Page 6
1019061-B
CLEARANCES -
Continued
1.
If the wall furnace is installed directly on carpeting, tile or any combustible material other than wood flooring, the wall furnace
shall be installed on a metal plate or wood panel secured to the floor, extending the full width and depth of the wall furnace.
2.
RESIDENTIAL GARAGE INSTALLATION:
Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located
not less than 18 inches (46cm) above the floor. Such equipment shall be located, or protected so it is not subject to damage
by a moving vehicle. Use care in selecting a good location within the garage.
•
DO NOT
locate the appliance where heated air will be directed onto a nearby parked vehicle.
•
Paint may discolor or rubber may harden and crack.
•
DO NOT
allow heated discharge air to blow directly onto open or closed containers of paint, gasoline
or other liquids having flammable vapors.
SPECIAL PRECAUTIONS
Due to high temperatures the appliance should be located out of
traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface
temperature and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the
same room as the appliance.
Clothing or other flammable material should not be placed on or near
the appliance.
Any safety screen, guard, or casing top removed for servicing a room
heater must be replaced prior to operating the appliance.
Do not use this heater if any part has been under water. Immediately
call a qualified service technician to inspect the heater and to replace
any part of the control system and any gas control which has been
under water.
LOCATION
1) The wall furnace must be
installed on an outside wall.
2) For optimal heat distribution,
locate furnace as centrally as
possible in the area to be heated
and where occupants may move
about freely without coming into
contact with the grille.
3) If the furnace is installed in a
basement, a 12” clearance must
be maintained between ground
level and the bottom of the vent
cap. Do not install furnace where
vent cap will terminate in a
window well or any other opening
below ground level.
ALL VENT CAPS
FIG. 3
9”
Min.
12”
Min.
18” Minimum
12” Minimum
FIG. 2
CDV25-D / CDV30-D
CDV15-D
FIG. 1
Left Side W
all
Ceiling
1”
24”
1/2”
Floor
Right Side W
all
1”
Left Side W
all
Ceiling
Floor
0”
1”
4”
30”
Right Side W
all