SGPC GRINDER PUMP TROUBLE SHOOTING

CAUTION !

 Always disconnect the pump from the electrical power source before handling.

If the system fails to operate properly, carefully read instructions and perform maintenance recommendations.

If operating problems persist, the following chart may be of assistance in identifying and correcting them:

MATCH “CAUSE” NUMBER WITH CORRELATING “CORRECTION” NUMBER

.

NOTE:

 Not all problems and corrections will apply to each pump model.

PROBLEM

CAUSE

CORRECTION

Pump will not run

1.

 Poor electrical connection, blown fuse, 

tripped breaker or other interruption of power, 

improper power supply.

2.

 Motor or switch inoperative (to isolate 

cause, go to manual operation of pump).

2a.

 Float movement restricted.

2b

. Switch will not activate pump or is defec-

tive.

3.

 Insufficient liquid level.

16.

 Check jumper between #7 and #8 in 

control panel. 

1. 

Check all electrical connections for 

security. Have electrician measure current 

in motor leads, if current is within ±20% 

of locked rotor Amps, impeller is probably 

locked. If current is 0, overload may be 

tripped. Remove power, allow pump to cool, 

then recheck current.

2a.

 Reposition pump or clean basin as 

required to provide adequate clearance for 

float.

2b.

 Disconnect level control. Set ohmmeter 

for a low range, such as 100 ohms full scale 

and connect to level control leads. Actuate 

level control manually and check to see that 

ohmmeter shows zero ohms for closed switch 

and full scale for open switch. (Float Switch).

3.

 Make sure liquid level is at least equal to 

suggested turn-on point.

4.

 Recheck all sizing calculations to 

determine proper pump size.

5.

 Check discharge line for restrictions, 

including ice if line passes through or into 

cold areas.

6.

 Remove and examine check valve for 

proper installation and freedom of operation.

7.

 Open valve.

8.

 Check cutter for freedom of operation, 

security and condition. Clean cutter and inlet 

of any obstruction.

9.

 Loosen union slightly to allow trapped air 

to escape.Verify that turn-off level of switch 

is set so that the suction is always flooded. 

Clean vent hole.

10.

 Remove & examine for damage. Replace 

pump stator if required.

11.

 Repair fixtures as required to eliminate 

leakage.

12.

 Check pump temperature limits & fluid 

temperature.

13.

 Replace portion of discharge pipe with 

flexible connector.

14.

 Turn to automatic position.

15.

 Check for leaks around basin inlet and 

outlets.

16.

 A jumper between #7 and #8 is required 

for standard SGPC grinder pumps. For 

pumps with Closed Valve Protection (CVP) 

the jumper is replaced with the red and 

orange leads from the pump, the system 

pressure may exceed the rating of the CVP.

Pump will not turn off

2a.

 Float movement restricted.

2b

. Switch will not activate pump or is defec-

tive.

4.

 Excessive inflow or pump not properly sized 

for application.

9.

 Pump may be airlocked.

14.

 H-O-A switch  on panel is in “HAND” posi-

tion

Pump hums but does not run

1.

 Incorrect voltage

8.

 Cutter jammed or loose on shaft, worn or 

damaged, inlet plugged.

Pump delivers insufficient capacity

1.

 Incorrect voltage.

4.

 Excessive inflow or pump not properly sized 

for application.

5.

 Discharge restricted.

6.

 Check valve stuck closed or installed 

backwards.

7.

 Shut-off valve closed.

8.

 Cutter jammed or loose on shaft, worn or 

damaged, inlet plugged.

9.

 Pump may be airlocked.

10.

 Pump stator damaged/torn.

Pump cycles too frequently or runs 

periodically when fixtures are not in use

6.

 Check valve stuck closed or installed 

backwards.

11.

 Fixtures are leaking.

15.

 Ground water entering basin.

Pump shuts off and turns on indepen-

dent of switch, (trips thermal overload 

protector). 

CAUTION!

  Pump may start 

unexpectedly. Disconnect power supply.

1.

 Incorrect voltage.

4.

 Excessive inflow or pump not properly sized 

for application.

8.

 Cutter jammed, loose on shaft, worn or 

damaged, inlet plugged.

12.

 Excessive water temperature.

Pump operates noisily or vibrates 

excessively

4.

 Operating at too high a pressure.

5.

 Discharge restricted.

8.

 Cutter broken.

13.

 Piping attachments to buiding structure too 

rigid or too loose.

Содержание Barneb PS SGPC Series

Страница 1: ...ement program product changes may occur As such Crane Pumps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 108093 Rev P TM ultra Series SGPC 1 0 HP 1750 RPM 60 Hz SUPERSEDED Some parts may ...

Страница 2: ...G Keep clear of suction and discharge openings DO NOT insert fingers in pump with power connected Make sure lifting handles are securely fastened each time before lifting Do not operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Do not exceed manufacturers recommendation for maximum performance as this could cause the motor to...

Страница 3: ...is the Barnes UltraGRIND grinder pump station The basin collects all wastewater from the house The solids in the sewage are then ground to a small size suitable for pumping in the slurry The grinder pump generates sufficient pressure to pump this slurry from your home to the wastewater plant Power Failure Your grinder pump cannot dispose of wastewater or provide an alarm signal without electrical ...

Страница 4: ...m 15 Ft 4 6m Std or 30 Ft 9m Cord Custom Molded Quick Connected for sealing and strain relief CORD AU CVP CSA UL Approved 12 5 Type SOW L CSA UL Approved 12 3 Type SOW SPEED 1750 RPM 60Hz UPPER BEARING Design Single Row Ball Lubrication Oil Load Radial LOWER BEARING Design Single Row Ball Lubrication Oil Load Radia Thrust MOTOR Design Oil Filled Squirrel Cage Induction Insulation Class B Type Perm...

Страница 5: ...5 inches mm SGPC1024AUF SGPC1024AUE ESPS 150 Level Control Sold Separatly ...

Страница 6: ...24CVP 1 240 1 D 9 2 17 5 2 3 9 7 PUMP MODEL HP 60Hz BREAKER SIZE CORD SIZE CODE TYPE CORD O D 02 5 in mm CORD LENGHT Ft m SGPC1014L 1 30 AMP 12 3 SOW 61 15 5 15 4 6 SGPC1024L 1 25 AMP 12 3 SOW 61 15 5 15 4 6 SGPC1024AU 1 25 AMP 12 5 SOW 71 18 30 9 SGPC1024AU 1 25 AMP 12 3 SOW 61 15 5 30 9 SGPC1024CVP 1 25 AMP 12 5 SOW 71 18 15 4 6 Winding Resistance 5 measured from terminal block Pump rated for op...

Страница 7: ...he pump be installed and tested before the long term storage begins such installa tion will be allowed provided 1 The pump is not installed under water for more than one 1 month 2 Immediately upon satisfactory completion of the test the pump is removed thoroughly dried repacked in the original shipping container and placed in a temperature controlled storage area SERVICE CENTERS For the location o...

Страница 8: ... float is attached to the piping at the factory or shipped loose Hardware is provided for mounting the ON OFF float typically to a 1 25 NPT pipe Other various mounting methods can be used so long the ON OFF float is 1 Securely mounted to a fixed object such as pipe brackets etc 2 Has a three to three and one half inch tether length 3 Basin wall pump inflow etc DO NOT obstruct float operation 4 Bel...

Страница 9: ...ed to as an inherent overheating protector and operates on the combined effect of temperature and current This means that the overload protector will trip out and shut the pump off if the windings become too hot or the load current becomes too high It will then automatically reset and start the pump after the motor cools to a safe temperature In the event of an overload the source of this conditio...

Страница 10: ...10 FIGURE 5 Single Phase 240 Volt AC with Closed Valve Protection CVP Single phase 240 Volt AC AU Series Wiring Schematic For Pumps with Dual Hole Motor Housing ...

Страница 11: ...ny obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Remove examine for damage Replace pump stator if required 11 Repair fixtures as required to eliminate leakage 12 Check pump temperature limits fluid temperature 13 Replace portion of discharge pipe with flexible connector 14 Turn...

Страница 12: ...ower Guide Bracket Assembly 4 1 112354 Check Valve Upper Moveable 5 1 116470 Street Elbow Pump NOT included under these part numbers The Moveable Assembly will be factory assembled to the pump when a Basin Package system is ordered MOVEABLE ASSEMBLY P N 116601 For SGPC UltraCAV Grider Pump with C Channel Rail ...

Страница 13: ...13 FIGURE 7 ...

Страница 14: ...242 39 A R Permatex 2C 41 A R Grease Food Grade 450 deg MP 48 1 105197 Snap Ring ITEM QTY PART NO DESCRIPTION 49 1 2 31051 224 O Ring 50 1 103760 113271 Terminal Block STD Terminal Block AU or Press Cutout 51 1 625 02117 Sleeving PRESSURE CUTOUT SWITCH OPTION 52 1 103759 Block Terminal 2Pin 53 1 113281 Switch Pressure Cutout 54 1 105147B Wire Jumper 10 55 1 105149 Wire Jumper 56 1 625 00163 Connec...

Страница 15: ...15 NOTES ...

Страница 16: ... A RETURNED GOODS AUTHORIZATION CONTACT YOUR LOCAL CRANE PUMPS SYSTEMS INC DISTRIBUTOR Products Returned Must Be Cleaned Sanitized Or Decontaminated As Necessary Prior To Shipment To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty If...

Отзывы: