1

B 335 -RTP 82 Eng

 

03.93

We reserve the right to make changes without notice

COSTER

APPLICATION

RTP 82 is designed for the control of mixing or diverting valves
operated by reversible actuators (3-wire electric control), for the
regulation of room temperature and of the maximum flow tempe-
rature limit (45 

°

C) in underfloor heating systems:

 Single-family dwellings

 Flats with autonomous heating

 Residential complexes with zone heating.

 Single spaces in industrial or craft premises

ESSENTIAL ACCESSORIES

No.

Description

Model

Sensing element

Symbol

Data sheet

For all models :

1

Immersion flow temperature detector

SIH 010

NTC 10 k

B1

N 140

For /D models :

1 or 4

Room temperature detectors (4 for large spaces)

SDA 010

NTC 10 k

B2

N 110

or 2

Room temperature detectors (for large spaces)

SDA 020

NTC 20 k

B2

N 110

MODELS

Model

Description

RTP 825

With 24-hour quartz time switch and room detector incorporated

RTP 826

With 7-day quartz time switch and room detector incorporated

RTP 825/D

With 24-hour quartz time switch and remote room detector

RTP 826/D

With 7-day quartz time switch and remote room detector

B 335

03.93

MODULATING  ELECTRONIC  ROOM  CONTROLLERS
FOR  UNDERFLOOR  PANELS

RTP 82  

Eng.

 Power supply 220/240 Volt ac; IP 20 protection

 One modulating output with PI control action and voltage-free SPDT contacts

 24-hour or 7-day time switch

 Maximum flow temperature limit (45 

°

C)

fig. 1

OPERATING DIAGRAMS

Controller with room detector incorporated

Controller with remote room detector

12

3

6

9

20

15

COSTER

RTP 82

T

N1

Y

M

B1

E2

E1

12

3

6

9

20

15

COSTER

RTP 82

T

N2

Y

M

B1

E2

E1

B2

E1
E2

– Boiler
– Underfloor panels

B1
B2

– Flow detector
– Room detector

N1
N2

– RTP 82 .. controller
– RTP 82 .. /D controller

M
Y

– Plant pump
– Mixing valve

Содержание B 335

Страница 1: ...ors for large spaces SDA 020 NTC 20 kΩ B2 N 110 MODELS Model Description RTP 825 With 24 hour quartz time switch and room detector incorporated RTP 826 With 7 day quartz time switch and room detector incorporated RTP 825 D With 24 hour quartz time switch and remote room detector RTP 826 D With 7 day quartz time switch and remote room detector B 335 03 93 MODULATING ELECTRONIC ROOM CONTROLLERS FOR ...

Страница 2: ...value of the room temperature with the desired Normal and Setback temperatures set by means of the two potentiometers on the facia of the case fig 2 6 and fig 2 7 In the event of a difference RTP 82 produces a modu lating signal with PI control action for the control of the valve Y proportional to the difference itself and to the proportional band 1 C The immersion detector B1 monitors the flow te...

Страница 3: ... temperature Two values for desired temperature can be set Normal temperature for periods when the premises are oc cupied with the Sun potentiometer fig 2 6 Setback temperature for periods of non occupation of the premises or for the night period with the Moon potentio meter fig 2 7 The setting range of the desired temperatures can be limited by means of two pins fig 3 5 housed on the base at the ...

Страница 4: ...ctuator with voltage other than 220 240 Volt Connection RTP 82 D detectors B1 6 7 8 t t B2 t t B2a B1 6 7 8 t B1 6 7 8 t t t t t B2b 1 2 L 0 220 240 Volt ac T 3 4 5 Y Co 1 Cl 3 Op 2 RTP 82 1 2 3 4 5 B1 L 0 220 240 Volt ac 6 7 t Y Co 1 Cl 3 Op 2 Room detector SDA 020 Room detector SDA 010 B2a B2b Y T Valve Transformer Flow detector SIH 010 Room detector SDA 010 B1 B2 L 0 Live Neutral COSTER CONTROL...

Отзывы: