Note: READY appears on the top right hand cor ner of the screen.

Press and hold down the      or      keys to program 

the cylinders manufacturer‚s maximum fill weight plus the empty tank. 

This can be calculated as 

follows: 80%WC+TW WC=W ater W eight Capacity of Cylinder

,  TW=Empty tank weight

6)  Press the GO key to open the solenoid valve. 

This allows the flow of refrigerant to a refrigerant 

recovery unit.

RECOVERY

1)   Place the Scale on a level, rigid surface.

2)   Press POWER key to turn the unit ON, 

it zeroes out any weight on platform.

3)   Select the desired unit by pressing UNITS key .

4)   Connect scale as shown in Figure 1. Do not place cylinder on 

platform at this time.

5)   Press the SET key and the display will show:

READY

READY

000 lbs

000 kg

00.00 oz  “   OR

0000 g”.

7) Now place the cylinder on the scale platform as shown in Figure 2. 

Caution: It is very important 

not to place the cylinder on the platform before this step. Failure to do so could lead to 
overfilling a refrigerant cylinder. 

Danger

- the recovery cylinder used contains liquid refrigerant. Overfilling of the recovery tank 

may cause a violent explosion resulting in severe injury or even death.

8) Turn on the refrigerant recovery unit. Follow the recovery unit‚s instructions.

9) If the recovery process finishes before the weight exceeds the programmed maximum tank weight, 

push the SET key to return to stop the RECOVERY mode and return to the Weighing mode. Reweigh

the tank to confirm the total weight of the cylinder does not exceed the maximum allowable amount.

10) If during the recovery process the gross weight exceeds the programmed maximum tank weight, the 

solenoid valve will close preventing the additional filling of the refrigerant cylinder

. Exchange the 

cylinder with an empty one and proceed back to STEP 4.

When CHARGE mode has been completed, remove the cylinder from the platform, press and hold the 

POWER key for 1 second to turn the unit OFF .

OTHER FEATURES

Battery Low Indications:

-Scale Electronics Battery

The battery indicator is shown on the LCD as a battery shape with a 3 segment Power Level Bar Graph:

Note: If the unit shuts off on low battery, the unit will revert to Auto Shut Off feature.

-Solenoid Valve Battery

The CC800A has a separate 9 VDC battery for the solenoid valve. It is located in the lower battery 

compartment. Please note that the LCD low battery indicator does not detect battery levels for this battery.

If the Solenoid Valve battery is low, the CC800A will briefly sound an alarm after pushing the GO key while

in the RECOVER or CHARGE mode.  Under a low battery condition, the solenoid valve will only operate 

with up to 350-PSI dif ferential.  A fresh valve battery will operate the solenoid valve with up to 485-PSI 

pressure difference across its ports.

100% (3 segments) of Bar Graph-
67% (2 segments) of Bar Graph-
33% (1 segment) of Bar Graph-
0% (0 segments) of Bar Graph-
LO CELL displayed on LCD-

Battery at 100% to 80%

Battery at 80% to 60%

Battery at 60% to 20%

Battery at 20% to 5%

Battery below 5%, replace

Figure 2

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание PRO-SET CC800A Series

Страница 1: ...idity 0 to 95 non condensing Display Resolution oz gm Increments 25 ounces 10 grams Accuracy 0 05 of reading or 25 oz 10 grams whichever is greater Operating Power Source Two 9V alkaline battery ANSI 1604AC IEC 6LR61 Battery Life 30 hours of continuous use Battery Indicator Battery symbol with 3 segment Power Level Bar Graph Maximum Working Pressure 500 PSIG 34 bar Max Operating Pressure Different...

Страница 2: ...or 1 second to tare while the unit is in the WEIGHING mode It returns the display to 00 00 in the SETTING mode The TARE key is not active while the unit is in the HOLD mode In the SET mode the TARE key will reset the programmed amount to zero GO HOLD Initiates the CHARGING or RECOVER Y modes per the data entered after pushing the SET key The data entered will determine how long the solenoid valve ...

Страница 3: ...item A or B A When the programmed charge amount is reached the CC800A will sound a continuous beep and the display will show the amount that has been charged sign on the display Set up another charging process by pressing SET RESET twice and follow the instruction in STEP 6 note that the previous setting amount will show B If the refrigerant is no longer being dispensed after 3 minutes but the pro...

Страница 4: ...e total weight of the cylinder does not exceed the maximum allowable amount 10 If during the recovery process the gross weight exceeds the programmed maximum tank weight the solenoid valve will close preventing the additional filling of the refrigerant cylinder Exchange the cylinder with an empty one and proceed back to STEP 4 When CHARGE mode has been completed remove the cylinder from the platfo...

Страница 5: ...unds makes the unit display OL Auto Shut Off and Smart Awake features Auto Shut Off The unit will automatically shut off after 10 minutes if the weight on its platform does not change by more than 1oz 30g in that period of time Note Auto Shut Off is disabled in the RECOVERY and CHARGE modes Smart Awake When Auto Shut Off feature is active the last weight reading is stored in memory Next time scale...

Страница 6: ...ration 10 C ˆ 50 C Humidité de stockage et opération 0 a 95 Résolution d affichage once gramme incrémente 10 grammes Accuratesse 0 05 de la lecture ou 0 25 oz 10 g selon le plus élevé Source Deux batteries 9V alkaline ANSI 1604AC IEC6LR61 Batterie 30 heures de marche Indicateur de charge indication par graphique a trois segments Pression maximale 34 bar Poids 3kg 900 www GlobalTestSupply com Find ...

Страница 7: ...r nière mesure TARE Presser la touché pendant une seconde dans le mode WEIGHING Ceci remet la balance a 00 00 dans le SETTING LeTARE est inactif dans le mode HOLD Dans le mode SET la touche TARE remettra le montant programmé à zéro GO HOLD Commence le CHARGING charge or RECOVER Y récupération conforme aux données entrées en mémoire après avoir activé la touche SET L entrée des données détermine l ...

Страница 8: ...ignal sonore l indique ainsi que l écran qui affichera le poids symbole à l écran Pour une seconde charge il faudra activer a deux fois la touche SET RESET et suivre les instructions en point 6 notez que les donnée précédentes seront affichés B Au cas ou le réfrigérant n est plus transvasé pendant 3 minutes bien que le poids enregistré n est pas atteint un signal sonore intermittent est audible L ...

Страница 9: ...ir si le poids maximal du cylindre ne surpasse pas le poids maximal admis 10 Si pendant le processus de récupération le poids brut dépasse le poids maximal du cylindre la valve solenoid se fermera prévenant l éventuel surcharge du cylindre Remplacez le cylindre par un cylindre vide et reprenez à partir du point 4 Dés que la CHARGE est complète retirer le cylindre de la plate forme et tenir la touc...

Страница 10: ... off et Smart Awake Auto Shut Off Arrêt automatique après 10 minutes si le poids sur la plate forme ne change pas plus de 30g dans cette periode Note il n y a pas de shut of f dans le mode de récupération et charge Smart Awake Lorsque la fonction d arrêt automatique est activée la lecture de poids LAST est stock ée en mémoire Échelle de temps suivante est activée l échelle reprendra son fonctionne...

Отзывы: