CLCI-1SW2EX-W

Wireless In-Ceiling Switch, 230 Vac
Installation Guide

Description

The CLCI-1SW2EX-W is a two-channel switch capable of controlling two independent, 
230 Vac lighting loads. Its ultraslim design allows it to be installed in the ceiling, either next 
to or near the fixture. Powered by infiNET EX

®

 technology, the CLCI-1SW2EX-W 

communicates wirelessly with the Crestron

®

 control system, making it perfect for both new 

and retrofit applications. Additionally, the switch installs inline without requiring any special 
wiring and can be controlled via a standard light switch.

CLCI-1SW2EX-W Specifications

Additional Resources

Visit the product page on the Crestron website (www.crestron.com) 
for additional information and the latest firmware updates. Use a QR 
reader application on your mobile device to scan the QR image.

* VA ratings are for input power to the transformer. If the input power requirements of the transformer are

unknown, use the bulb's wattage rating to determine proper rating.

Important Notes

CAUTION

:  Observe the following points:

•  Install the CLCI-1SW2EX-W only on 10 A branch circuits.
•  Install using wires that are a maximum of 2.5 mm

2

 and that comply with 

BS6004:2000/IEC 60245 and local electrical codes. 

•  Use the CLCI-1SW2EX-W with loads that have a power factor greater than 0.95. 

NOTE

:  Record the serial number of the device before installation.

Refer to the CLC(I)-SERIES IMPORTANT NOTICE (Doc. 7179) included in the box.

The device must remain in an accessible location when placed into Acquire mode and 
joined to a gateway.

LOW-VOLTAGE APPLICATIONS NOTE

:  Operation of a low-voltage circuit with all 

lamps inoperative or removed may result in current flow in excess of normal levels. To 
avoid overheating the transformer and premature transformer failure, please observe the 
following points: 

•  Do not operate low-voltage circuits without operative lamps in place.
•  Replace burned-out lamps as quickly as possible.
•  Use transformers that incorporate thermal-protection or fuse-transformer primary 

windings to prevent transformer failure caused by overcurrent.

NOTE

:  Observe the folowing points:

• Codes: Install in accordance with all local and national electrical codes.
• Wiring: The CLCI-1SW2EX-W requires a neutral connection to operate.
• Wiring: Use copper wire only. For supply connections, use wires rated at least 75°C.
• Lamp Type: For use with permanently installed incandescent, tungsten-halogen, 

magnetic low voltage, electronic low voltage, fluorescent ballast, neon or cold 
cathode, and motor.

• Temperature: For use where temperatures are between 0°C and 40°C 

(32°

F

 and 104°F).

• Spacing: If mounting one device above another, leave at least 115 mm (4-1/2 in) 

vertical space between them. 

Wiring

WARNING

:  Turn off the power at the circuit breaker. Wiring with the power on can 

result in serious personal injury and damage to the device.

WARNING

: New installations should be checked for short circuits prior to installing a 

CLCI-1SW2EX-W switch. With the power off, close the circuit and then restore the 
power. If the loads do not work or a breaker trips, check and correct the wiring or fixture 
(if necessary). Install the switch only when the short is no longer present. The warranty is 
void if the switch is installed and operated with a shortened load.

The following describes the wiring for the CLCI-1SW2EX-W.

Typical Existing Wiring Diagram (without the CLCI-1SW2EX)

Neutral (Blue)

230 Vac 

Maintained Switch

Live 

(Brown)

Remote 
(Brown)

Live (Brown)

To Additional Fixtures

Neutral 

(Blue)

Typical Wiring Diagram (with the CLCI-1SW2EX-W)

To Additional Fixtures

To Additional Fixtures

Neutral (Blue)

Live (Brown)

Live 

(Brown)

Neutral 

(Blue)

Zone 2

Zone 1

(2.4 GHZ RF 
Communication to 
Control System)

L  N  G  G   N  L  L  R

SL2 N2 SL1 N1

Remote (Brown)

AC Input 

from 

Breaker

AC to 

Next 

Device

Neutral (Blue)

Live (Brown)

Live 

(Brown)

Neutral (Blue)

Live
(Brown)

Earth

(Green/Yellow)

Earth

(Green/Yellow)

230 Vac 

Maintained or 

Momentary 

Switch

Remote Switch Wiring Options

Local and Remote Operation

The operation described in this guide assumes the device is in Local mode.The device can 
also operate in Remote mode, where button behavior is dictated by the control system.

Local mode options (available in SIMPL Windows):

•  Maintained Switch (Default): Unit will toggle on and off when the switch is toggled.
•  Momentary Switch: Single Tap - Both loads will toggle on and off. 

NOTE

:  If one load is on, both turn off. If both loads are off, both turn on.

SPECIFICATION 

DETAILS 

Input Voltage 

220 to 240 Vac, 50/60 Hz line power 

Load Ratings* 

Number of Channels 

Maximum Load per Channel 
Switch Load Types 

Environmental 

Temperature 
Humidity 

2 AX (2 A fluorescent) 
Incandescent, tungsten-halogen, magnetic low 
voltage, electronic low voltage, fluorescent 
ballast, neon or cold cathode, and motor 

0°C to 40°C (32°

F

 to 104°F) 

10% to 90% RH (noncondensing) 

Remote Maintained (Single Switch)

Remote Maintained (Multiway)

Remote Momentary (Single Switch)

Remote Momentary (Multiway)

Remote Maintained (Multiway)

Live

Remote

Live

Remote

Remote

Live

Remote

Live

Live

Remote