Problem Solving
Troubleshooting
The table below provides corrective action for possible trouble situations. If further
assistance is required, please contact a Crestron customer service representative.
Series 1000 Touchpanel Troubleshooting
TROUBLE
POSSIBLE
CAUSE(S)
CORRECTIVE ACTION
Touchpanel
does not
function.
Touchpanel is not
communicating to the
network.
Use Performance Viewport (via SIMPL Windows
or VT Pro-e) to poll the network. Verify network
connection to the touchpanel.
Verify touchpanel is in "CRESNET MODE" as
defined in "Interface Menu", page 8.
Touchpanel is not
receiving network
power.
Confirm that power is supplied to the network.
Touchpanel is
incorrectly calibrated.
Enter "SETUP MODE" and recalibrate.
Touchpanel
is not
Incorrect network
wiring.
Touch screen to remove message and verify
correct wiring to all connectors.
responding
and screen
displays
"Cresnet
Error"
Touchpanel Cresnet
ID is not set to match
the Net ID in the
SIMPL program.
Touch screen to remove message and enter
Performance Viewport (via SIMPL Windows or
VT Pro-e) to poll the network. Verify that the
Cresnet ID for the touchpanel is properly set to
match the Net ID in the SIMPL program.
message.
Touchpanel Cresnet
ID not unique, two or
more units share
same ID.
Enter Performance Viewport (via SIMPL
Windows or VT Pro-e) to poll the network. Verify
that each ID is used once.
Touchpanel
display is
Standby timeout has
elapsed.
Touch screen to reactivate.
dark.
Screen brightness or
contrast is improperly
set.
Enter "SETUP MODE" and hold finger to
touchscreen for five seconds to set the
brightness to high and the contrast to a default
level.
Screen is
blank (either
all white or
all black,
backlight is
on).
Contrast adjustment
outside visible range.
Remove power. Restore power while pressing
on touchscreen (for approximately 10 seconds)
until "SETUP MODE" appears.
Unexpected
response
from
touchpanel.
Touchpanel is
incorrectly calibrated.
Enter "SETUP MODE" and recalibrate.