![COX EC80 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/cox/ec80/ec80_user-manual_2674291026.webp)
Profile Programming
April 2019
CXX-UM-03060-EN-01
Page 26
c With the Roshko/Strouhal values highlighted, right-click in the shaded area
and click
Copy
to place data onto the clipboard Alternatively, with the data
highlighted, press
Ctrl+C
to copy the data to the clipboard
2 Switch to or re-open the GUI and right-click
IDX
in the upper left corner of
the table
3 Select
Paste Grid
to copy the raw data from the clipboard to the table
Figure 15: Pasted table
Linearization
The
Linearization
process takes a raw, non-linear output from a turbine meter and
performs mathematical calculations to provide a linearized output The EC80 Flow
Processor uses the Roshko/Strouhal method for correlating the meter’s volumetric
flow rate and reflects the sum of all rotors In a single rotor application, the sum
Roshko and sum Strouhal equate to the correlation of a single rotor In a dual rotor
application, the sum Roshko and sum Strouhal equate to the correlation of both
rotors, summed together
The minimum number of IDX (X,Y) entries for the linearization table is 2 The
maximum number of IDX (X,Y) entries for the linearization table is 200 Fill out the
table according to instructions in
In addition to the Linearization table itself, a number of additional fields on the
linearization tab can be changed Although not typically modified from factory
settings, they perform additional advanced operations in the EC80 Flow Processor
Field
Function
Alpha
Corresponds to the coefficient of thermal expansion of the flow meter housing This field
is factory configured for the thermal expansion of stainless steel The thermal expansion
coefficient for stainless steel is 9 6 × 10
-4
or 0 0000096 Other expansion coefficients are
available from the factory
Reference
Temp
The reference temperature, in degrees Fahrenheit, in which the calibration data was
obtained Typical calibration reports state the reference temperature in which the data
was obtained, and should be the same as the temperature in which the Roshko/Strouhal
calibration data was obtained
Rotor
Frequency
Cutoff
These fields limit the output of the flow processor to a minimum and maximum
frequency threshold If rotor frequency decreases below the minimum flow rate or over
the maximum flow rate, the flow processor stops outputting a flow rate The left column
corresponds to the rotor frequency of the A rotor (Upstream), and the right column is for
the B rotor (Downstream) In single rotor applications, only the left field is used