system any time the meter is powered on by pressing and holding one of the ARROW buttons Please note that you may need to hold the ARROW button down for several seconds before entering th...

Страница 5: ...on of this feature see the Measurement Examples section When you exit the Display Units menu the meter will show an example of what the measurement results screen will look like according to your sele...

Страница 6: ...the ARROW keys to change the time and then press ain MENU PLEASE NOTE If you would prefer that the change the Result Screen times to the maximum value of me each screen is displayed allowing you to a...

Страница 7: ...stop navigating the menu and allow the meter to automatically power down The meter will automatically shut off after 1 to 2 minutes of inactivity When the meter powers back up it will display the prev...

Страница 8: ...n while taking a measurement Place your index finger next to the button as shown at left Proper Operation of the Glass Chek ELITE Page 6 Place the meter at the bottom center of the window to be tested...

Страница 9: ...is on surface 3 Please note there are times where the meter will not specifically designate surface 3 and may show the result as Surface 3 or 4 This means that the meter is only indicating the coatin...

Страница 10: ...format the measurement will alternate the following three messages Resulting Measurement Displays Due to the application and display format the measurement will alternate the following 2 messages Dis...

Страница 11: ...s lami 159 or 5 32 On screens 2 and 4 you will see that these two thickness values are denoted by the letter D D1 D2 Because the meter does not know which thickness value is the glass and which one co...

Страница 12: ...e material when taking measurements will result in the most accurate Low E measurements One additional note regarding Low E detection If your application contains more than one low e coating in the wi...

Страница 13: ...the window A convenient reference chart is included with the GC3001 meter that lists many of the common Low E coatings used in the USA Here are some examples Triple Pane Windows The GC3001 will specif...

Страница 14: ...will take to complete a measurement 2 If testing dark glass in a window try to test from the side of the window that contains the clear piece of glass 3 Always conduct your measurements in the BOTTOM...

Страница 15: ...error message will appear that recommends replacing the battery soon This gives the user plenty of warning that a battery replacement is needed soon but the meter will still function for a period aft...

Страница 16: ...meter will record accurate readings until the point the electronics reach the temperature below the operating range Depending on the degree of coldness this will allow for several readings to be taken...

Страница 17: ...hing the glass while taking measurements Placing your hand or any metallic object against the lite of glass you are testing may cause the Glass Chek ELITE to yield improper Low E results Remove your h...

Страница 18: ...space and the total IG thickness Depending on the thickness of the glass the maximum thickness range for the total IG thickness changes according to the data below Note these same dimensions apply wh...

Страница 19: ...factory prepaid by the user and the unit is disclosed to the manufacturers satisfaction to be thus defective This warranty shall not apply to any unit that has been repaired or altered other than by t...

Страница 20: ...1 Low E Coating Table Triple Silver Soft Coat Guardian ClimaGuard 62 67 Cardinal LoE 336 PPG SolarBan 70XL Double Silver Soft Coat Cardinal LoE 240 Guardian ClimaGuard 55 27 PPG SolarBan 67 Guardian C...

Отзывы: