![CORTEM FLOWEX Series Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/cortem/flowex-series/flowex-series_mounting-instructions_2669874006.webp)
PAG.6
Lighting Fixtures series FLOWEX..
safety, maintenance and mounting instruction
Codification for Luminaires
TYPE OF LIGHTING FIXTURE
N° 4 Screws M5x12
note: factory connection
Cable Gland
VERSION OF THE LAMP - ME, MN
SIZE (060, 080, 100)
POWER OF THE LIGHTING FIXTURE
OTHERS PARTICULARS DESCRIPTIONS (if required)
INPUT CABLES
RESTRICTED BREATHING TEST
THE INCOMING CABLES ARE FORESEEN INTO
LATERAL HOUSING BY MEANS OF CABLEGLANDS
Ex eb, Ex tb, Ex nR AS PER THE INSTALLATION ZONE
AND IN COERENCE WITH IEC/EN 60079-14 AN M20x1.5
CABLEGLAND WITH LOCKING NUT
FOR THE CABLE CONNECTION TO TERMINALS, TAKE OFF THE SCREWS
OF COVER AND REMOVE THE COVER
TIGHTEN THE SCREW TERMINALS AT 0.5 Nm TORQUE
PAY ATTENTION TO DO NOT PULL THE INSIDE CABLES
REMOVE THE CLOSE-UP PLUG TO ACCESS THE TEST
DOOR AND THEN INSERT THE MEASURING INSTRUMENT
INTO IT
TO CREATE IN THE INTERNAL OF THE LIGHTING FIXTURE
A DEPRESSION OF 0,3 kPa (mbar)
TO VERIFY THAT THE DEPRESSION DOES NOT BE UNDER
0,15 kPa (1,5 mbar) AFTER A TIME OF 90 SECONDS
AT THE END OF THE TEST, REMOUNT THE CLOSE-UP PLUG
FLOWEX ....
....
....
....
ARMATURE ILLUMINANTI SERIE FLOWEX..
ISTRUZIONI DI SICUREZZA, USO E MANUTENZIONE
Lighting fixtures series EVNL...
safety, maintenance and mounting instruction
CODICI LAMPADE
TIPO DI LAMPADA
VERSIONE DI LAMPADA - ME, MN
GRANDEZZA (060, 080, 100)
POTENZA DEL DISPOSITIVO DI ILLUMINAZIONE
ALTRE DESCRIZIONI PARTICOLARI (SE RICHIESTE)
INGRESSO CAVI
TEST DI RESPIRAZIONE LIMITATA
L’INGRESSO CAVI È PREVISTO NEL COPERCHIO SUPERIORE PER MEZZO DI
PRESSACAVI Ex eb, Ex tb, Ex nR A SECONDA DELLA ZONA DI INSTALLAZIONE
E IN COERENZA A QUANTO RICHIESTO DALLA IEC/EN 60079-14 USARE
PRESSACAVI M20x1.5 CON CONTRODADO
PER ACCEDERE AI MORSETTI DI COLLEGAMENTO SVITARE LE VITI DEL
COPERCHIO E TOGLIERE IL COPERCHIO
SERRARE LE VITI DEI MORSETTI A 0.5 Nm DI COPPIA
FARE ATTENZIONE A NON STIRARE I CAVI INTERNI
SVITARE IL TAPPO PER ACCEDERE ALLA PORTA DI PROVA,
QUINDI INSERIRVI LO STRUMENTO DI MISURA
CREARE ALL’INTERNO DELL’ARMATURA ILLUMINANTE
UNA DEPRESSIONE DI 0.3 kPa (3 mbar)
VERIFICARE CHE LA DEPRESSIONE NON SCENDA AL DI
SOTTO DI 0.15 kPa (1,5 mbar) DOPO 90 SECONDI
AL TERMINE DELLA PROVA RIMONTARE IL TAPPO
T amb
Cavi adatti a
Cable suitable for
40°C
75°C
45°C
80°C
50°C
85°C
55°C
90°C
60°C
95°C