COX EC80 Скачать руководство пользователя страница 26

Profile Programming

April 2019

CXX-UM-03060-EN-01

Page 26 

c   With the Roshko/Strouhal values highlighted, right-click in the shaded area 

and click 

Copy

 to place data onto the clipboard  Alternatively, with the data 

highlighted, press 

Ctrl+C

 to copy the data to the clipboard 

2   Switch to or re-open the GUI and right-click 

IDX

 in the upper left corner of 

the table 

3   Select 

Paste Grid

 to copy the raw data from the clipboard to the table 

Figure 15:  Pasted table

Linearization

The 

Linearization

 process takes a raw, non-linear output from a turbine meter and 

performs mathematical calculations to provide a linearized output  The EC80 Flow 

Processor uses the Roshko/Strouhal method for correlating the meter’s volumetric 

flow rate and reflects the sum of all rotors  In a single rotor application, the sum 

Roshko and sum Strouhal equate to the correlation of a single rotor  In a dual rotor 

application, the sum Roshko and sum Strouhal equate to the correlation of both 

rotors, summed together 
The minimum number of IDX (X,Y) entries for the linearization table is 2  The 

maximum number of IDX (X,Y) entries for the linearization table is 200  Fill out the 

table according to instructions in 

“Table Data Entry” on page 25

 

In addition to the Linearization table itself, a number of additional fields on the 

linearization tab can be changed  Although not typically modified from factory 

settings, they perform additional advanced operations in the EC80 Flow Processor 

Field

Function

Alpha

Corresponds to the coefficient of thermal expansion of the flow meter housing  This field 

is factory configured for the thermal expansion of stainless steel  The thermal expansion 

coefficient for stainless steel is 9 6 × 10

-4

 or 0 0000096  Other expansion coefficients are 

available from the factory 

Reference 

Temp

The reference temperature, in degrees Fahrenheit, in which the calibration data was 

obtained  Typical calibration reports state the reference temperature in which the data 

was obtained, and should be the same as the temperature in which the Roshko/Strouhal 

calibration data was obtained 

Rotor 

Frequency 

Cutoff

These fields limit the output of the flow processor to a minimum and maximum 

frequency threshold  If rotor frequency decreases below the minimum flow rate or over 

the maximum flow rate, the flow processor stops outputting a flow rate  The left column 

corresponds to the rotor frequency of the A rotor (Upstream), and the right column is for 

the B rotor (Downstream)  In single rotor applications, only the left field is used 

Содержание EC80

Страница 1: ...CXX UM 03060 EN 01 April 2019 User Manual Flow Processor EC80...

Страница 2: ...Flow Processor EC80 April 2019 CXX UM 03060 EN 01 Page ii...

Страница 3: ...ing and Jumpers 12 RM1 12 RM2 14 XP1 15 Dimensions 17 RM1 Configuration 17 RM2 Configuration 17 XP1 Configuration 18 Specifications 19 Using the IFC Software 20 Password Initialization 20 Establish Li...

Страница 4: ...quid Pressure Compensation 35 Hardware Configuration 36 Model Information 36 General Hardware Information 36 Oscillation 37 Meter Selection BUS ID 37 Real time Monitoring 38 Real Time Report Display 3...

Страница 5: ...odes Failure to read and follow these instructions can lead to misapplication or misuse of the flow processor resulting in personal injury and damage to equipment Safety Symbol Explanations DANGER IND...

Страница 6: ...uhal Roshko algorithms for a more comprehensive compensation method taking into consideration all the secondary effects to which the meter is sensitive like the expansion and contraction of the meter...

Страница 7: ...ng is not in excess of the flow processor s rating A setting over the rating will cause the flow processor to fail and not be covered under the warranty Tighten all terminal block connections with rea...

Страница 8: ...N SHOWN PT02E 12 8P NOT INCLUDED CABLE NOT INCLUDED 2 4 2X 4 92 4X 17 2X 1 42 Figure 2 RM1 Configuration RM2 N CONFIGURATION SHOWN IS TYPICAL FOR RF INPUT CABLE NOT INCLUDED CABLE NOT INCLUDED PT02E 1...

