Crestron CLW-SLVS1W Скачать руководство пользователя страница 5

 

CLW-SW1, SWS1, & SLVS1(W/A/B)

 

Wiring Diagram for CLW-SW1 (L) or CLW-SWS1 (R) 

NOTE:

  The WHITE (Neutral) connection on the  

-SLVS1 is optional and is only required for operation of 
the LED. If the neutral is not available, the white lead 
should be capped off. 

Cresnet

Hot

Neutral

Load

RED

BLACK

WHITE

BLUE

Ground

GREEN

LINE

120VAC

60Hz

60Hz

120VAC

LINE

GREEN

Ground

WHITE

BLACK

RED

Load

Neutral

Hot

Cresnet

 

5.  Splice the gray wires of the -SW1 or -SWS1 to 

the Class 2 low voltage wires connected to the 
Crestron control system or a Crestron connection 
block device. Push the wires and the splices into 
a hole in the drywall to provide the necessary 
separation. 

6.  Push all Class 1 Power wires back into the 

wallbox and fasten the device to the wallbox 
with the provided screws. 

NOTE:

  The RED (Load) and BLACK (Hot) wires are 

#14 AWG. The BLUE (Slave) and WHITE (Neutral) 
wires are #18 AWG. The GREEN (Ground) wire is #16 
AWG. The GRAY (Cresnet) wires are #22 AWG. The 
BLACK wire (Cresnet ground) paired with the GRAY 
(Cresnet) wires is #22 AWG. 

7.  Attach decorative faceplate. 

8. Restore 

power. 

Operating Button and Switch  

The -SW1, -SWS1, and -SLVS1 feature one pushbutton. 
The -SW1 and -SWS1 also have a three-position mode 
selection switch. The function the pushbutton is 
determined by the position of the mode selection switch. 
Refer to the following diagram. 

CLW-SWS1 with CLW-SLVS1 Wiring 

NOTE:

 The -SWS1 must be installed in the same 

wallbox that contains the connections to the load. 

Buttons of CLW-SW1, -SWS1, and -SLVS1 

The following wiring diagram illustrates installation of 
the -SWS1 with a -SLVS1. 

Wiring Diagram of CLW-SWS1 with CLW-SLVS1 

GREEN

LINE

120VAC

60Hz

WHITE

Ground

GREEN

BLACK

BLUE

CLW-SLVS1

Hot

Neutral

Load

RED

CLW-SWS1

BLACK

WHITE

CLW-SLVS1

BLUE

BLACK

BLUE

Ground

Ground

GREEN

WHITE

Cresnet

 

Button

Mode Selection Switch
(-SW1 & -SWS1 Only)

 

NOTE:

  The -SLVS1 does not have a mode selection 

switch. It will act in the same mode as the -SWS1. 

NOTE:

  Do not connect the BLUE (Slave) wire to the 

BLACK (Hot) or RED (Load) wires. 

OFF 

When the mode selection switch is in the “OFF” position, 
the pushbutton will not have any function and the load is 
disconnected from the power source. This 

must

 be used 

when changing light bulbs to ensure that the load is fully 
disconnected from power. 

NOTE:

  The RED (Load) and BLACK (Hot) wires are 

#14 AWG. The BLUE (Slave) and WHITE (Neutral) 
wires are #18 AWG. The GREEN (Ground) wire is #16 
AWG. The GRAY (Cresnet) wires are #22 AWG. The 
BLACK wire (Cresnet ground) paired with the GRAY 
(Cresnet) wires is #22 AWG. 

NOTE:

  If a -SWS1 is installed without a -SLVS1, the 

BLUE lead (Slave) should be capped. 

Installation Guide – DOC. 6251 

Stand Alone Wall Box Switch:  CLW-SW1, SWS1, & SLVS1  