background image

12

We reserve the right to make changes without notice

H 355 - IET 7143 - 7183  C1 Eng.

  

18.01.10 AM  

Rev. 06

COSTER

17.

6

 Calculation of flow of vector fluid and of instantaneous power

On the basis of the signal received from the volumetric meters the instantaneous flow in m

3

/h is calculated and also 

the instantaneous power in Kw which at that moment is being supplied to the site.

17.

7

 Recording of the meter readings 

The recording of the meter readings is carried out so as to ensure there is absolutely no loss of data. 

When the meter is being used to its maximum capacity the four most important meter readings to be recorded are:

– ENERGY HEATING SIDE (MWh)

– VOLUME HEATING SIDE (m

3

)

– ENERGY COOLING SIDE (MWh)

– VOLUME COOLING SIDE (m

3

)

All the four meter readings are also recorded as “Total meter readings”: these are four additional values which 

represent the sum of meter readings from when the meter was first used; they can be compared to the total mileage 

of an automobile.

The total meter readings cannot be altered in any way since they represent values which regard important fiscal 

matters.

The meter readings normally displayed can be adjusted, as will be shown in the following section.

The single meter reading is stored in two separate memories: should either of the two memories become 

corrupted, it is automatically replaced by the other.

Only if both memories should become corrupted simultaneously would the data be lost; the probability of this hap-

pening is practically nil, because the two memories are never used at the same moment and the levels of protec-

tion against electrical and radio disturbances are at the maximum level required by the standards (see section 11).

17.

8

 Adjustment of meter readings 

The adjustment of all meter readings serves to equalize the readings of external meters to those of the IET 71.. 

meters. Examples :

– the meter is installed after the volumetric meter installed has totalled the readings. Normally, when the turbine 

volumetric meter is first installed the plant is started up and the meter starts to measure the volume flowing past 

it (m

3

).

IET 71.., when first installed and set in operation, has all its meters set to zero or at the minimum amount necessary 

for testing. The metering of m3 by the volumetric meter is, therefore, different from the metering of the same m

3

 by 

the electronic meter: it is possible to reconcile the two meter readings.

– the meter is installed as a replacement for a pre-existing meter; in this situation also it is useful for the client to 

have the readings on the new meter which start from those already made by the old one.

The adjustment operation must obviously be protected by a seal, since any alteration would mean different data 

readings. 

The basic data, however, is always stored in the meter and must not be altered in any way, since they are fiscal 

data ; the next section describes these meter readings in more detail.

In the memories are stored the basic meter readings together with the adjusted values; in this way the true readings 

are securely safeguarded, as are the adjustment values; the figures to present to the user are the basic meter readin-

gs, corrected by the adjustment values. 

Furthermore, all data which has undergone any adjustments is recorded, in order to identify errors and intentional 

tamperings.

17.

9

 Data storage (DATA LOGGER) of meter readings, power and flow peaks, and errors 

The unit incorporates a DATA LOGGER which can store 52 weeks of meter readings and operational data: by this 

means it is possible to understand, check and if necessary interpolate all the data for a whole year.

– RECORDING METER READINGS: every week (at around midnight on Sundays) a recorded the four fundamental 

meter readings made up to that moment (see section 17.

8

) with day and date.

– RECORDING OF POWER & FLOW PEAKS: every week are recorded the values of maximum power and flow 

reached that week.

  The maximum flow of the vector fluid is calculated as the mean over a certain number of minutes (chosen via 

Telemanagement), so as to avoid sudden insignificant peaks; the same criteria are followed for power.

  The power peaks are recorded indifferently for heating and for cooling, since it is very easy to understand, on the 

basis of the season, if reference is to one or the other.

– RECORDING OF ERRORS (ALARMS): each type of alarm (see section 16) is recorded both when it is triggered 

and when it ceases, with exact date and time. The system records up to 10 of these events; after this it cancels 

the oldest to leave space for new onesi.

Everything having reference to the DATA LOGGER can be set and read via Telemanagement C-Bus.

Содержание ET 7183 C1

Страница 1: ... weekly of the flow and of the power these figures are processed at a programmable time interval ALARM SYSTEM the unit processes10 different types of alarm with a local or remote output the alarms are recorded in the DATA LOGGER by type and time of event ADDITIONAL PROCESSING the unit continuously processes the flow of the fluid vector and the instantaneous power of the system Moreover it provides all...

Страница 2: ...mperature range 0 150 C Difference temperature return flow range 3 150 C Cable section 2 x 0 5 mm2 Standard cable length 3 m Special length cable 10 m Essential accessories Pair of pockets for sensors brass or stainless steel GIS thread 1 2 depth 2 measurements 25 and 45 mm Standards Specific standard for the meter UNI EN 1434 Immunity from electric disturbances RF CEI EN 61000 Telemanagement Speed ...

Страница 3: ...the meters The pockets are available in various models sizes and materials according to type of application STANDARD BRASS POCKETS supplied in pairs These pockets are in packages of two Other pockets are available with different depths for any pipe diameter See the sensors pockets section of the catalogue Misc A B Model 1 2 45 56 ART 015 3 4 45 56 ART 020 1 42 62 ART 025 Each item represents a pai...

Страница 4: ...ng it should it not be used for a long tim JUMPER P2 serves for programming output G power supply ultrasound sensors or similar between 3 6 and 5 volts See wiring diagram section 10 output G JUMPER P3 serves for programming the pulse output of the volume that can be either equal to the pulse output of the volumetric meter or with the metering unit already processed by IET 71 JUMPER P4 serves to pr...

Страница 5: ...ected directly to the terminal block over 3 meters extend it with screened cable 2 wires screen up to a maximum of 30 meters connecting the screen only to point M of the terminal block in the event of doubt or where there are existing installations which fall outside this advice consult COSTER tech nical staff to find solutions that do not require the re design of the wiring If possible avoid layin...

Страница 6: ... litres over 10 up to 100 below 10 up to 5 100 litres over 100 below 5 1000 litres This transmission of pulses is of the indirect type since it is not a copy of what the volumetric meters transmit but is already the processed volume which by means of an external meter can be measured in a second way for sa fety Note the pulses recorded are transmitted after a maximum interval of 15 minutes Applica...

Страница 7: ...HE SYSTEM The maximum error of the pair of sensors is lower than that prescribed by the EN 1434 2007 Directive The maximum error on the difference between the flow and return temperatures is given by the following formula Et 0 5 3 T min T where T min difference flow return minimum 3 C T actual difference between flow and return Examples with actual T tof 3 C the maximum error accepted by the regulati...

Страница 8: ... 0 0 0 0 2 3 4 5 K W v v 0 0 0 0 2 5 0 0 L P v v F L O R E T v v 0 0 0 0 2 3 4 5 m 3 h v v F M A X 0 0 3 6 6 7 8 9 M W h v v T O T 0 0 5 6 6 7 8 9 m 3 v v T O T RETURN TO HEAD OF COLUMN RETURN TO HEAD OF COLUMN 1 8 2 3 1 5 H R S v 0 0 0 0 0 3 6 9 H R S v 0 0 0 4 2 6 0 0 H R S v A L A I E T 7 1 C 1 V X X v 1 1 9 0 7 0 4 D A T E v SEGMENTS ALL LIT RETURN TO HEAD OF COLUMN RETURN TO HEAD OF COLUMN HE...

Страница 9: ...t of the meter to check the above actions 16 2 Simplified readout of the unit In this section is described the simplified readout of all the metering parameters for normal use The decimals in the readouts are after the point to indicate them more clearly the standards require that the decimal figures are clearly distinct from the whole numbers for this reason the decimal figures are highlighted by das...

Страница 10: ...rogrammable via Telemanagement Alarm 4 exceeding the number operational hours programmable via Telemanagement after which the standards require the recalibration of the system usually seven years Alarm 5 alarm clock this alarm triggers when the clock incorporated in the unit shows incon gruent times and dates Alarm 6 alarm for use of incorrect base for the electronic unit this alarm is triggered w...

Страница 11: ...e figures are shown as MWh 1 MWh 1000KWh for ease of reference 17 4 Separation of thermal and refrigeration energy IET 7183 7143 meters can separate thermal energy heating from refrigeration energy cooling the distinction is made by noting the minus sign Tf Tr if the difference is positive thermal energy is being metered flow warmer than return if the difference is negative refrigeration energy is b...

Страница 12: ...ary for testing The metering of m3 by the volumetric meter is therefore different from the metering of the same m3 by the electronic meter it is possible to reconcile the two meter readings the meter is installed as a replacement for a pre existing meter in this situation also it is useful for the client to have the readings on the new meter which start from those already made by the old one The a...

Страница 13: ...e identity of the user names of persons or site 17 13 Clock IET 71 is provided with a universal clock which is essential for recording the times and for assigning the time and date to each DATA LOGGER recording In the event of a power failure the system battery keeps the clock and the rest of the unit in operation should the module be removed from the base the clock has its own power reserve for a...

Страница 14: ...0 0 0 1 0 0 0 0 L P v v M 1 4 L P output vol meter litres per pulse Max 1000 l p P L outputvol meterpulsesper litre Max 1000 p l F LO R E T v v M 1 5 RET volumetric meter installed on return FLO volumetric meter installed on flow 0 2 0 0 0 0 0 0 m 3 h v v M 1 6 m3 h alternates with FMAX maximum flow threshold abo ve which alarm triggered for maximum flow Alarm 3 Group ALA 2 0 0 4 5 6 7 8 9 m 3 v v M ...

Страница 15: ...ted by pressing the two keys at the same time for at least 10 se conds this indication is annulled but not the data recorded I E t 7 1 C1 V X X v M 7 3 Shows version of software with consequent update C C1 first update C V XX version software 1 8 2 3 1 5 T I M E v M 6 2 The default values factory settings where present are shown in bold type M 6 3 1 1 day of week flashes adjust with key 1 Monday 7 S...

Страница 16: ... HEAD OF COLUMN 0 7 8 9 3 1 2 3 m 3 v M 3 TF 0 7 8 9 3 1 2 3 m 3 v 0 7 8 9 3 1 2 3 m 3 v F L O R E T v F L O R E T v 0 2 0 0 0 0 0 0 m 3 h v 0 2 0 0 0 0 0 0 m 3 h v RETURN TO HEAD OF COLUMN 0 0 1 2 3 4 5 6 M W h v M 4 TF 0 0 1 2 3 4 5 6 M W h v 0 0 1 2 3 4 5 6 M W h v RETURN TO HEAD OF COLUMN 0 0 0 4 3 8 0 0 H R S v M 8 TF 0 0 0 4 3 8 0 0 H R S v RETURN TO HEAD OF COLUMN RETURN TO START SETTING HE...

Страница 17: ... the settings POSITION SINGLE SWITCH lever in up position towards ope rator lever in down position away from operator 20 2 Switch number 4 Enabling COOLING With this switch you can decide whether to have metering of heating only calories or metering of heating calories and at the same time of cooling frigories as described in section 16 4 METERING HEATING COOLING METERING HEATING ONLY 20 3 Switch ...

Страница 18: ... numbers flash one at a time forward with and adjust with Proceed until num ber set equals desired aligned value Max 1000 l pul RETURN TO HEAD OF COLUMN 0 0 1 2 3 4 5 6 MW h v M 2 TF MWh alternating with TOT total metering heating energy 0 0 1 2 3 4 5 6 MW h v M 2 1 TF MWh alternating with ALI aligned metering Flashing cursor indicates entry in setting sub menu 0 0 1 2 3 4 5 6 MW h v M 2 1 1 M 2 1 ...

Страница 19: ...al volume heating 0 2 0 0 0 0 0 0 m 3 h v M 3 2 TF m3 h alternating with FMAX alarm threshold for maximum flow Max 2000 m3 h F LO R E T v M 3 3 TF RET volumetric installed on return FLO volumetric installed on flow F LO R E T v M 3 3 1 M 3 3 2 TF With choose RET or FLO 0 2 0 0 0 0 0 0 m 3 h v 0 0 1 2 3 4 5 6 MW h v M 4 TF MWh alternating with TOT metering total volume heating 0 0 1 2 3 4 5 6 MW h v ...

Страница 20: ...number set equals desired ali gned value 0 7 8 9 3 1 2 3 m 3 v M 5 1 1 M 5 1 8 TF 0 7 8 9 3 1 2 3 m 3 v M 5 TF m3 alternating with TOT metering total volume cooling 0 0 0 4 3 8 0 0 HR S v M 6 TF HRS alternating with ALI hours over which alarm servicing carried out Alarm 4 Group ALA2 Cursor numbers flash one at a time can be adjusted according procedure already seen forward with and adjust with Proc...

Страница 21: ...erted With the plant switched off the temperature difference can be positive or negative check the installation of the sen sors by removing the sensor from the pocket warming it with the hands andchecking the values indicated If the sensors have been interchanged when heating only is metered the readings will not be affected whilst when heating and cooling are metered the relative measurements wil...

Страница 22: ...some reason and the circulation pump continues to operate it may happen that the flow temperature rises and at the same time the return temperature also rises and to a greater extent since it is heated by a larger number of consumers the room is warm because there is no longer conditioning Without this function the refrigeration energy which the rooms give up to the conditioning system in the inter...

Страница 23: ...23 We reserve the right to make changes without notice H 355 IET 7143 7183 C1 Eng 18 01 10 AM Rev 06 COSTER ...

Страница 24: ...4 26 09 08 AM 03 5 10 WIRING DIAGRAM Update wiring diagram 16 07 09 VM 04 2 5 6 6 4 TECHNICAL DATA 10 1 Connection of the temperature 12 LABELING OF METERS 13 and 14 Directive MID 2004 22 EC 25 11 09 VM 05 6 10 7 and 10 8 Application example for the use of impulse relay in direct and indirect mode 18 01 10 MM 06 various various Addition of the option of communicating at different speeds from 1200 ...

Отзывы: