CHARGE MODE

1) Place the Scale on a level, rigid surface.

2) Press POWER key to turn the unit ON, it 

zeroes out any weight on platform.

3) Select the desired unit by pressing UNITS key.

4) Place cylinder on scale and connect scale as shown in Figure 1.

5) Open the cylinder liquid valve and all other valves that are in the 

charging pathway.

6) Press the SET key and the display will show: 

READY

READY

000 lbs               

“000 kg  

00.00 oz “         OR    

0000 g “.

Note: READY appears on the top right hand cor ner of the screen.

Press and hold down  the       or       keys to program the charge amount.

7) Press the GO key to begin the CHARGE. While in CHARGE, pressing the 

RESET

key will stop and 

cancel the CHARGING process and go back to normal mode by displaying the net weight. The 

HOLD

key may be depressed at any time during the CHARGE or RECOVER

Y mode. When this key is 

depressed, the solenoid valve will close, and display will read the net weight.  

The amount of

refrigerant transferred at the time the 

HOLD

key is activated is stored in the memory . While in 

HOLD

mode, any adjustments such as replacing a container , or tightening loose connections may be done. 

When the adjustments are complete, the program may be resumed at the point it was interrupted by 

depressing the 

GO

key; or press 

SET

once to adjust the desired weight if the user wants to change 

the setting and press 

GO

again to resume.

8) The refrigerant is now being dispensed by the opening of an electro-mechanical solenoid valve. 

The unit will now proceed to either item “A” or ”B”.

A. When the programmed charge amount is reached, the CC800A will sound a  continuous beep and 

the display will show the amount that has been charged (“-”

sign on the display). Set up another 

charging process by pressing 

SET/RESET

twice and follow the instruction in STEP 6; note that the 

previous setting amount will show.

B. If the refrigerant is no longer being dispensed after 3 minutes*, but the programmed charge amount 

has not been met, the CC800A will sound an intermittent beep.  The user will need to push the HOLD 

key and exchange the empty virgin tank with a full one (or correct flow path restriction). Push the GO 

key to resume charging.

Note: Watch Dog timer turn ON right after pressing GO; after 3 minutes without a weight change of 1 oz. (30 grams) 

the unit begins to beep inter mittently, at which point the user may pr ess HOLD to review the problem.

When CHARGE mode has been completed, remove the cylinder from the platform, press and hold the 

POWER key for 1 second to turn the unit OFF .

OPERATION

The CC800A can be used for W eighing, Charging and Recovering refrigerants.  The following are

instructions and information on how to use the CC800A

for common refrigeration service functions.

WEIGH MODE

1) Place the Scale on a level, rigid surface.

2) Press POWER key to turn the unit ON, any weight on platform will  be set to zero (T are).

3) Select the desired unit by pressing UNITS key.

4) Place the object that is to be weighed on the platform.

5) Gross weight will display.

6) When weighing has been completed, remove the object, press and hold the POWER key for 1 

second to turn the unit OFF.

Figure 1

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание PRO-SET CC800A Series

Страница 1: ...idity 0 to 95 non condensing Display Resolution oz gm Increments 25 ounces 10 grams Accuracy 0 05 of reading or 25 oz 10 grams whichever is greater Operating Power Source Two 9V alkaline battery ANSI 1604AC IEC 6LR61 Battery Life 30 hours of continuous use Battery Indicator Battery symbol with 3 segment Power Level Bar Graph Maximum Working Pressure 500 PSIG 34 bar Max Operating Pressure Different...

Страница 2: ...or 1 second to tare while the unit is in the WEIGHING mode It returns the display to 00 00 in the SETTING mode The TARE key is not active while the unit is in the HOLD mode In the SET mode the TARE key will reset the programmed amount to zero GO HOLD Initiates the CHARGING or RECOVER Y modes per the data entered after pushing the SET key The data entered will determine how long the solenoid valve ...

Страница 3: ...item A or B A When the programmed charge amount is reached the CC800A will sound a continuous beep and the display will show the amount that has been charged sign on the display Set up another charging process by pressing SET RESET twice and follow the instruction in STEP 6 note that the previous setting amount will show B If the refrigerant is no longer being dispensed after 3 minutes but the pro...

Страница 4: ...e total weight of the cylinder does not exceed the maximum allowable amount 10 If during the recovery process the gross weight exceeds the programmed maximum tank weight the solenoid valve will close preventing the additional filling of the refrigerant cylinder Exchange the cylinder with an empty one and proceed back to STEP 4 When CHARGE mode has been completed remove the cylinder from the platfo...

Страница 5: ...unds makes the unit display OL Auto Shut Off and Smart Awake features Auto Shut Off The unit will automatically shut off after 10 minutes if the weight on its platform does not change by more than 1oz 30g in that period of time Note Auto Shut Off is disabled in the RECOVERY and CHARGE modes Smart Awake When Auto Shut Off feature is active the last weight reading is stored in memory Next time scale...

Страница 6: ...ration 10 C ˆ 50 C Humidité de stockage et opération 0 a 95 Résolution d affichage once gramme incrémente 10 grammes Accuratesse 0 05 de la lecture ou 0 25 oz 10 g selon le plus élevé Source Deux batteries 9V alkaline ANSI 1604AC IEC6LR61 Batterie 30 heures de marche Indicateur de charge indication par graphique a trois segments Pression maximale 34 bar Poids 3kg 900 www GlobalTestSupply com Find ...

Страница 7: ...r nière mesure TARE Presser la touché pendant une seconde dans le mode WEIGHING Ceci remet la balance a 00 00 dans le SETTING LeTARE est inactif dans le mode HOLD Dans le mode SET la touche TARE remettra le montant programmé à zéro GO HOLD Commence le CHARGING charge or RECOVER Y récupération conforme aux données entrées en mémoire après avoir activé la touche SET L entrée des données détermine l ...

Страница 8: ...ignal sonore l indique ainsi que l écran qui affichera le poids symbole à l écran Pour une seconde charge il faudra activer a deux fois la touche SET RESET et suivre les instructions en point 6 notez que les donnée précédentes seront affichés B Au cas ou le réfrigérant n est plus transvasé pendant 3 minutes bien que le poids enregistré n est pas atteint un signal sonore intermittent est audible L ...

Страница 9: ...ir si le poids maximal du cylindre ne surpasse pas le poids maximal admis 10 Si pendant le processus de récupération le poids brut dépasse le poids maximal du cylindre la valve solenoid se fermera prévenant l éventuel surcharge du cylindre Remplacez le cylindre par un cylindre vide et reprenez à partir du point 4 Dés que la CHARGE est complète retirer le cylindre de la plate forme et tenir la touc...

Страница 10: ... off et Smart Awake Auto Shut Off Arrêt automatique après 10 minutes si le poids sur la plate forme ne change pas plus de 30g dans cette periode Note il n y a pas de shut of f dans le mode de récupération et charge Smart Awake Lorsque la fonction d arrêt automatique est activée la lecture de poids LAST est stock ée en mémoire Échelle de temps suivante est activée l échelle reprendra son fonctionne...

Отзывы: