background image

Crestron 

CLTI- & CLXI-4HSW4

   

Terminal Block & Module 

Module Installation 

NOTE:  

Before the two-position bypass jumpers, 

shown in the illustration, are removed, the Crestron 
Professional Automation Computer (PAC2), which 
provides control to the system, should be properly 
connected and contain a valid program to provide 
control of the module.  

CAUTION:  

Module contains electrostatic sensitive 

devices (ESDs); unit must be handled from metal 
chassis – do not touch PC board or components. 

NOTE:  

Modules are to be installed after enclosure 

has been completely wired. Refer to the terminal 
block installation procedure on page 2 for details.  

Wiring Diagram of the Terminal Block to the Module 
(Single-wide and Left Side Double-wide Enclosures) 

JUMPERS

INSTALLED

RED

BROWN

BLUE

RED

BROWN

BLUE

RED

BROWN

BLUE

RED

BROWN

BLUE

BLUE

BLUE

BLUE

BLUE

BYPASS JUMPERS ON BROWN AND

RED SECTIONS OF TERMINAL

BLOCK HAVE BEEN REMOVED

AFTER LOOSENING ALL SCREWS.

JUMPER ON BLUE SECTIONS

ARE NOT REMOVED.

ENLARGEMENT DETAIL:

BYPASS JUMPERS

REMOVED

 

1.  Use the four supplied self-tapping pan Phillips 

screws (8B x ¼-inch (6 mm) length) to secure 
the module to the enclosure.  

2.  As shown in the wiring diagrams (next column), 

connect the wires from the module to the 
terminal block. Each wire exits the module 
directly in line with, and is the same color as, the 
terminal to which it should be connected. Wires 
are pre-stripped to 12 mm. Tighten to 1 Nm. Do 
not over tighten. 

3.  If the module is being installed above another 

module within the enclosure, attach the supplied 
module interconnect cable between the two 
modules. The illustration below depicts the area 
within a double-wide enclosure where the 
corners of four modules meet.  

NOTE:  

One wire on the module interconnect cable 

may be a different color from the rest. The color has 
no bearing on its orientation during installation.  

Wiring Diagram of the Terminal Block to the Module 
(Right Side Double-wide Enclosures) 

Use Module Interconnect Cable to Wire Module to Module  

              

MODULE

INTERCONNECT

CABLE ATTACHED

CONNECTION

NOT

MADE

 

JUMPERS

INSTALLED

RED

BROWN

BLUE

RED

BROWN

BLUE

RED

BROWN

BLUE

RED

BROWN

BLUE

BLUE

BLUE

BLUE

BLUE

BYPASS JUMPERS

REMOVED

BYPASS JUMPERS ON BROWN 

AND RED SECTIONS OF TERMINAL

BLOCK HAVE BEEN REMOVED

AFTER LOOSENING ALL SCREWS.

JUMPER ON BLUE SECTIONS

ARE NOT REMOVED.

ENLARGEMENT DETAIL:

 

4.  Turn on the circuit breaker and verify that the 

green 

PWR 

LED on the module lights, the 

breaker does not trip, and power is delivered to 
the loads. 

5.  Turn off the circuit breaker and remove the two-

position bypass jumpers on the brown and red 
sections of the terminal block. The jumpers on 
the blue sections of the terminal block remain 
installed. Refer to the figures in the next column 
for a close-up of the jumpers.  

Installation Guide – DOC. 6412 

Terminal Block & Module:  CLT- & CLX-4HSW4  

  3  

 

Содержание CLTI-4HSW4

Страница 1: ... not exceed 1000 watts Terminal Block Module Locations Double wide Enclosure Installation GROUNDING TERMINAL BLOCKS MODULE TERMINAL BLOCK LEFT TERMINAL BLOCK RIGHT Terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electrician in accordance with all national and local codes CAUTION This equipment is for indoor use only and needs to be air cooled Mount in a...

Страница 2: ...t shorts the hot to switch so that the circuit is receiving power Do not remove any bypass jumpers until all feed and load wiring has been completed the circuit has been tested for electrical faults and the module has been installed Refer to Module Installation on the next page Jumpers are also installed on the blue sections of the terminal block and tie the neutrals together These jumpers should ...

Страница 3: ...or as the terminal to which it should be connected Wires are pre stripped to 12 mm Tighten to 1 Nm Do not over tighten 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE One wire on the mod...

Страница 4: ...following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years from the...

Отзывы: