FnIO MODBUS Adapter NA-9171, NA-9173
FnIO S-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr
6.3.3.
Adapter Information Special Register (0x1100, 4352)
Address
Access
Type, Size
Description
0x1100(4352)
Read/Write
1 word
Hi byte is two rotary switch values; low byte is current slave node
address. MODBUS slave node address.
If two rotary switches value are 0, the slave node address is assigned
with last valid address and can be changed by software (1~247).
0x1101(4353)
Read
1 word
Hi byte is a current dip switch value; low byte is used current setup
value.
0x1102(4354)
Read
1 word
Start address of input image word register. =0x0000
0x1103(4355)
Read
1 word
Start address of output image word register. =0x0800
0x1104(4356)
Read
1 word
Size of input image word register.
0x1105(4357)
Read
1 word
Size of output image word register.
0x1106(4358)
Read
1 word
Start address of input image bit. = 0x0000
0x1107(4359)
Read
1 word
Start address of output image bit. =0x1000
0x1108(4360)
Read
1 word
Size of input image bit.
0x1109(4361)
Read
1 word
Size of output image bit.
0x110E(4366)
Read
upto
33 word
Expansion slot’s ST-number including NA.
First 1word is adapter’s number, if NA-9173, then 0x9173
0x1110(4368)
Read
1 word
Number of expansion slot
0x1111(4369)
Read
1 word
Number of active slot
0x1112(4370)
Read
1 word
Number of inactive slot
0x1113(4371)
Read
upto
33 word
Expansion slot Module Id. Refer to Appendix A.1 Product List.
First 1word is adapter’s module id.
0x1114(4372)*
Read/Write
1 word
Input process image mode. The default value is 2.
Valid value range is from 0 to 3. Refer to 5.3.1.
0x1115(4373)*
Read/Write
1 word
Output process image mode. The default value is 0.
Valid value range is from 0 to 1. Refer to 5.3.2.
0x1116(4374)**
Read/Write
2 words
Inactive slot list, The corresponding bit represents slot position.
0: Active slot, 1: Inactive slot.
Ex) if value is 0x0001, 0x8000, then slot#1,#32 are inactive slots
0x1117(4375)
Read
2 words
Live slot list. , The corresponding bit represents slot position.
1: live slot, 0: not live slot
0x1118(4376)
Read
2 words
Alarm slot list. The corresponding bit represents slot position.
1: Alarm slot, 0: Normal slot
0x1119(4377)
Read
1 word
Hi byte is MODBUS status, low byte is FnBus status.
Refer to 5.3.1.
0x111A(4378)
Write
1 word
Reserved. Adapter Scan command.
0x111B(4379)
Read/Write
1 word
Reserved. IO State machine.
0x111C(4380)
Read
2 words
Reserved. Runtime fault code.
0x111D(4381)
Read
1 word
Adapter FnBus Revision. If 0x013C, FnBus Revision is 1.60
0x111E(4382)
Read
1 word
Reserved. Adapter IO identification vendor code.
*, ** After the system is reset, the new “Set Value” action is applied.
** If the slot location is changed, set default value automatically (all expansion slots are live).