background image

2 of 2

LPN00102X0001A2_A

lighting.cree.com

© 2018 Cree, Inc. All rights reserved. For informational purposes only. Content is subject to change. 
See http://lighting.cree.com/warranty for warranty and specifications. Cree

®

 is a registered trademark, and the Cree logo and 

Cree Edge

TM

 are trademarks of Cree, Inc. 

ELECTRICAL CONNECTIONS

STEP 1:

Make the following Electrical Connections:

a.  For 120/277/347V connect the black fixture lead to the 

voltage supply position of the terminal block or Hot 1 (for 
208/240/480V wiring).

b.  For 120/277/347V connect the white fixture lead to the 

neutral supply position of the terminal block or Hot 2 (for 

208/240/480V wiring).

c.  Connect the green or green/yellow ground lead to the 

green wire position of the terminal block.

d.  If Dimming is an option; connect the violet dimming 

positive lead to the supply dimming positive lead.

e.  If Dimming is an option; connect the grey dimming 

negative lead 

to the supply dimming negative lead

   LINE
OR HOT 1

GREEN

LINE-BLACK

GROUND-GREEN

NEUTRAL-WHITE

DIM (-) GREY

DIM (+) VIOLET

NEUTRAL

OR HOT 2

VIOLET

GREY

SUPPL

Y WIRING

(DIMMING OPTIONAL)

LUMINAIRE

STEP 6:

Attach the Mounting Bracket to the customer supplied pendant and pendant 
coupling. Secure the pendant fitter to the pendant coupling.

STEP 7:

Install a suitable Listed cord strain relief brushing or bushing in the customer 
supplied junction box, and feed the luminaire’s cord through it. 

STEP 8:

Connect the cord to the supply wiring per the 

Electrical Connections 

section.

MOUNTING - HOOK AND CORD MOUNT

STEP 1:

Remove the (4) nuts and washers securing the retained Mounting Bracket 
Bolts to the top of the mounting bracket. Remove the top piece of the 
mounting bracket assembly from the luminaire. See 

Figure 1.

 

STEP 2:

Install hooks using supplied set screws to the mounting bracket. See 

Figure 

4.
NOTE: 

Do not fully tighten hook set screws until luminaire is balanced. Slid 

the hooks until luminaire is properly balanced and tighten set screws when 
finished.

STEP 3:

Secure the mounting bracket to the luminaire using the nuts and washers 
removed in Step 1 to 180 in/lbs.

STEP 4:

Push down on retainer spring until top of spring is free of luminaire hook.

STEP 5:

Slide hook into securely mounted customer supplied eye hanger and return 
retainer spring to original position.

STEP 6:

Install a suitable listed cord strain relief brushing or bushing in the customer 
supplied junction box, and feed the luminaire’s cord through it. 

STEP 7:

Connect the cord to the supply wiring per the 

Electrical Connections 

section.

Mount Hook

Power Cord

Hook Set Screw

Retainer Spring

4