VCIOM-05044
Page 62 of 75
DIgITal EPIC-2 TEChnICal Manual
InstallatIon and operatIng InstructIons
From PST Sign Sub-menu, scroll down
to “View all PST” then press SElECT.
This is the Page 1 of 3 of the Maintenance PST
Data. Press the down arrow to go to Page 2.
7.3.4.3.2.2.2 View maintenance PST
From View PST Sub-menu, scroll down
to “View MPST” then press SElECT.
This is the Page 2 of 3 of the Maintenance PST
Data. Press the down arrow to go to Page 3.
This is the Page 3 of 3 of the Baseline PST Data.
From here, press the up arrow key to go back
up to the Open Runtime Data menu and up
arrow again to go back to View PST sub-menu.
7.3.4.3.3 Solenoid operated valve test
The SOVT is a special test to test the solenoid
without requiring any movement of the valve.
Signatures must be enabled. The SOVT
doesn’t create a signature but does require
the pressure sensor which is only available
when signatures are enabled. This test will
de-energize the solenoid and look for a change
of pressure. When the pressure drops to about
50% of the normal break pressure, the solenoid
will be energized again to avoid moving the
valve.
From Diagnostics Sub-menu, scroll down to
“SOV Test” then press SElECT.