infiNET™ Switches 

Crestron 

CLW-SW1/4RF, -SWS1/4RF, -SLVS1RF

 

Identity Code 

Just like every device on a Cresnet system requires a unique identity code (NET ID), 
every device and user interface on the infiNET network requires a unique identity 
code (MNET ID). These codes are two-digit hexadecimal numbers from 03 to 20. 
The MNET ID of each unit must match an ID code specified in the SIMPL Windows 
program. Refer to “Setting the MNET ID in Device Settings” on page 26 for details 
of the SIMPL Windows procedure. 

The MNET ID of each infiNET device has been factory set to 

01

. After an infiNET 

device is added to an infiNET network, its MNET ID must be changed to a value that 
can be addressed by the control system program (03 to 20). MNET IDs are changed 
from a personal computer (PC) via the Crestron Toolbox. 

NOTE:  

For detailed information on establishing communication between the PC, 

control system, and the dimmer, refer to “Establishing Communications” on page 28
If communication cannot be established, refer to the “Troubleshooting 
Communications” section in the latest version of the 2-Series Control System 
Reference Guide (Doc. 6256), which is available from the Crestron website. 

The Crestron Toolbox provides several methods to easily set or change device 
MNET IDs for any device on the infiNET network. MNET IDs can be set with the 
touch settable ID (TSID) function or manually. To use TSID to set MNET IDs, 
continue reading “Using Touch Settable ID (TSID) to Set MNET ID” below. To 
manually change MNET IDs, refer to “Manually Setting the MNET ID in Crestron 
Toolbox”
 on page 19.  

Using Touch Settable ID (TSID) to Set MNET ID 

Each infiNET device is shipped with the default MNET ID 

01

. Since 01 is an MNET 

ID that cannot be addressed by the control system, the MNET ID of each infiNET 
device (except C2N-MNETRPT repeaters) must be changed to a value between 03 
and 20.  

Using Toolbox, the SIMPL Windows program file (

filename

.smw) can be used in 

conjunction with a device’s TSID feature to set MNET IDs of devices that were 
assigned IDs in a SIMPL Windows program.  

Example: 

A SIMPL Windows program was saved with the filename 

infiNET.smw

. The 

program contains the following devices: 

• 

(1) Crestron PRO2 control system 

• 

(1) TPMC-15-CH touchpanel (NET ID 03) 

• 

(1) C2N-MNETGW infiNET gateway (NET ID 0F) 

• 

(2) CLW-DIM1RF infiNET dimmers (MNET IDs 03 and 0D) 

• 

(1) CLW-SW1RF infiNET switch (MNET ID 04) 

NOTE:

  For reference, one dimmer (MNET ID 03) is described in the example 

SIMPL Windows program as “BR Dimmer” and is located in a bedroom while the 
other dimmer (MNET ID 0D) is described as “LR Dimmer” and is located in the 
living room. 

12  

  infiNET Switches:  Crestron CLW-SW1/4RF, -SWS1/4RF, -SLVS1RF 

Operations Guide - DOC. 6397 

Содержание CLW-SW1

Страница 1: ...Crestron CLW SW1 4RF CLW SWS1 4RF CLW SLVS1RF infiNET Switches Operations Guide...

Страница 2: ...ctronics Inc 15 Volvo Drive Rockleigh NJ 07647 1 888 CRESTRON All brand names product names and trademarks are the property of their respective owners Windows and Windows XP are registered trademarks...

Страница 3: ...de 12 Using Touch Settable ID TSID to Set MNET ID 12 Manually Setting the MNET ID in Crestron Toolbox 19 Programming Software 21 Earliest Version Software Requirements for the PC 22 Programming with D...

Страница 4: ......

Страница 5: ...d interference One button and four button configurations available in white black and almond Can be ordered with custom engraved buttons Can operate as a local load control or infiNET keypad These swi...

Страница 6: ...s a slave unit that when used in conjunction with the SWS1RF or SWS4RF acts as an additional switch control point in a multi switch single circuit application It does not connect to an infiNET system...

Страница 7: ...A SWS1RF SWS4RF 3A SLVS1RF N A Minimum Load 40W 0 5A Operating Temperature and Humidity 32 F to 104 F 0 C to 40 C 10 to 90 Relative Humidity Non Condensing SW1RF SW4RF and SWS1RF SWS4RF Height 4 13 in...

Страница 8: ...Physical Description The SW1RF and SWS1RF have a light emitting diode LED with adjustable brightness via Crestron programming software a rocker button and a three position mode selection switch as sho...

Страница 9: ...s via Crestron programming software four pushbuttons and a three position mode selection switch as shown in the following diagrams Each of the buttons may be pushed to perform certain functions The fu...

Страница 10: ...8 32 cm 3 81 in 9 68 cm 4 13 in 10 48 cm 1 88 in 4 77 cm 2 70 in 6 86 cm 1 50 in 3 81 cm The SLVS1RF is similar in appearance to the SW1RF and SWS1RF but does not have the three position mode selectio...

Страница 11: ...5 19 This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interfer...

Страница 12: ...tiple gateways are installed only one gateway should be in the Acquire mode at a time 2 Place the SW1RF SW4RF SWS1RF SWS4RF into the Acquire mode by doing the following a Move the mode selection switc...

Страница 13: ...ess and hold the top or bottom of the button on the SW1RF SWS1RF or any button on the SW4RF SWS4RF 3 While holding the button slide the mode selection switch to the RUN position 4 Hold the button for...

Страница 14: ...tap Button 1 1 If delay is set to 0 seconds the load will turn off immediately 2 If the switch was in the middle of a delay pressing the button will cancel the delay and turn off the load immediately...

Страница 15: ...ce the LED can be in one of three intensity levels OFF LOW and HIGH The following table describes the LED pattern in all modes of operation Dimmer Operation LED Behavior LED BEHAVIOR DEVICE STATE LOW...

Страница 16: ...change device MNET IDs for any device on the infiNET network MNET IDs can be set with the touch settable ID TSID function or manually To use TSID to set MNET IDs continue reading Using Touch Settable...

Страница 17: ...MNET ID 01 as shown in the Network Device Tree window below Network Device Tree 1 With the Network Device Tree open select Tools SMW Program Tree or click SMW Program Tree Click to Select Program 2 C...

Страница 18: ...riptions such as BR Dimmer LR Dimmer and kitchen switch were created by editing each devices symbol name in the SIMPL Windows Programming Manager For information on editing a symbol name refer to the...

Страница 19: ...ee to the Network Device Tree Link Instruction Window 5 Click OK The cursor will change to a target selector 6 Click on the Network Device tree that is to be linked to the SMW Program Tree A message w...

Страница 20: ...me an installer may want to first identify a device by the entryway then a device in the hallway followed by devices in a room Devices that do not need to be identified can be removed from the list by...

Страница 21: ...l be highlighted Touching a device may result in setting a duplicate MNET ID A warning will be displayed Duplicate MNET ID Warning Click Yes to set the device to the duplicate MNET ID the status will...

Страница 22: ...When all devices have been identified a summary will be displayed in the upper portion of the window Setup Complete 11 Click Close to close the window once all devices have been identified All of the...

Страница 23: ...gram use the Touch Settable ID method described on page 12 to change the MNET ID to match the MNET ID specified in the SIMPL Windows program NOTE You may also use D3 Pro or SystemBuilder to perform MN...

Страница 24: ...en the sub menu appears select Change Network ID Network Device Tree Sub Menu NOTE Any infiNET switch in the Network Device Tree can be identified using Crestron Toolbox Right click a device in the Ne...

Страница 25: ...ired While traditional programming tools can still be used to program a system D3 Pro and SystemBuilder can be used to easily complete all necessary programming for a base system including all touchpa...

Страница 26: ...r o Crestron Engraver 2 2 2 3 or later o CUZ 3 154 for 2 Series processors or later Optional SystemBuilder version 2 0 or later with SystemBuilder Templates version 2 0 1or later Also requires o Visio...

Страница 27: ...which a programmer can select configure program test and monitor a Crestron control system SIMPL Windows offers drag and drop functionality in a familiar Windows environment This section describes a s...

Страница 28: ...er pane of System Views Additional units are assigned different Net ID numbers as they are added For more information on the Net ID of a C2N MNETGW refer to the latest revision of the C2N MNETGW Opera...

Страница 29: ...adds the selected infiNET device with a default MNET ID Following are the default MNET IDs used by SIMPL Windows for each of the switch models CLW SW1RF 07 CLW SW4RF 09 CLW SWS1RF 08 CLW SWS4RF 0A NOT...

Страница 30: ...atically changes MNET ID values of a device added to a program if a duplicate device or a device with the same default MNET ID already exists in the program Always ensure that the hardware and softwar...

Страница 31: ...n be programmed in SIMPL Windows to control the electrical load or to perform another function in the control system program NOTE If a detached device restarts from either a power failure or from movi...

Страница 32: ...ade via the Crestron Toolbox The following sections define how one would upload a SIMPL Windows program to the control system and upgrade the firmware of CLW SW1RF SWS1RF SW4RF SWS4RF However before a...

Страница 33: ...re should match the protocol that the control system expects The usual settings are as follows Port COM 1 through COM 8 Select the correct COM port on the PC Baud rate Auto detect Parity None Number o...

Страница 34: ...vice expand the network device tree by clicking Expand the network device tree until the device to be managed is selected Right click the desired MNET ID to open the sub menu This menu provides a wide...

Страница 35: ...ower and the C2N MNETGW is connected to the control system 2 Reacquire the infiNET device on the C2N MNETGW Refer to Acquiring the Switch on the infiNET Network on page 8 for more information Also ref...

Страница 36: ...you are connected to the control system the Functions option becomes available from the menu bar 4 Select Functions SIMPL Program The SIMPL Program window contains information about the currently load...

Страница 37: ...Switches 5 Click the button to browse for a new compiled spz program Open Window 6 Select a file and click Open When the SIMPL Program window re opens click Send Operations Guide DOC 6397 infiNET Swit...

Страница 38: ...firmware complete the following steps 1 Verify that the procedure for Establishing Communications that begins on page 28 has been performed 2 Open Crestron Toolbox and open the Network Device Tree the...

Страница 39: ...dow 7 Click Open to select the file 8 The Firmware window reopens indicating the target device the new firmware version and release notes information Click View to view the release notes or click Send...

Страница 40: ...cquire the device on infiNET network as described in Acquiring the Switch on the infiNET Network on page 8 If the LED flashes OFF for second two times then returns to low the MNET ID of device is not...

Страница 41: ...of the SIMPL Windows program set the signal Enable_Local_Btn_Outputs high Switch does not operate as described in the manual Switch is detached from the load In the switch symbol of the SIMPL Windows...

Страница 42: ...dvantage of Crestron s award winning customer service team by calling the Crestron corporate headquarters at 1 888 CRESTRON 1 888 273 7876 For assistance in your local time zone refer to the Crestron...

Страница 43: ...mps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the d...

Страница 44: ...Crestron Electronics Inc Operations Guide DOC 6397 15 Volvo Drive Rockleigh NJ 07647 2014134 Tel 888 CRESTRON 12 05 Fax 201 767 7576 Specifications subject to www crestron com change without notice...

Отзывы: