46
FnIO MODBUS Adapter NA-9171, NA-9173
FnIO S-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr
+ 0x1D(+29)
0x201D(8221)
0x203D(8253)
0x205D(8285)
……
0x23DD(9181)
0x23FD(9213)
+ 0x1E(+30)
0x201E(8222)
0x203E(8254)
0x205E(8286)
……
0x23DE(9182)
0x23FE(9214)
+ 0x1F(+31)
0x201F(8223)
0x203F(8255)
0x205F(8287)
……
0x23DF(9183)
0x23FF(9215)
Address
Access
Type, Size
Description
+ 0x00(+0)
Read
1 word
Slot module id. Refer to Appendix A.1 Product List.
+ 0x01(+1)
Read
1 word
Expansion Slot IO code. Refer to Table IO Data Code Format.
+ 0x02(+2)**
Read
1 word
Input start register address of input image word this slot.
+ 0x03(+3)**
Read
1 word
Input word’s bit offset of input image word this slot.
+ 0x04(+4)**
Read
1 word
Output start register address of output image word this slot.
+ 0x05(+5)**
Read
1 word
Output word’s bit offset of output image word this slot.
+ 0x06(+6)**
Read
1 word
Input bit start address of input image bit this slot.
+ 0x07(+7)**
Read
1 word
Output bit start address of output image bit this slot.
+ 0x08(+8)**
Read
1 word
Size of input bit this slot
+ 0x09(+9)**
Read
1 word
Size of output bit this slot
+ 0x0A(+10)**
Read
n words
Read input data this slot
+ 0x0B(+11)**
Read/Write
n words
Read/write output data this slot
+ 0x0C(+12)*
Read/Write
1 word
Inactive slot, 0x0000:active, 0x0001:inactive
+ 0x0E(+14)
Read
1 word
ST-number, if ST-1324, returns 0x1324
+ 0x0F(+15)
Read
String upto
74 words
First 1word is length of valid character string.
If ST-1324, returns
“
00 21 53 54 2D 31 33 32 34 2C 20 46 6E 49 4F 20 34 20 53 6F 75 72
63 69 6E 67 20 49 6E 20 34 38 56 64 63 00”
Valid character size = 0x0021 =33 characters,
“
ST-1324, FnIO 4 Sourcing In 48Vdc”
+ 0x10(+16)
Read
1 word
Size of configuration parameter byte
+ 0x11(+17)**
Read/Write
n words
Read/write Configuration parameter data, up to 8byte. Refer to
document(FnIO_Configuration_Parameter_Memory_Register_Rev1.01)
***
+ 0x12(+18)
Read
1 word
Size of memory byte.
+ 0x13(+19)**
Read/Write
n words
Read/write Memory data. Offset of memory is fixed with 0.
+ 0x14(+20)**
Read/Write
n words
Read/write Memory data. First 2byte of write data is memory offset.
+ 0x15(+21)
Read
2 words
Product code Refer to Appendix A.1 Product List.
+ 0x16(+22)
Read
2 words
Catalog number. Refer to Appendix A.1 Product List.
+ 0x17(+23)
Read
1 word
Firmware Revision
+ 0x18(+24)
Read
1 word
FnBus Revision
+ 0x1A(+26)
Read/Write
n words
Reserved. Read/write expansion class access.
+ 0x1B(+27)
Read/Write
n words
Reserved. Read/write maintenance data access.
* After the system is reset, the new “Set Value” action is applied.
** Nothing of output, input, and memory or configuration parameter corresponding slot returns Exception 02.
*** Slot Configuration parameter saved by internal EEPROM during power cycle until slot position changed.
*** All of output modules and special modules have the slot configuration parameter data. Refer to Document.
(FnIO_Configuration_Parameter_Memory_Register_Rev1.01)