READ CAREFULLY BEFORE  INSTALLING UNIT

These installation instructions are a general guide, and do not supersede applicable local codes and ordinances.  Before planning or
making the installation, be sure it complies with all phases of the local heating codes.  Or, in the absence of local codes, with the latest
edition of the National Fuel Gas Code, ANSI.Z223.1.  In Canada, see the current installation code CAN1-B149.

The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with
the latest edition of the National Electrical Code ANSI/NFPA No. 70.  In Canada, see the current Canadian Electrical Code
C5AC22.1.

The ANSI standards are available from the American Gas Association, 1515 Wilson Blvd., Arlington, Virginia 22209.

The NFPA standards are available from the National Fire Protection Association, Batterymarch Park, Quincy, MA. 02269.

Canadian standards are available from International Approval Services,178 Rexdale Blvd.,Etobicoke,Ontario, Canada

 M9W 1R3.

NOTE:  If optional rear register kit is to be used, see supplemental installation instructions (No. 84504) and section marked
“Special Instructions for Rear Register Kit Application” prior to installation of Rough-In.

INTRODUCTION

THIS IS A GAS-FIRED, GRAVITY VENTED WALL FURNACE THAT WILL OPERATE SAFELY AND PROVIDE AN
EFFICIENT SOURCE OF HEAT WHEN INSTALLED, OPERATED AND MAINTAINED AS RECOMMENDED IN THESE
INSTALLATION AND OPERATING INSTRUCTIONS.  READ THESE INSTRUCTIONS THOROUGHLY BEFORE
INSTALLING, SERVICING, OR USING THE APPLIANCE.  IF YOU DO NOT UNDERSTAND ANY PART OF THESE
INSTRUCTIONS, CONSULT LOCAL AUTHORITIES, OTHER QUALIFIED INSTALLERS, SERVICE AGENCIES, THE GAS
SUPPLIER OR THE MANUFACTURER.

SPECIFICATIONS

Your vented wall furnace comes packed in a single carton.  (For wall thermostat models that includes the thermostat, thermostat
wire, and insulated staples).  Before installing the wall furnace check the rating plate to verify that the Model Number is correct
and that the wall furnace is equipped for the type gas you intend to use.

Model

Type

Type

BTU/Hr.

Vent

Gas

Shpg.

REAR  REG. KIT

 FAN KIT

No.

Control

Gas

Input

 Size

Inlet

FINISHED DIMENSIONS

Wt.

Model

Weight

 Model

Wt.

SINGLE WALL FURNACE

W251F Snap Bulb

Nat.

25,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

90  Lbs.

40542

5 Lbs.    WFF81   10 lbs.

W255F Wall Stat

Nat.

25,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

90  Lbs.

40542

5 Lbs.    WFF81   10 lbs.

W252F Snap Bulb

L.P.

25,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

90  Lbs.

40542

5 Lbs.    WFF81   10 lbs.

W256F Wall Stat

L.P.

25,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

90  Lbs.

40542

5 Lbs.    WFF81   10 lbs.

W351F Snap Bulb

Nat.

35,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

90  Lbs.

40542

5 Lbs.    WFF81   10 lbs.

W355F Wall Stat

Nat.

35,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

90  Lbs.

40542

5 Lbs.    WFF81   10 lbs.

W352F Snap Bulb

L.P.

35,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

90  Lbs.

40542

5 Lbs.    WFF81   10 lbs.

W356F Wall Stat

L.P.

35,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

90  Lbs.

40542

5 Lbs.    WFF81   10 lbs.

DUAL WALL FURNACE

W501F Snap Bulb

Nat.

50,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

134 Lbs. N/A

N/A

WFF81   10 lbs.

W505F Wall Stat

Nat.

50,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

134 Lbs. N/A

N/A

WFF81   10 lbs.

W502F Snap Bulb

L.P.

50,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

134 Lbs. N/A

N/A

WFF81   10 lbs.

W506F Wall Stat

L.P.

50,000

4 ”

1/2”

16-1/2”Wx68”Hx6-1/2”D

134 Lbs. N/A

N/A

WFF81   10 lbs.

One or two fan kits may be used on dual-wall furnace.

CONTENTS

Page 2

Introduction................................................

2

Rear Register Kit Instructions....................................

 9

Specifications..............................................

2

Lighting Instructions...................................................  10/11

Safety Rules.................................................

3

Pilot Adjustment...........................................................

12

Clearances....................................................

3

Burner Flame Adjustment............................................

12

Controls........................................................

3

Maintenance Instructions...........................................

12

Combustion & Ventilation Air...................

4

WFF81 Fan Instructions..............................................  13/14

Venting..........................................................

5,6

Trouble Shooting Chart................................................ 15/16

Rough-In Instructions................................

6

Parts Drawing................................................................

17

Installation....................................................

8

Parts List........................................................................

18

Wiring Instructions.....................................

9

Warranty........................................................................

20

Содержание W251F and

Страница 1: ...fthisoccurs This heater may be installed without recessing into stud space by using optional FSK Free Standing Kit Thisunitisnotapprovedforinstallationinmobilehomes greenhouses orenvironmentsinvolvingdusty wet corrosive orexplosiveconditions Suchconditionswillinvalidatethewarrantyandmaycreateunsafeconditions THIS UNIT IS NOT TO BE INSTALLED IN MOBILE HOMES WARNING If the information in this manual...

Страница 2: ... carton For wall thermostat models that includes the thermostat thermostat wire and insulated staples Before installing the wall furnace check the rating plate to verify that the Model Number is correct and that the wall furnace is equipped for the type gas you intend to use Model Type Type BTU Hr Vent Gas Shpg REAR REG KIT FAN KIT No Control Gas Input Size Inlet FINISHED DIMENSIONS Wt Model Weigh...

Страница 3: ...dividual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of psig The appliance must be isolated from the gas supply piping system by closing its individual manual shutoffvalveduring any pressuretesting ofthegassupply piping system at test pressures equal to or less than psig The minimum inlet pressure in th...

Страница 4: ...stud and joist spaces cannot be blocked with insulation or other objects Each of these openings using vertical ducts shall have a minimum free area of one square inch per 4 000 btu hr of total input rating of all gas appliances See Figure B and C If horizontal ducts are used the minimum free area shall be one square inch per 2 000 btu hr of total input rating of all gas appliances Fresh make up ai...

Страница 5: ...locationofthemanualresetblocked flue switch To reset the switch insert a slender rigid object i e screwdriver through the front panel louvers and push the reset button down See Figure B 1 However you may have toremovethefrontpanel thenresettheswitchandreinstallthe front panel to relight heater If homeowner experiences this problem the vent system must be checked and corrected NOTE A pre existing v...

Страница 6: ...ne of left stud either 4 above top of floor plateor4 torightofleftstudthroughfloor plate See Figure 1 located on Page 7 Page 6 FIGURE C Installation of B W Gas Vent for one story buildings or for first floor of multi story buildings Ceiling plate spacers to center B W gas vent in stud space nail securely at both ends Plate cut away for full width of stud space to provide ventilation Studs on 16 in...

Страница 7: ...STEP 5 If the vent continues through additional stories within the 2x4 stud space then fire stop spacers must be installed at the second and subsequent ceiling levels See Figure D FIGURE D Installation of B W gas vent for each subsequent ceiling or floor level of multi story buildings Firestop spacers supplied by manufacturer of B W gas vent Plate cut away to provide passage of B W gas vent Nail f...

Страница 8: ...nces require that the manual valve be located outside theappliance STEP 8 Makegasconnectionusingconnectorthe samesizeasgasconnectionoffurnace CHECK ALL CONNECTIONS FOR GAS LEAKS WITH LEAK DETECTOR SOLUTION DO NOT USE OPEN FLAME STEP 9 For wall thermostat units see Wiring section for thermostat connections Make sure all connections are correct and connector stems arenottouching STEP10 Tofastenfront...

Страница 9: ...me stud space with vent Conceal wire inside wall or secure to wall with insulated staples that are included YOUR FURNACE MAY BE EQUIPPED WITH EITHER A WALL THERMOSTAT Figure 2 OR SNAP BULB BUILT IN THERMOSTAT Figure 1 CONTROL CHECK THE CONTROL ASSEMBLY TO DETERMINE WHICH WIRING EXAMPLE TO USE SPECIAL INSTRUCTIONS FOR REAR REGISTER KIT APPLICATION Figures 6 and 7 line drawings of rear register open...

Страница 10: ... Read the information on the safety label 2 Set thermostat to it s lowest setting 3 Open cabinet door 4 Depress and turn gas control knob clockwise to OFF 5 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the information on the safety label If you don t smell gas go to the next step 6 Locate the pilot Follow metal pilot tube fr...

Страница 11: ...re control knob to LO 4 Depress and turn gas control knob clockwise to OFF 5 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the information on the safety label If you don t smell gas go to the next step 6 Locate the pilot Follow metal pilot tube from gas control 7 Turn gas control knob counterclockwise to PILOT 8 Depress gas c...

Страница 12: ...ating air passageways and venting systems of the appliance be kept clean 2 If the appliance has been equipped with the optional WFF81 C fan kit assembly the bearings of the motor should be oiled every six months with approximately 2 drops of S A E 20 oil 3 The appliance area must be kept clear and free of any combustible materials gasoline and other flammable vapors and liquids 4 It is essential t...

Страница 13: ... the wall Mark a small vertical line which aligns with the slot located toward the rear of the fan kit casing STEP 3 Using the four one inch screws provided secure the wall mounting bracket to wall 1 8 below the horizontal line Fan attachment bracket must be up and threaded nut sert aligned with the small vertical line Note Anchors not provided may be required STEP 4 Remove junction box and connec...

Страница 14: ...ACK BLACK MOTOR WHITE GREEN GROUND WIRE L2 White L1 Black 115 VAC 60 HZ Less than 12 Amps If any of the original wire as supplied with this appliance must be replaced it must be replaced with type thermoplastic 105 degree C wire or its equivalent WFF81 C WIRING SCHEMATIC Page 14 ...

Страница 15: ...burner ports Do not enlarge ports 3 Low gas pressure 3 Check gas supply pressure 4 Pilot decreases in size when main burners 4 Supply piping is inadequately sized Consult local come on gas utility or competent installer 5 Air shutter open too far 5 Close air shutter to proper setting as outlined in these instructions slight yellow tipping is allowable on L P Gas See Page 12 6 Drafts around applian...

Страница 16: ...tem system A Vent too short A The vent should terminate a minimum of 12 feet above the floor See Figure 2 Also the top of the vent must be at least 2 foot above any obstacle within a 10 foot radius including the roof See Figure A B Restriction in B All type B vents shall extend in a generally vertical direction with offsets not exceeding 45 vent system degrees except that a vent system having not ...

Страница 17: ... change without notice All prices are F O B factory GRAVITY WALL FURNACE LIST PRICES JUNE 2004 3 11 2 8 9 46 1 7 12 10 47 4 1 7 A 47 9 46 3 2 11 8 4 8 2 11 9 10 7 12 1 57 59 60 55 58 56 FSK A FREESTANDING KIT BURNER ASSEMBLY SINGLE WALL FURNACE 38 39 35 29 36 42 31 30 32 34 44 19 14 18 15 16 17 21 20 13 48 49 WFF81 C FAN KIT Used on Single and Dual Wall models REAR REGISTER KIT Used on Single Wall...

Страница 18: ...Burner Steel 29 84070 39 30 84070 39 30 Damper Spring 23 40377 1 90 Burner Steel WITH Frame Assembly 24 40365 11 60 Carry Over Tapping 29A N A N A 84071 51 40 Register Chain 25 40379 1 30 Burner Restrictor Plate N A N A N A 40220 2 10 Bell Pull 26 85003 1 10 for W502F and W506F Register Assembly 27 40355 18 50 Orifice Coupling 30 84631 4 50 N A N A Installation Manual N A 84504 N C Elbow 3 8 90 De...

Страница 19: ...r death IF YOU SMELL GAS DON T LIGHT IT IF YOU CAN T LIGHT IT DON T FIGHT IT THIS IS NOT AN ADVERTISEMENT WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire departmen...

Страница 20: ...defective to the manufacturer for inspection to enable the manufacturer to determine if the claimed defect is covered by this warranty No charges for freight labor or other expenses incurred in the repair removal or replacement of any product or component claimed to be defective will be paid by the manufacturer to the user and the manufacturer will not be liable for any expenses incurred by the us...