-R

 -

 You can control output ON/OFF remotely in Option -R units. To 
do so, connect an external DC power supply and apply a volt-
age to a CN4, which is available as option.

 -

 Remote ON/OFF circuits (RC+ and SGND) are isolated from 
input, outputs and FG.

 -

 All outputs (V1,V2,V3) are targets of remote ON/OFF.

 -

 Targets of remote ON/OFF is selectable. Please contact us for 
detail.

Ri

Input 

Current

5max

0

0.5

4.5

12.5

2200

Input

Current 

[mA]

Output OFF

Output ON

Voltage between

RC and SGND[V]

SGND

RC

Built-in

Resistor

Ri[

Ω

]

3

1

CN4

Inside of a Power 

Supply

 

R1

External 

Power 

Source

 

SW

Fig.5.2 

 

Example of using a remote ON/OFF circuit

*

If the output of an external power supply is within the range of 4.5 

- 12.5V, you do not need a current limiting resistor R1.

  If the output exceeds 12.5V, however, please connect the current 

limiting resistor R1.

Ri : 2200

Ω

Vcc

(1.1

Ri

×

0.003)

0.003

R1 Recommended resister [

Ω

]

*

Please wire carefully. If you wire incorrectly, the internal compo-

nents of a unit may be damaged.

¿

-T

 -

 Option -T units have vertically positioned screws on a terminal 
block.

 -

 The size specification is different from standard version. (Refer 
to external view).

 -

 If you configure Slot 2 as “O”, +V2, G2 and -V2 of TB2 is NC.

 -

 If you configure Slot 3 as “O”, TB3 is not installed.

5.2 Others

¡

High voltage exists in the power supply for a few minutes after 
input voltage is stopped. Please pay attention to this during main-
tenance.

¡

This power supply is manufactured by SMD technology. The 

stress to PCB like twisting or bending causes the defects of the 
unit, so handle the unit with care.

 -

 Notes for mounting

  

1

 All Mounting holes should be tight and secured.

  

2

 Power supply should be mounted parallel to the mounting 
surface.

  

3

 Avoid applying mechanical stress or shock to the power sup-
ply.

  

4

 Do not touch any SMD components on the unit.

¡

When power supply is energized or immediately after power sup-
ply stops working, power supply is still very hot, so please handle 
it with care.

AC-DC Power Supplies Configurable Type

Instruction Manual

RB-13

Содержание RBC200F

Страница 1: ...Parallel operation Input module of RBC200F Active filter 40 220 2 4 1 Relay FR 4 Yes No No Output module of Y Z LLC resonant converter 90 180 FR 4 Yes No No Output module of G H J K L Flyback converte...

Страница 2: ...odel Name Construction RB 8 3 Series Operation and Parallel Operation RB 10 3 1 Series Operation RB 10 3 2 Parallel Operation RB 10 4 Assembling and Installation Method RB 10 5 Option and Others RB 12...

Страница 3: ...1 output is connected to V1 G1 Slot 2 output is connected to V2 V2 and G2 Slot 3 output is connected to V3 G3 Configuration rules 1 The code of the module installed in Slot 1 is selected from Slot 1 o...

Страница 4: ...tage protection circuit is built in If the overvoltage pro tection circuit is activated shut down the input voltage wait more than 3 minutes and turn on the AC input again to recover the out put volta...

Страница 5: ...ing on input voltage is shown in Fig 4 3 The definition of load factor is the following suffix k means the k th slot Ak Ik Vk Rated output power of k th module Rated output power Depends on input refe...

Страница 6: ...ing screw should be M3 The hatched area shows the allowance of metal parts for mounting 8 8 8 8 8 8 8 8 CN1 CN2 CN3 FG Fig 4 7 Allowance of metal for mounting If the power supply unit is fixed with me...

Страница 7: ...5 1 Table 5 4 and Table 5 5 Table 5 3 Maximum temperature of measurement points RBC200F O SN Installation condition Cooling Method Load factor Maximum temperature C 1 Capacitor 2 V1 Capacitor 3 V2 Ca...

Страница 8: ...y If you wire incorrectly the internal compo nents of a unit may be damaged T Option T units have vertically positioned screws on a terminal block The size specification is different from standard ver...

Отзывы: