LEMCOM CANopen®
– User manual
Detailed
description of CANopen objects
COVAL
– LMCOP-EN-A-1155UM0068
46/49
12.34
210Dh – Valve status if communication is lost
In the event that the communication is lost (PLC
LEMCOM master module or LEMCOM master
module
LEMCOM secondary modules), the behavior of the suction and blowing valves can be
defined.
The following modes are possible:
MODE
Byte 0
Detailed operation
MD1
00h
Status of solenoid valves prior to loss of communication is preserved
MD2
01h
Vacuum command active / blowing command inactive
MD3
02h
Vacuum command inactive / blowing command active
MD4
03h
Vacuum and blowing commands inactive
MD5
04h
Vacuum inactive, then blowing for 2 s, followed by vacuum and blowing
inactive
Table 17
– Valve status in case of loss of communication
SDO command:
CAN-ID
(600h+ID)
620h
Command
2Fh
Object L
0Dh
Object H
21h
Subindex
Module no.+1
Byte 0
00h
Byte 1
00h
Byte 2
00h
Byte 3
00h
The
subindex
is used to define the module to be set (from 1 to 16):
- Subindex = 0x01
set VALVE_STATUS on master module (address #0)
- Subindex = 0x02
set VALVE_STATUS on secondary module at address #1
-
…
- Subindex = 0x10
set VALVE_STATUS on secondary module at address #15
Byte 0
is used to define the operating mode of the valves according to the above table. Mode MD1
is the default operating mode.