background image

Table 5.10  LV alarm operating conditions

Alarm

Output of alarm

LV

If the output voltage drops below 

the rating, the alarm signal is out-

put from LV and LVG terminal.

Note : 

1

This becomes unstable 

in the event of output 

overcurrent (intermit-

tent overcurrent).

2

The alarm signal is not 

output for parallel op-

eration that does not 

use OR diodes.

Open collector method

Good : Low

 

 (0 - 0.8V, 10mA max)

Fail   : High or Open

50V   10mA max

¡

Parallel operation

  In case of parallel operation, please make the following process.

 

1

  Before wiring, output voltage should be set to the required 

voltage at fi rst to each power supply. Each output voltage dif-

ferences must be less than 0.1V or 1% of the rated output volt-

age, whichever smaller.

 

2

  Please connect each wire refer to Fig.5.10.  And please use 

same length and same type wire to connect each load line.

 

3

  As variance of output current drew from each power supply is 

maximum 15%, the total output current must not exceed the   

value determined by the following equation.

The rated

current per unit

=                              

X

 (Number of unit) 

X

0.85

Output current in 

parallel operation

 

Please confi rm that each output current is within the rated cur-

rent.

When the output voltage adjustment is required after wiring, retry 

the above process from 

1

 again.

When the number of units in parallel operation increases, input 

current increases at the same time. Adequate wiring design for in-

put circuitry is required, such as circuit pattern, wiring and current 

capacity for equipment.

-

In parallel operation, the maximum operative number of units is 5.

-

It is not possible to work as master and booster operation.

CB

CB

CB

-S

-S

-S

Load

(+)

(-)

Fig.5.10  Parallel operation condition

When the output current is less than 10% of rated output current, 

the output voltage fl uctuates occasionally.  The minimum current 

is different depending on the model and the number of parallel 

operation. Please contact us.

When output cable is not same length from each power supplies,  

output current value will not be balanced at each units. Please  

set the cable length as same as possible.

¡

Remote sensing

-

These models have a built-in remote sensing function.

  If you do not use the remote sensing function, you can short out 

bS and +M and between -S and -M on CN1.

  When the power supplies are shipped from a factory, they come 

with a dedicated harness (H-SN-31) being mounted on CN1. If 

you do not use the remote sensing function, you can use the 

power supplies as they are.

-

Please see Fig.5.10 if you do not use the remote sensing function.

  Please see Fig.5.11 if you use the remote sensing function.

-

When you use the remote sensing function, please wire from +S 

and -S on CN1. Harnesses are available for your purchase.

  Please contact us for details.

  When you use the remote sensing, please note the followings.

1

  Wire carefully. When a connection of a load line becomes loose 

(due to such factors as loose screw), the load current flows to 

the sensing line and internal circuits of the power supply may be 

damaged.

2

  Use a suffi ciently thick wire to connect between the power supply 

and the load and keep the line drop at 0.3V or below. 

3

 If the sensing line is long, connect C1 and R1.

4

 Use a twisted pair wire or a shielded wire as the sensing line.

5

 Do not draw the output current from +M, -M, +S or -S.

6

  When the remote sensing function is used, the output voltage of 

the power supply may show an oscillating waveform or the output 

voltage may dramatically fl uctuate because of an impedance of 

wiring and load conditions.

  

 

Please check and evaluate carefully before using the remote 

sensing function.

  

 

If the output voltage becomes unstable, we suggest you to try the 

followings.

 - 

 

Remove the remote sensing line on the minus side and short 

out between -S and -M.

  - Connect C1, R1 and R2.

    Please contact us for details.

AC-DC Power Supplies Enclosed type

Instruction Manual

PLA-19

PLA

me̲pla1.indd   PLA-19

me pla1 indd PLA-19

2014/03/04   10:34:44

2014/03/04 10:34:44

Содержание PLA100F

Страница 1: ...ted input fuse Inrush current protection circuit PCB Pattern Series Parallel operation availability Material Single sided Double sided Series operation Parallel operation PLA100F Active filter 40 to 1...

Страница 2: ...on 1 4 Overvoltage Protection 1 5 Thermal Protection 1 6 Output Ripple and Ripple Noise 1 7 Output Voltage Adjustment 1 8 Isolation 1 9 Low Power Consumption 1 10 Remote ON OFF 1 11 Remote Sensing 1 1...

Страница 3: ...imary inrush cur rent and secondary inrush current will be generated because the thyristor technique is used for the inrush current limiting circuit 1 3 Overcurrent Protection An overcurrent protectio...

Страница 4: ...ial probe C1 Film capacitor 0 1 F C2 Aluminum electrolytic capacitor 22 F Fig 1 2 Measuring method of Ripple and Ripple Noise Remarks When GND cable of probe with flux of magnetic force from power sup...

Страница 5: ...ility of the unit periodic mainte nance of the fan is required Expected life of fan R t 90 is different by the used condition 2 2 Parallel Operation Redundancy operation is available by wiring as show...

Страница 6: ...Forced air 0 5m3 min 1Convection A mount 2Convection B C mount 0 8 0 10 0 6 0 4 0 5 0 2 20 10 Load factor C Ambient temperature Fig 3 3 Ambient temperature derating curve for PLA100F 150F 12 15 20 10...

Страница 7: ...e of fan AIR FLOW 20mm Measurement point Power supply Terminal block F A N Side AIR FLOW 20mm Measurement point Power supply Terminal block F A N Top Fig 3 8 Temperature of measurment point for fan li...

Страница 8: ...0F You can control output ON OFF in Option R units An external DC power supply is connected and it should be applied a volt age to a remote ON OFF connector to control it Appearance is changed from st...

Страница 9: ...ard model There is a lineup of optional harnesses Refer to option parts Please contact us for details Differences from standard versions are summarized in Table 5 6 Table 5 7 Specification differences...

Страница 10: ...on the model and the number of parallel operation Please contact us When output cable is not same length from each power supplies output current value will not be balanced at each units Please set the...

Страница 11: ...Please do not apply more than 5A per 1 pin Option J can not meet UL508 V ADJ AC L AC N FG V V CN1 CN2 Fig 5 15 Example of option J PLA100F Table 5 11 Mating connectors and terminals on CN1 and CN2 in...

Страница 12: ...e turning on the electricity and for a while after turning off please don t touch the inside of a power supply because there are some hot parts in that When a mass capacitor is connected with the outp...

Отзывы: