![Crestron CLS-SLVS1 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/crestron/cls-slvs1/cls-slvs1_user-manual_2684882006.webp)
CLW-SW1, SWS1, & SLVS1(W/A/B)
Buttons of CLW-SW1, -SWS1, and -SLVS1
Setup & Programming
Button
Mode Selection Switch
(-SW1 & -SWS1 Only)
Required Software
Software
TASK
REQUIRED SOFTWARE VERSION
Program control
system to operate
CLW-SW1.
SIMPL™ Windows
®
version
2.07.32 or later with SIMPL+ Cross
Compiler version 1.1 or later and
Library update 387 or later; Also
requires Crestron Database
version 18.1.5 or later.
Upload program
and firmware.
Crestron Toolbox 1.02.29 or later.
Program with
simple wizards for
lighting systems
using a CLW-SW1
(optional but
recommended).
Crestron D3 Pro™ version 2.1.7 or
later with D3 Pro Templates
version 2.0.1 or later. Refer to
software release notes or Crestron
website for other required Crestron
software packages.
OFF
When the mode selection switch is in the “OFF” position,
the pushbutton will not have any function and the load is
disconnected from the power source. This
must
be used
when changing light bulbs to ensure that the load is fully
disconnected from power.
ADJ
Setup
When the switch is in the ADJ position, pressing and
holding the pushbutton will set a delay time for
deactivating the load when the switch is in the PRE
position. To set the delay time, press and hold the
pushbutton for the desired amount of time delay and
release. When the pushbutton is released, the LED will
flash three times to confirm the time delay setting. When
done, return the switch to the PRE position.
The Net ID of the CLW-SW1 has been factory set to
82
.
The Net IDs of multiple CLW-SW1 devices in the same
system must be unique. Net IDs are changed from a
personal computer (PC) via the Crestron Toolbox. When
setting the Net ID, the Net ID of each unit must match an
ID code specified in the SIMPL Windows program.
For more details, refer to the Crestron Toolbox help file.
NOTE:
If a time delay is not set, the delayed-off feature
is disabled by default.
D3 Pro
Crestron D3 Pro Software provides all the tools necessary
to create a complete Crestron Lighting System for
residential applications. The lighting system includes the
control system program, touchpanel screens and keypad
programming, documentation, and real-time lighting
adjustment capabilities. As with all Crestron software, the
D3 Pro software provides extensive right-click and drag-
and-drop functionality, in addition to convenient
keyboard shortcuts for frequently used functions and
commands.
PRE
When the switch is in the PRE position, the load can be
manually activated and deactivated with the pushbutton.
Pressing the pushbutton will deactivate the load after a
delay that was set when the switch was in the ADJ mode.
During the delay, the LED will flash. Tapping the
pushbutton during the delay will deactivate the load
without a delay.
For additional details, download D3 Pro from the
Crestron website and examine the extensive help file.
NOTE:
The device may be warm to the touch during
operation. This is normal.
SIMPL Windows
SIMPL Windows is Crestron’s premier software for
programming Crestron control systems.
NOTE:
While SIMPL Windows can be used to program
the CLW-SW1, it is recommended to use D3 Pro for
configuring a Crestron lighting system.
•
In Configuration Manager, incorporate a CLW-SW1
into the system by dragging the CLW-SW1 from the
6
•
Stand Alone Wall Box Switch: CLW-SW1, SWS1, & SLVS1
Installation Guide – DOC. 6251A