Crestron
CHV-TSTAT and CHV-THSTAT
Thermostats
Viewport ID String
Using the
Diagnostics | Report Network Devices
(
F4
) command in Viewport, the
thermostats output a string of characters that describe the setup and configuration of
the thermostat. Refer to the following table for an explanation of this string. A
semicolon separates each element of the setup string. Strings are contained within
parenthesis, and follow one space after the PPN in the ID string. Refer to the
following two examples of ID strings.
Example 1:
- SLAB 4B system with aux heat (SB4B-AX;)
- Slab max is 50C (SMX50;)
- Interstage differential is 2.0C (ID2.0;)
- Balance points are -10C, 0C, offset of 0C (HBP-10; ABP0; OS0.0;)
- Auto dead band 2C (ADB2.0;)
- Half C units (C05;)
2A: CHV-THSTATA [v2.0, #D8000000] (SB4B-AX;H1;C1;HA2;CA2;SMX50;ID2.0;
HBP-10;ABP0;OS0.0;ADB2.0;DA;C05;OUSOOO;SETUP)
Example 2:
- SLAB 1 system with slab regulation index 3 (SB1;SRG3;)
- Offset of 0C (OS0.0;)
- Half C units (C05;)
2B: CHV-THSTATA [v2.0, #D8000000] (SB1;SRG3;OS0.0;C05;OUSOOO;SETUP)
Refer to the following chart for ID string definitions.
Operations and Installation Guide – DOC. 8163C
Thermostats: CHV-TSTAT and CHV-THSTAT
•
81