background image

Version 1.0b 

 

INSTALLATION, GAS LINE 

Installation of the Inglenook fireplace and the Inglenook gas log kit must conform to National Standards, 
NFPA 54 (natural gas) or NFPA 58 (propane).  The installation of gas line and leak testing must conform to 
the National Fuel Gas Code ANSI Z223.1 (United States) and CAN/CGA B-149 (Canada) Installation Code 
and all local codes and gas supplier restrictions.  The Inglenook fireplace has been tested and approved for 
installation using a (7/8" O.D. / 1/2" I.D.)  Model #1650 N Dormont Flex Connector supplied with the unit.   
A licensed plumber will be required to install a gas line and a supply cut-off valve to the Inglenook 
fireplace.  Purge air from the gas supply line before connection is made to the Inglenook fireplace.  The 
shut-off connection between the gas line and the Inglenook gas logs will be installed similar to that shown 
in FIGURE 2.  Do not install gas supply lines in chimneys, gas vents, dumb waiters, elevator shafts, clothes 
chutes, or other air ducts.  Gas piping should be sloped ¼” for every 12 feet of horizontal run.  The slope 
will run from the gas meter down to the Inglenook.  Horizontal runs of gas piping require mechanical 
support every 10 feet by suitable gas pipe hangars or straps.  Install drip leg traps where condensate might 
accumulate in the gas supply line.  Verify local code requirements for sediment traps.  Traps collect 
moisture and sediment that might otherwise block the Inglenook gas log orifices or valves.  Blockages can 
prevent the gas log system from operating properly.  Depending on the length of gas line installed from the 
gas company meter to the Inglenook gas control valve, different size piping is required.  Check with the 
local gas company for requirements but NEVER use plastic or galvanized pipe.  Always follow the flow 
direction marked on all gas line connectors.  Once installation of the gas line is complete, the Inglenook 
fireplace damper setting should remain in the fully open position as shown in FIGURE 2. 

ADJ

PILOT

IN

OUT

PI

L

O

T ON

OFF

LO

HI

GAS LINE 

CUT-OFF

SIT 820 NOVA mV GAS
CONTROL VALVE

GAS LOG

LOWER GRILL

SHOWN OPEN

GAS SUPPLY

OPEN

CLOSED

 

FIGURE 2:  INGLENOOK GAS LINE INSTALLATION 

 

PRESSURE TESTING 

The Inglenook and its control valve are to be isolated from the gas supply piping system by closing its 
individual cut-off valve during any pressure testing of the gas supply piping system at test pressures equal 
to or less than ½ psig (3.5 kPa).  If pressures above ½ psig (3.5 kPa) are present, the Inglenook and its gas 
valve must be disconnected from the gas supply piping during any pressure testing. 

Содержание INGLS 24-N

Страница 1: ...contained in this manual are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life IF YOU SMELL GAS FOR YOUR SAFETY Do not light any appliance Do...

Страница 2: ...LLATION GAS LOGS 17 OPERATING INSTRUCTIONS 21 LIGHTING INSTRUCTIONS 21 TO TURN OFF GAS TO INGLENOOK 21 FIRST FIRE 21 MAINTENANCE INSTRUCTIONS 22 SPECIFIC TASKS 22 CLEANING BURNERS AND CONTROLS 22 REPL...

Страница 3: ...Version 1 0b 3 TABLE OF CONTENTS NOVA mV SET UP GUIDE 31 SAFETY LABEL 32 REPLACEMENT PARTS INGLS 24N or INGLS 24P 33 LIMITED 10 YEAR WARRANTY 34...

Страница 4: ...vironment while obtaining maximum value from the purchase Each employee at Country Flame pledges to ensure every one of our customers has our continuing commitment of product support Country Flame ded...

Страница 5: ...high traffic areas and away from furniture and draperies Children and adults should be alerted to the hazards of high surface temperatures Maintain safe clearances stay away to avoid burns or clothing...

Страница 6: ...that the combustion air vent has no blockage allowing free airflow into the combustion chamber NEW INSTALLATION For first time Inglenook fireplace installations complete ALL installation instructions...

Страница 7: ...obtain new parts before attempting wood burning operations in the Inglenook fireplace again FIGURE 1 INGLENOOK SOLID FUEL PARTS REMOVAL TABLE 1 should be used as a checklist to ensure all solid wood...

Страница 8: ...by suitable gas pipe hangars or straps Install drip leg traps where condensate might accumulate in the gas supply line Verify local code requirements for sediment traps Traps collect moisture and sedi...

Страница 9: ...by a certified professional For lighting instructions refer to the section on first fire in this manual or on the units control panel ON OFF PILOT H I LO PILOT ADJ IN OUT FIGURE 3 SIT 820 mV NOVA GAS...

Страница 10: ...ont Orifice Spud Rear Spud Orifice 1 IN 6516 55 DMS LP Rear Orifice Spud Conversion Label 1 IN 6522 Conversion NG to LP Instructions 1 IN 6524 Conversion Kit Instructions TABLE 2b IN 6503 CONVERSION K...

Страница 11: ...ING inches 0 1 8 PILOT ORIFICE DMS 51 35 INPUT RATING Btu hr 610 1370 Meters 59 000 58 700 ORIFICE SIZE DMS 610 1370 Meters 32 44 49 56 MANIFOLD PRESSURE Inches of Water Column 3 5 10 0 MANIFOLD PRESS...

Страница 12: ...bly includes the gas valve and gas line with front and rear gas orifices the gas valve frame the base plate and the pilot valve assembly This assembly should be placed through the grate opening and sh...

Страница 13: ...ttom of the Inglenook Fireplace Note that the gas tube of the rear burner must go through the slot in the right side of the floor and sit on top of the rear burner orifice mounted to the lower gas lin...

Страница 14: ...front burner tray will sit flat into its opening FIGURE 10 shows the front burner tray sitting in the Inglenook Fireplace The front burner plate is blue in color and the rear burner plate is red in c...

Страница 15: ...a look at the proper installation FIGURE 12 LOG RETAINER STEP 4 COMPLETE STEP 5 The control panel is installed in STEP 5 The control panel face plate covers the ash pan housing opening FIGURE 13 show...

Страница 16: ...h effect to the log system when gas is burnt Embers also help to break up the gas molecules as they pass through the front and rear burner plates and into the burn chamber where these gas molecules co...

Страница 17: ...orrectly will cause the Inglenook gas log system to burn inefficiently Inefficient gas burns can create a significant amount of soot WARNING Do not reconfigure the logs in any different formation othe...

Страница 18: ...Version 1 0b 18 FIGURE 17 THIRD LOG INSTALLATION FIGURE 18 FOURTH LOG INSTALLATION...

Страница 19: ...Version 1 0b 19 FIGURE 19 FIFTH LOG INSTALLATION FIGURE 20 SIXTH LOG INSTALLATION...

Страница 20: ...the next page The entire system should be carefully monitored for the first several fires until the homeowner is convinced that everything is operating properly If there are any signs that the Ingleno...

Страница 21: ...r LIGHTING INSTRUCTIONS 1 STOP Read the safety information above this section 8 Push in and turn the ON PILOT OFF control knob counterclockwise to ON 2 3 4 5 6 7 Turn off all electrical power to the I...

Страница 22: ...pect and clean pilot assembly and inspect and clean surrounding burner area REPLACE OLD EMBERS FREQUENCY Once during annual inspection PERFORMED BY Qualified service technician TASK PERFORMED Replace...

Страница 23: ...lation GENERAL CLEANING REQUIREMENTS Routinely perform general cleaning of the Inglenook to remove all dust lint or other debris that has built up during non use or in the off season Clean the two bur...

Страница 24: ...Item C comes preinstalled into Item E Inspect the wiring of the pilot assembly before installation to ensure all wires are properly connected to the gas valve The gas control valve Item D must be plu...

Страница 25: ...ppliance is checked as specified in the owner instructions supplied with the kit STEP 1 Turn the control knob to the OFF position and turn off the gas supply to the valve STEP 2 Remove control knob ex...

Страница 26: ...lot flame diffuser FIGURE 25 Item B by pulling up on it The retainer clip FIGURE 26 Item A should release the pilot flame diffuser with a light pulling motion b Remove the pilot gas orifice FIGURE 10...

Страница 27: ...k gas log control valve is pre wired to accept a millivolt wall thermostat This remote thermostat can be used to turn the Inglenook gas log system on and off automatically If additional airflow is des...

Страница 28: ...ve hand tight plus turn with a wrench Defective thermocouple mV Plus systems Verify that thermocouple is not kinked or damaged Check open circuit voltage of thermocouple Voltage should be between 18mV...

Страница 29: ...me procedures but substitute the word wall switch where the word thermostat appears Excessive wire resistance Make certain that all mV connections are made using wire of the proper AWG size Refer to t...

Страница 30: ...mA NOVA mV Plus Vented Coil Resistance 2 25 0 5 Coil resistance 0 018 0 003 Minimum Voltage 145 mV Hold in current Less than 200mA Drop out current Greater than 80mA NOVA mV Plus Un vented Coil Resist...

Страница 31: ...le to engage the safety magnet Remember the Millivolt Plus system uses a thermocouple to power the safety magnet and the Millivot system utilize power from a single thermopile to engage the safety mag...

Страница 32: ...Version 1 0b 32 SAFETY LABEL FIGURE 29 CONTROL PANEL OVERLAY...

Страница 33: ...gure 30 Item 3 FRONT BURNER ASSEMBLY IN 6506 Figure 30 Item 4 GAS VALVE PLATE ASSEMBLY IN 6528 Figure 30 Item 5 GRATE ASSEMBLY IN 6520 Figure 30 Item 6 CONTROL PANEL FACEPLATE IN 6527 Figure 15 21 Ite...

Страница 34: ...ts or accessories not including glass panels broken during misuse or careless handling Country Flame Technologies shall not be responsible for any labor transportation or other costs Furthermore Count...

Отзывы: