Standard Recommended Procedure 003-1002-AEN | Issue 7 | January 2019 | Page 20 of 25

Step 4:  Module Location with Fiber or Port Range (Figure 31)

Each tray comes pre-labeled A through F to identify module position within the tray.

Figure 31  — Module Label Location

Step 5:  Documentation (Figure 32)

Identify remote location termination and determine code to be printed. It should only be necessary 

to print the remote location. Printed code from label makers may be a    xed to the label card on the 

inside of the front door.

Figure 32  — Print Remote Termination Label

Содержание EDGE8-01U

Страница 1: ...unk Cable Placement with the Pulling Grip 5 4 2 2 Pulling Grip Removal 5 4 3 OPTIONAL Install CDF Bracket 7 4 4 InstallTrunk Cables from Either Side of the Housing 8 4 4 1 InstallingTrunk Cable Using...

Страница 2: ...management ngers 3 Tools and Materials Required 3 1 Tools Phillips screwdriver Reel stand 3 2 Materials Hook and loop straps LCconnector adapter cleaning tool p n CLEANER PORT LC MTP connector cleani...

Страница 3: ...nstalled in the rack Step 3 Install screws into the rack through the mounting brackets Step 4 If installing a 2U or 4U housing slide the ber management ngers onto the housing NOTE Installation of ber...

Страница 4: ...utlined on the reel Observe This End Up arrows on reels or boxes Ensure that all ange bolts are tight prior to loading a reel for pulling Changes in temperature and humidity can cause the wooden cardb...

Страница 5: ...e the corrugated reel from its protective shipping box or pallet Step 2 Place the cable reel on a reel stand so that the pulling grip cable will pay o the top of the reel Figure 4 NOTE Cables greater...

Страница 6: ...furcation end of the coupler to separate the coupler s two halves Step 7 Remove the coupler halves from the trunk furcation body and dispose of the coupler assembly Figure 9 96 and 144 ber Trunks Step...

Страница 7: ...a pass through IBU system Step 1 Align bracket within the same height of the 4U housing Step 2 Install bracket using two 12 24 screws Figure 11 Allow enough clearance when routing trunks from the brac...

Страница 8: ...e the reel and press each trunk cable furcation plug into cradle Figure 12 double stack cradle or Figure 13 single stack cradle NOTE One double stack cradle shown in Figure 12 is provided with the tru...

Страница 9: ...place Figure 14 Install Trunk Cable with Keyhole Adapter 4 5 InstallTrunk Cables from Rear of Housing If rear cable entry into the housing is desired or necessary the backplates must be turned 180 deg...

Страница 10: ...lished in a location external to the housing the trunk plate may be removed to allow more room behind the housing Figure 16 Step 1 For 4U housing only Remove side panel from each side of the housing S...

Страница 11: ...oad all trays from right to left bottom to top in the housing as seen from the back Step 4 Loop slack as shown in Figure 17 leaving enough slack to pull out trays without violating the minimum bend ra...

Страница 12: ...access to mount the trunk cables and connect the trunk legs Figure 18 Lower Tilt down Drawer Step 4 From rear of housing feed connectorized MTP trunk connector legs through to the front of the housing...

Страница 13: ...corner Tray 1 slot A insert port breakout module from the rear until it locks into place Load all trays from right to left bottom to top in the housing as seen from the back Step 2 Loop slack as shown...

Страница 14: ...ls are not pinched in the process Figure 21 Install EDGE8 Module 4 9 Connect Jumpers to EDGE8 Modules CAUTION When removing the trays position yourself in the center of the rack and use both hands to...

Страница 15: ...removed from the rear of the housing and install additional trunks Installer MUST obtain slack in the ber connected to the panels on the front side Without slack tension in the jumpers will result in...

Страница 16: ...ables may occur Step 1 Open housing front door and pull out tray Ensure there is enough ber slack in the rear of the housing to allow for this movement Step 2 Remove dust caps from the front of the MT...

Страница 17: ...e pre labeled for identi cation and promote a consistent labeling scheme Users must provide their own label maker and media for the frame or cabinet and hardware Labeling is best supported with use of...

Страница 18: ...e 27 Recommended Labeling Guidelines Step 1 Frame Cabinet Location Figure 28 Identify location of frame or cabinet within the oor space grid coordinate system Preprint labels and adhere to front and b...

Страница 19: ...t corner of the housing chassis Print two labels and adhere one to the front chassis door using the crop mark for alignment Adhere the second label to the label card on the inside of the door Figure 2...

Страница 20: ...gh F to identify module position within the tray Figure 31 Module Label Location Step 5 Documentation Figure 32 Identify remote location termination and determine code to be printed It should only be...

Страница 21: ...important to follow suite with previous de ned code indicating rack or cabinet ID patch panel ID and more speci cally the individual port or ber termination location One should cross reference the rec...

Страница 22: ...cal Power Meter and Test Kits for testing the MTP connections Follow the Fluke Networks manual which can be found on line at http download ukenetworks com Download Asset MultiFiberPro_9827313_ENG_A_W...

Страница 23: ...pull module out Step 4 Unplug MTP connector s in rear of module Step 5 Reverse process to install new module or panel if upgrading the network Figure 34 Replace EDGE8 Module 6 3 Remove Trunk Cable 6 3...

Страница 24: ...dy up from the bottom using your fore nger Alternate method Insert a at head screwdriver into the hole in the cradle to pry up the furcation body Figure 36 RemoveTrunk Cable from U Clip Cradle 6 4 Cha...

Страница 25: ...ropyl alcohol is ammable with a ashpoint at 54 F It can cause irritation to eyes on contact In case of contact ush eyes with water for at least 15 minutes Inhalation of vapors irritates the respirator...

Отзывы: