WARING !
The installation of a fuse must be on positive cable.
Failure to place a fuse on “+” cables running between the
inverter and battery may cause damage to the inverter
and will void warranty.
Increasing your DC cable size will help improve the situation.
Cotek recommends the following cables for optimum inverter performance
(apply both 120V and 230V versions )
Model No
Wire AWG
Inline Fuse
S1500-112 #
2
200A
S1500-212 #
2
200A
S1500-124 #
4
130A
S1500-224 #
4
130A
Also, use only high quality copper wiring and keep cable length short, a
maximum of 3-6 feet.