Страница 9: ...Installation Page 9 CXX UM 03060 EN 01 April 2019 XP1 IS TYPICAL FOR RF INPUT CONFIGURATION SHOWN 2X 4 7 B 9541 CABLE WITH 6907K13 CORD GRIP NOT INCLUDED Figure 4 XP1 Configuration...

Страница 10: ...r is supplied with a 10 k thermistor but can be jumper configured for 0 5V DC 0 10V DC or 4 20 mA temperature transducers Consult the factory if you need to incorporate the analog input for reasons ot...

Страница 11: ...Mass Raw Frequency Rotor A Raw Frequency Rotor B Raw Sum Frequency A Frequency B Dual Rotor Applications Total Flow Accumulation Analog Linearized Flow Rate Temperature A P N M L K J H F E D C B R Fi...

Страница 12: ...ON SIGNAL J1 J4 J5 WIRE COLOR PINOUT N A VDC PWR 1 RED A VDC PWR RETURN 2 BLK B N A N A RS 485 5 WHT C N A RS 485 6 WHT BLK D N A Hz RAW A OUT 1 ORG E N A Hz RAW B OUT 2 RED WHT F N A Hz GND 3 ORG BLK...

Страница 13: ...RF PICKOFF A 1 A WHT RF A RETURN 2 B BLU RF PICKOFF B 3 C BLU RF B RETURN 4 D GRN RF PICKOFF Q 5 N A GRN RF Q RETURN 6 N A ORG RTD EX 4 E ORG RTD 3 F ORG RTD 2 G ORG RTD EX 1 H JMP 1 Pickoff Jumper Ta...

Страница 14: ...RG E N A Hz RAW B OUT 2 RED WHT F N A Hz GND 3 ORG BLK H Hz FREQ 1 OUT 4 GRN J Hz FREQ 2 OUT 5 GRN WHT K N A Hz GND 6 GRN BLK L V ANALOG 1 VOLTAGE OUT 9 BLU M V ANALOG 2 VOLTAGE OUT 8 BLU WHT N N A N...

Страница 15: ...J5 JMP B JMP A JMP C EC80 Flow Computer to B 9541 Cable EC B 9541 SCALING UNITS FUNCTION SIGNAL J1 J4 J5 WIRE COLOR N A VDC PWR 1 RED VDC PWR RETURN 2 BLK N A N A RS 485 5 WHT N A RS 485 6 WHT BLK N...

Страница 16: ...ROTOR B 4 OHMS JMP B OFF ROTOR B 10 OHMS JMP C ON ROTOR Q 4 OHMS JMP C OFF ROTOR Q 10 OHMS Flow Meter to EC80 Flow Computer WIRE COLOR FUNCTION SIGNAL J2 J5 WHT RF PICKOFF A 1 WHT RF A RETURN 2 WHT R...

Страница 17: ...nt View Side View A 3 40 in 86 36 mm 1 22 in 30 99 mm B 2 38 in 60 45 mm 5 43 in 137 92 mm C 0 16 in 4 06 mm RM2 Configuration A B C C B A D Front View Side View Front View Side View A 4 75 in 120 65...

Страница 18: ...l 2019 CXX UM 03060 EN 01 Page 18 XP1 Configuration A C B A B C Front View Side View Front View Side View A 4 70 in 119 38 mm 2 71 in 68 83 mm B 2 80 in 71 12 mm 4 70 in 119 38 mm C 2 80 in 71 12 mm 0...

Страница 19: ...esolution 12 bit 1 4096 Input Impedance 100k Ohms Frequency Output Two Independent Channels 0 5V TTL 1 20 000 Hz square wave 50 duty cycle Minimum Load Impedance 10k Ohm Analog Outputs Two Independent...

Страница 20: ...ily remembered For example User Name admin Password admin Un installing or re installing does not erase any set users To set the password for the first time or to add a user name later 1 Click the Opt...

Страница 21: ...e software can also choose to add new users Establish Link Via RS485 You need to establish communication between the PC and the flow processor hardware before you can program the flow processor using...

Страница 22: ...Save Open Figure 11 New Load and Save buttons Create a new profile by going to File New or clicking the New button on the toolbar Save a new profile by selecting File Save As and then choosing a save...

Страница 23: ...ied any of the data entry look up tables can be modified Make sure to follow these guidelines when importing or exporting the data Always erase the cell s entirely before entering data so the new data...

Страница 24: ...s interpolate between points Data tables do not extrapolate beyond the minimum and maximum values The flow processor holds the last value in the table if the threshold is exceeded Flow processors with...

Страница 25: ...is procedure saves time and provides data accuracy To import multiple values into the interface using Microsoft Excel 1 In Excel highlight a minimum of 2 X Y pairs and a maximum of up to 200 X Y pairs...

Страница 26: ...rding to instructions in Table Data Entry on page 25 In addition to the Linearization table itself a number of additional fields on the linearization tab can be changed Although not typically modified...

Страница 27: ...ease contact Badger Meter as a large database of liquid properties has been generated To select the Auto Viscosity feature 1 Click the Linearization tab on the GUI interface main screen Figure 16 Line...

Страница 28: ...one rotor to the other you can determine if bearing failure pickoff failure or even liquid particulates are hindering meter performance This same method is also used to determine viscosity Load Rotor...

Страница 29: ...calibration of the flow processor s temperature input device Obtain a temperature profile by testing the temperature sensor being used The temperature profile is unique to the individual sensor To ca...

Страница 30: ...ed to be the same 2 Fill the tables according to instructions in Table Data Entry on page 25 The first entry typically corresponds to zero flow and is set to zero Hertz while the last entry is typical...

Страница 31: ...e drop down menu 3 Fill the tables according to instructions in Table Data Entry on page 25 The first entry typically corresponds to zero flow and is set to 0V DC or mA Calibrate Analog Channels In ad...

Страница 32: ...s analog inputs may be used for other functions Consult the factory if your application includes an analog input The electrical waveform needs to match your board s jumper configuration See Wiring and...

Страница 33: ...ave Liquid Tables button to Save the new liquid When you change the data in the table or re name an existing liquid the software shows additional options in the menu bar Save Liquid Tables Delete Sele...

Страница 34: ...ick the bullet next to the ASTM or Andrade method for computation of viscosity The ASTM equation is typically more accurate 3 Input the lesser temperature value and the corresponding viscosity value i...

Страница 35: ...emperature vs Density table and then multiplied by the volumetric flow rate to obtain the mass flow rate MassFlowRate VolumetricFlowRate Density Leave these fields blank or clear the table using the I...

Страница 36: ...Identifies the configuration of EC80 Flow Processor for which the profile was designed IFC SN Provides traceability of an individual EC80 Flow Processor and associated documentation Meter Model No Id...

Страница 37: ...inputting a value to the processor Low Flow Cutoff Numeric Entry GPM The low flow cutoff omits erroneous data in the low flow region of a turbine meter Near zero state conditions or pulsating flow may...

Страница 38: ...r REAL TIME MONITORING The EC80 Flow Processor outputs real time values via the established RS485 communication Parameters and variables can be viewed in the Status section of the IFC15 GUI The Status...

Страница 39: ...ewhere in that table s data Use the IFC GUI data logging feature to create a log of selected data measured over a period of time The GUI sends information to a tab delimited file The software measures...

Страница 40: ...logging when you click Start The software logs one sample s worth of data and stops at the set interval in the sample rate field Viewing Log To view the log being populated click View You will be tra...

Страница 41: ...You can search to see which flow processors are currently connected in the loop Since each flow processor has its own Bus ID each flow processor appears on this display Information such as the Bus ID...

Страница 42: ...cation requires it Consult your sales representative if this feature interests you Figure 38 Commands menu CONFIGURATION OPTIONS Access the options menu either by clicking the Options Icon or navigati...

Страница 43: ...Style Communication Comm Use the Communications tab to establish communications with the flow processor See Establish Link Via RS485 on page 21 or Establish Link Via Ethernet on page 22 for more infor...

Страница 44: ...de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus...

Отзывы: