CLT- & CLX-4HSW4

 

4.  Test the circuit for electrical faults by turning on 

the circuit breaker and checking that the breaker 
does not trip and that the proper loads are 
energized.  

NOTE:  

Unless otherwise indicated, the lighting 

system specified in this guide is modular, requiring 
assembly in the field by a licensed electrician, in 
accordance with all national and local codes. 
If you require a UL Listed panel, Crestron offers this 
service through its UL Listed panel shop. This 
includes complete in factory system configuration 
and assembly by Crestron for an additional fee.  

Wiring Diagram of the Terminal Block to the Feed and 
Load(s)(Single-wide and Left Side Double-wide Enclosures) 

             

TO 

LOAD

4

TO 

LOAD

3

TO 

LOAD

2

TO 

LOAD

1

HOT 1 (*)

HOT 2 (*)

HOT 3 (*)

HOT 4 (*)

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

GROUNDING

TERMINAL

BLOCK

GND

TERMINAL

BLOCK

LEFT 

SIDE

WIRING 

LABEL

AREA FOR

MODULE

LOCATION

LABEL

BYPASS

JUMPERS

(*) FROM 15 OR 20 AMP

CIRCUIT BREAKER

 

 

Terminal Block Installation and Field 
Wiring 

1.  Use the two supplied self-tapping pan Phillips 

screws (8B x ¼ length) to secure the terminal 
block and the appropriate (left or right) wiring 
label to the Crestron Automation Enclosure. The 
wiring label lies beneath the terminal block as 
shown in the two wiring diagrams on this page. 

NOTE:  

Both left and right wiring labels are 

provided. The left-side labels are common for both 
single and double-wide enclosures. The right-side 
labels are only used in double-wide enclosures since 
the modules and terminal blocks along the right side 
must be inverted when mounting. 

 

CAUTION:  

Bypass jumpers are provided to allow 

testing of circuits and to protect the module during 
installation. When properly secured by two screws, 
each jumper on the black and red sections of the 
terminal block shorts the hot to switch so that the 
circuit is energized. On this terminal block there are 
four distinct circuits. Furthermore, the jumpers on the 
white sections of the terminal block tie the neutrals 
together. Do not remove any bypass jumpers until all 
feed and load wiring has been completed, the circuit 
has been tested for electrical faults, and the module 
has been installed. Refer to “Module Installation” on 
next page. 

Wiring Diagram of the Terminal Block to the Feed and 
Load(s) (Right Side Double-wide Enclosures) 

             

TO 

LOAD

1

TO 

LOAD

2

TO 

LOAD

3

TO 

LOAD

4

HOT 1 (*)

HOT 2 (*)

HOT 3 (*)

HOT 4 (*)

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

GROUNDING

TERMINAL

BLOCK

GND

TERMINAL

BLOCK

RIGHT

SIDE

WIRING 

LABEL

AREA FOR

MODULE

LOCATION

LABEL

BYPASS

JUMPERS

(*) FROM 15 OR 20 AMP

CIRCUIT BREAKER

 

NOTE:  

Use copper conductors only – rated 75

°

2.  With the circuit breaker turned off, connect the 

circuit feed (HOT and NEUTRAL) and 
controlled circuit (LOAD) wires to the terminal 
block per the markings provided on the wiring 
label (as shown in the diagrams on this page). 
Terminal blocks accept one 14 - 10 AWG wire. 
Wires should be stripped to ½ inch. Tighten 
terminal blocks to 9 in-lbs. Do not over tighten.  

3.  Grounding terminal blocks are available in the 

cabinet for termination of ground wires. Tighten 
to 35 in-lbs. (14 – 10 AWG), 40 in-lbs.  
(8 AWG), or 45 in-lbs. (6 – 4 AWG).  

2  

  Terminal Block & Module:  CLT- & CLX-4HSW4 

Installation Guide – DOC. 5986B 

Содержание CLT-4HSW4

Страница 1: ...al block and module must be mounted into a Crestron Automation Enclosure by a licensed electrician in accordance with all national and local codes CAUTION This equipment is for indoor use only and needs to be air cooled Mount in a well ventilated area The ambient temperature must be 32 F to 104 F 0 C to 40 C The relative humidity must be 0 to 90 non condensing Terminal blocks are installed along t...

Страница 2: ...the modules and terminal blocks along the right side must be inverted when mounting CAUTION Bypass jumpers are provided to allow testing of circuits and to protect the module during installation When properly secured by two screws each jumper on the black and red sections of the terminal block shorts the hot to switch so that the circuit is energized On this terminal block there are four distinct ...

Страница 3: ...the terminal to which it should be connected Wires are pre stripped to inch Tighten to 9 in lbs Do not over tighten 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE One wire on the module...

Страница 4: ...es following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years from ...

Отзывы: