CPI User Manual for Lithium Ion Online UPS
04/22v.1
Page 17
Interface
Settings
Parameter 2:
Enable or disable ECO function. You may choose
the following two options: mode enable
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
• 04: ECO enable/disable
Interface
Settings
Parameter 2:
Set the acceptable high voltage point and low
voltage point for ECO mode by pressing Down key or Up key.
HLS:
High loss voltage in ECO mode in parameter 2.
For 230 Models, the setting range in parameter 3 is from +7V to
+24V of the nominal voltage. (Default: +12V)
For 120 Models, the setting range in parameter 3 is from +3V to
+12V of the nominal voltage.
(Default: +6V)
LLS:
Low loss voltage in ECO mode in parameter 2.
For 230 Models, the setting range in parameter 3 is from -7V to
-24V of the nominal voltage.
(Default: -12V)
For 120 Models, the setting voltage in parameter 3 is from -3V to
-12V of the nominal voltage.
(Default: -6V)
• 05: ECO voltage range setting
Interface
Settings
Parameter 2:
Enable or disable Bypass function. You may
choose the following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
• 06: Bypass enable/disable when UPS is off