120/240 Volt AC, 30 Amp Receptacle
Use a NEMA L14-30 plug with this receptacle.
Connect a suitable 4-wire grounded cord set to the
plug and to the desired load. The cord set should be
rated for 250 Volts AC at 30 Amps (or greater).
Use this receptacle to operate 120 Volt AC, 60 Hz,
single phase loads requiring up to 3,600 watts
(3.6 kW) of power at 30 Amps or 240 Volt AC, 60 Hz,
single phase loads requiring up to 7,200 watts
(7.2 kW) of power at 30 Amps. The outlet is protected
by a 30 Amp push–to–reset circuit breaker.
120/240 Volt AC, 50 Amp Receptacle
Use a NEMA 14–50 plug with this receptacle. Connect
a 4-wire cord set rated for 250 Volts AC at 50 Amps to
the plug.
Use this receptacle to operate 240 Volts AC, 60 Hz,
single phase loads requiring up to 10,000 watts
(10.0 kW) of power.
CAUTION!
Although this outlet states it has a
240 Volt 50 Amp rating (up to 12,500 watts), the
generator is only rated for 10,000 watts.
Powering loads that exceed the wattage/
amperage capacity of the generator can
damage it and cause serious injuries.
11