background image

Complete the following to install a CLCI-1SW2EX-W switch.

  1.  Turn off the power at the main circuit breaker. 

WARNING

:  The device should be mounted in a well-ventilated and dry area. 

  2.  Identify the installation location for the CLCI-1SW2EX-W. 
  3.  Identify and tag the live, switched live, and neutral wires. 
  4.  Remove the end caps from the device by unfastening the two screws shown. 

 

Removing the end caps

  5.  Loosen the strain relief clamp screw and rotate the clamp to the side for wiring.

 

Rotating the strain relief clamp

  6.  To mount the device (optional), use two M3 X .05 screws (not supplied).

 

Mounting Screw Locations

  7.  Wire the device as shown in the illustration in the “Wiring” section. 

CAUTION

:  Use with wires that are a maximum of 2.5 mm

2

.

  8.  Tuck the wires under the strain relief clamps, and tighten the clamp screws. 

 

Fastening the strain relief clamp

  9.  Replace the end caps.
  10. With the device still accessible, turn on the main circuit breaker. 
  11. Acquire the device to the gateway (refer to “Wireless Communications”). 

L  N  G  G   N  L  L  R

Loosen the screw. 

(Do NOT remove.)

Mounting Screw Locations

Tighten the screw.

L  N  G  G   N  L  L  R

Unscrew 

and remove.

Unscrew 

and remove.

Installation

WARNING

:  To avoid fire, shock, or death, turn off the power at the circuit breaker or 

fuse and test that the power is off before wiring! 

NOTES

:  Observe the following points:

  •  This product must be installed and used in accordance with appropriate electrical 

codes and regulations.

  •  This product must be installed by a licensed electrician.

NOTE

:  Before using the CLCI-1SW2EX-W, ensure the device is using the latest 

firmware. Check for the latest firmware for the CLCI-1SW2EX-W at 
www.crestron.com/firmware. Firmware is loaded onto the device using Crestron 
Toolbox™.

This product is listed to applicable IEC Standards and requirements.

The product warranty can be found at www.crestron.com/warranty.
The specific patents that cover Crestron products are listed at patents.crestron.com.
Certain Crestron products contain open source software. For specific information, please visit 
www.crestron.com/opensource.
Crestron, the Crestron logo, Crestron Toolbox, infiNET EX, and the infiNET EX logo are either 
trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other 
countries. Other trademarks, registered trademarks, and trade names may be used in this document 
to refer to either the entities claiming the marks and names or their products. 

Wireless Communications

The device connects to the Crestron network via the infiNET EX communications protocol. 
Use the procedures outlined below to join or leave an infiNET EX network and to verify 
communications between the device and the control system.

Joining an infiNET EX Network

Before a device can be used in a lighting system, it must first join an infiNET EX network. 
To join an infiNET EX network, the device must be acquired by an infiNET EX gateway.

NOTE

:  A device can be acquired by only one gateway.

  1.  Put the infiNET EX gateway into Acquire mode from the unit itself or from Crestron 

Toolbox. Refer to the gateway’s manual at www.crestron.com/manuals for details.

NOTE

:  In an environment where multiple gateways are installed, only one gateway 

should be in Acquire mode at any time.

  2.  Put the device into Acquire mode.
 

a.  Tap the Setup button three times and then press and hold it down 

(tap-tap-tap-press+hold) until the Chan. 1 and Chan. 2 LEDs on the device blink 
once (this can take up to 10 seconds).

 

b. Release the button to start the acquire process. Chan. 1 LED and the attached 

load will blink slowly to show that the device is actively scanning the infiNET EX 
network. 

NOTE

:  The acquire process can also be initiated by a remote maintained switch (if 

equipped) by flipping the switch four times rapidly or by tapping the remote 
momentary switch (if equipped) four times rapidly. The Chan. 1 LED and attached 
load will blink (this can take up to 10 seconds).

 

•  Chan. 1 LED and load turn on for 5 seconds to show that the device has been 

successfully acquired by the infiNET EX network. The load will then turn on.

 

•  If the device fails to acquire, the Chan. 1 LED and load will flash rapidly until a 

button is pressed. The load will then turn off. Ensure the gateway is in Acquire 
mode and within range before attempting the acquire process again. 

 

3. Once all devices have been acquired, take the gateway out of Acquire mode. 

Refer to the gateway’s manual for details.

Leaving an infiNET EX Network

To leave an infiNET EX network, put the device into Acquire mode, as described in 
“Joining an infiNET EX Network” above, when no gateway is in Acquire mode.

Verifying Communications Status

To check the communications status of the device, tap the Setup button three times and 
then press and hold it down (tap-tap-tap-press+hold) for up to 2 seconds. The Chan. 1 
LED blinks to indicate the communications status. Refer to the following table for details.

Crestron Electronics, Inc. 

Installation Guide - DOC. 6952D

15 Volvo Drive   Rockleigh, NJ 07647 

(2028305)

Tel: 888.CRESTRON 

10.15

Fax: 201.767.7576  

Specifications subject to 

www.crestron.com 

change without notice.

Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not 
responsible for errors in typography or photography.
This document was written by the Technical Publications department at Crestron.
©2015 Crestron Electronics, Inc.

Troubleshooting

The following table provides corrective actions for possible trouble situations. If further 
assistance is required, please contact a Crestron customer service representative.

CLCI-1SW2EX-W Troubleshooting

LED 

COMMUNICATIONS STATUS 

Turns on for 5 seconds 

The device is communicating with the control system. 

Blinks three times 

The device is communicating with the gateway, but the 
gateway is not communicating with the control system. 

Blinks twice 

The device was previously joined to the network but is not 

communicating with the gateway. 

Blinks once 

The device is not joined to the network. 

TROUBLE 

POSSIBLE CAUSE(S) 

CORRECTIVE ACTION 

The unit does not 
function. 

The device is not receiving 
line power. 

Verify that the switch is 
properly connected to the 
power line and the neutral. 
Verify that the circuit 

breaker is closed.  

The device is in Remote 

mode. 

Check the SIMPL program 
to determine or change 

the operating mode. 

All attached lamps have 
burned out.  

Replace all of the burned-
out lamps.  

The device is not 
communicating with the 

gateway.  

Use the Crestron Toolbox 
to poll the network. Verify 
the network connection to 

the device. 

Отзывы: