6.4.

 

CoE Interface – parameter management in the EtherCAT system 

The CiA organization (CAN in Automation) pursues among other things the goal of creating order and 
exchangeability between devices of the same type by the standardization of device descriptions. For this purpose 
so-called profiles are defined, which conclusively describe the changeable and unchangeable parameters of a 
device. Such a parameter encompasses at least the following characteristics: 
 

 

Index number – for the unambiguous identification of all parameters. The index number is divided into a main 

index and a subindex in order to mark and arrange associated parameters. 
-

 

Main index 

-

 

Subindex, offset by a colon ‘:’   

 

Official name – in the form of an understandable, self-descriptive text   

 

Specification of changeability, e.g. whether it can only be read or can also be written   

 

A value – depending upon the parameter the value can be a text, a number or another parameter index. 

 

 

Example) NA-9286 (with ST-1224, ST-2414) CoE directory 

Index 

Name 

Flags 

Value 

1000 

 

Device type 

RO 

0x00001389(5001) 

1001 

 

Error register 

RO 

0x00 (0) 

1008 

 

Device name 

RO 

NA-9286(Crevis) 

1009 

 

Hardware version 

RO 

NA-9286.v1 

100A 

 

Software version 

RO 

1.001 

1018:0 

 

Identity 

RO 

> 5 < 

 

1018:01 

Vendor ID 

RO 

0x0000029D (669) 

 

1018:02 

Product Code 

RO 

0x39313836 (959526966) 

 

1018:03 

Revision 

RO 

0x00010001 (65537) 

 

1018:04 

Serial Number 

RO 

0x00000001 (1) 

 

1018:05 

Release date 

RO 

0x20120625 (538052133) 

10F1:0 

 

Error Settings 

RO 

> 2 < 

 

10F1:01 

Local Error Reaction 

RO 

0x00000000 (0) 

 

10F1:02 

Sync Error Counter Limit 

RO 

0x00000004 (4) 

1601:0 

 

Slot#2, ST-2414, RxPDO 

RO 

> 1 < 

 

1601:01 

SubIndex 001 

RO 

0x7010:01, 8 

1A00:0 

 

Slot#1, ST-1224, TxPDO 

RO 

> 1 < 

 

1A00:01 

SubIndex 001 

RO 

0x6000:01, 8 

1A01:0 

 

Slot#2, ST-2414, TxPDO 

RO 

> 1 < 

 

1A01:01 

SubIndex 

RO 

0x6010:01, 8 

1C00:0 

 

Sync manager type 

RO 

> 4 < 

 

1C00:01 

SubIndex 001 

RO 

0x01 (1) 

 

1C00:02 

SubIndex 002 

RO 

0x02 (2) 

 

1C00:03 

SubIndex 003 

RO 

0x03 (3) 

 

1C00:04 

SubIndex 004 

RO 

0x04 (4) 

1C12:0 

 

RxPDO assign 

RO 

> 0 < 

 

1C12:01 

SubIndex 001 

RO 

0x1601 (5633) 

1C13:0 

 

TxPDO assign 

RO 

> 0 < 

 

1C13:01 

SubIndex 001 

RO 

0x1A00 (6656) 

 

1C13:02 

SubIndex 002 

RO 

0x1A01 (6657) 

Содержание NA-9286

Страница 1: ...1 FnIO EtherCAT Network Adaptor NA 9286 FnIO S Series Copyright C CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr Version 1 02 2014 CREVIS Co Ltd NA 9286 EtherCAT Network Adapter User Manual...

Страница 2: ...right C CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr DOCUMENT CHANGE SUMMARY REV PAGE REMARKS DATE EDITOR 1 00 New Document 2014 04 24 YM KIM 1 01 Modify the Pin Description 2014 05 08 YM...

Страница 3: ...ation 7 2 1 The Interface 7 2 1 1 NA 9286 EtherCAT 7 2 2 Specification 8 2 2 1 General Specification 8 2 2 2 Interface Specification 9 2 3 LED Indicator 10 2 3 1 Module Status LED MOD 10 2 3 2 Current...

Страница 4: ...5 2 1 NA 9286 RJ 45 Socket 17 5 2 2 I O Process Image Map 18 5 3 Example 19 5 3 1 Example of Input Process Image Input Register Map 19 5 3 2 Example of Output Process Image Output Register Map 20 6 E...

Страница 5: ...pment or explosion Do not assemble the products and wire with power applied to the system Else it may cause an electric arc which can result into unexpected and potentially dangerous action by field d...

Страница 6: ...rmation about practices or circumstances that can lead to personal injury property damage or economic loss Attentions help you to identity a hazard avoid a hazard and recognize the consequences 1 1 2...

Страница 7: ...7 FnIO EtherCAT Network Adaptor NA 9286 FnIO S Series Copyright C CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr 2 Specification 2 1 The Interface 2 1 1 NA 9286 EtherCAT...

Страница 8: ...ly voltage range 11 28 8Vdc Max Current Field Power Contact DC 10A Max Weight 167g Module Size 54mm x 99mm x 70mm Environment Condition Environmental Specifications Operating Temperature Storage Tempe...

Страница 9: ...ac Address IP Address No need Interface Connector RJ 45 socket 2pcs Configuration Tool IO Guide Pro Serial Configuration RS232 Node 1 Fixed Baud Rate 115200 Fixed Data bit 8 Fixed Parity bit No parity...

Страница 10: ...t Running Status LED RUN State LED is To indicate Init Off State of the EtherCAT State Machine INIT Initialization Pre Operational Blinking State of the EtherCAT State Machine PREOP Pre Operational Sa...

Страница 11: ...figuration FnBus Connection Run Exchanging IO Green Exchanging I O data FnBus connection fault during exchanging IO Red One or more expansion module occurred in fault state Changed expansion module co...

Страница 12: ...12 FnIO EtherCAT Network Adaptor NA 9286 FnIO S Series Copyright C CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr 3 Dimension 3 1 NA 9286 mm...

Страница 13: ...m Exception ST 2748 is excepted to calculate maximum length because that is double width module 4 2 Plugging and Removal of the Components As above figure in order to safeguard the FnIO module from ja...

Страница 14: ...14 FnIO EtherCAT Network Adaptor NA 9286 FnIO S Series Copyright C CREVIS Co Ltd Support 82 31 899 4599 URL www crevis co kr 5 Electrical Interface 5 1 FnBus System...

Страница 15: ...les The connection to different field bus systems can be established by each of the corresponding Network Adapter Module e g for SyncNet PROFIBUS CANopen DeviceNet Ethernet IP EtherCAT CC Link MODBUS...

Страница 16: ...ternal bus It is comprised of 6 data pin and 2 field power pin Do not touch data and field power pins in order to avoid soiling and damage by ESD noise No Name Description 1 Vcc System supply voltage...

Страница 17: ...9 URL www crevis co kr 5 2 EtherCAT Electrical Interface 5 2 1 NA 9286 RJ 45 Socket Shielded RJ 45 Socket The use of an incorrect supply voltage or frequency can cause severe damage to the component R...

Страница 18: ...ess Image Map An expansion module may have 3 types of data as I O data configuration parameter and memory register The data exchange between network adapter and expansion modules is done via an I O pr...

Страница 19: ...put Ch1 low byte Slot 3 Byte 5 Analog Input Ch1 high byte Slot 3 Byte 6 Discrete Input low 8 pts Slot 4 Byte 7 Discrete Input high 8 pts Slot 4 Byte 8 Empty Always 0 Discrete Input 4 pts Slot 5 Byte 9...

Страница 20: ...byte Slot 3 Byte 6 Discrete Output low 8 pts Slot 4 Byte 7 Discrete Output high 8 pts Slot 4 Byte 8 Empty Don t care Discrete Output 4 pts Slot 5 Byte 9 Discrete Input 8 pts Slot 6 Byte 10 Empty Don t...

Страница 21: ...p to 4 gigabytes in size Addressing of the Ethernet terminals can be in any order because the data sequence is independent of the physical order Broadcast Multicast and communication between slaves ar...

Страница 22: ...gs are also transferred Safe Operational Safe Op During transition between Pre Op and Safe Op the EtherCAT slave checks whether the sync manager channels for process data communication and if required...

Страница 23: ...time the EtherCAT specification keeps it simple because all the protocols are optional The device manufacturer only has to implement the protocol that the device application needs Fig 1 Several Device...

Страница 24: ...ovides advanced real time Ethernet technology for this device profile which is particularly widespread in CNC applications Optionally the command position speed or torque can be transferred Depending...

Страница 25: ...or not they support TCP IP Literature 1 EN 50325 4 Industrial communications subsystem based on ISO 11898 CAN for controller device interfaces Part 4 CANopen 2 IEC 61800 7 301 304 Adjustable speed ele...

Страница 26: ...he parameter the value can be a text a number or another parameter index Example NA 9286 with ST 1224 ST 2414 CoE directory Index Name Flags Value 1000 Device type RO 0x00001389 5001 1001 Error regist...

Страница 27: ...Index 002 RO 0x00002414 9236 Index Range The relevant ranges for EtherCAT fieldbus users are x1000 This is where fixed identity information for the device is stored including name manufacturer serial...

Страница 28: ...4 4 Points 220Vac 41 00 0A Active Digital Output Module ST 2114 4 Points TTL Inverting 5Vdc 20mA 81 00 0D Active ST 2124 4 Points TTL Non Inverting 5Vdc 20mA 81 00 0F Active ST 221F 16 Points Sink Neg...

Страница 29: ...tive ST 3524 4 Channels Voltage 10Vdc 10Vdc 12bit 41 43 21 Active ST 3544 4 Channels Voltage 10Vdc 10Vdc 14bit 41 43 23 Active ST 3624 4 Channels Voltage 0 5Vdc 12bit 41 43 24 Active ST 3644 4 Channel...

Страница 30: ...PWM output 0 5A 24Vdc source C1 05 01 56 Active ST 5444 4 CH PWM output 0 5A 24Vdc source C1 0B 03 54 Active ST 5641 1 CH Pulse output 0 5A 24Vdc source C1 05 03 92 Active ST 5642 2 CH Pulse output 0...

Отзывы: