CornellCookson FS-500EP Series Скачать руководство пользователя страница 6

FS500-EP SERIES 

REVISION # 0000 

DATE: 04/03/2019

 

 

LIMIT SWITCH ADJUSTMENT 

 

Make sure the limit cams are positioned between the limit switch actuators before proceeding 
with adjustments. 

 

1. Open / remove the control panel cover. 
 
2. Open or close door to determine the moving direction of the limit switch cams. 
 
3. Open or close door to the desired position. 

 

 
Disconnect power before adjusting limit switch cams. 
 

 
4. While pressing the spring-loaded lever (G), which holds the limit switch cams in place, adjust the 

limit switch cam (E or F) until the micro switch (C or D) clicking sound is heard.  

 
5. If the limit switch cam cannot be rotated to its desired position, release the lever and move the door 

away from the desired position, then adjust the limit switch cam to its desired position. It may be 
necessary to repeat this step until the exact position has been reached. 
 

6. Repeat step 3 and 4 for the opposite direction. Adjust close limit cams so that actuator is engaged 

as door fully seats at the floor. 

 

7. Micro switch (A or B) can be adjusted to accommodate sensing edge cut-off position. 

 

A

D

B

C

F

G

E

 

 

NOTE:

 “C” is usually the opening side and “D” is usually the closing side. 

 
 

 

WARNING

 

Содержание FS-500EP Series

Страница 1: ...INSTALLATION INSTRUCTIONS AND OPERATION MANUAL FS 500EP Series Rolling Fire Door Operators UL325 2010 Compliant Restricted Duty Operators SMART Control ...

Страница 2: ...posed moving parts If the operator must be mounted less 8 ft 2 44 m above the floor then exposed moving parts must be protected by covers or guarding Contact the manufacturer 6 Do not connect the door operator to the source of power until instructed to do so 7 Locate the control station open close stop push button key station or the like a within sight of the door b at a minimum height of 5 feet a...

Страница 3: ...Door Speed 6 8 per sec average typical Brake Solenoid actuated brake ENTRAPMENT PROTECTION Sensing Edge Optional Sensing device attached to the bottom edge of the door Non Contact Device Optional Photo eye device Per the requirements of UL Standard 325 the door operator is setup for constant pressure to close the door As an alternative the door may be provided with a monitored entrapment protectio...

Страница 4: ...ly in a change of control functions Consult factory for any changes LS mounting position is LH operator RS position is RH operator OPERATOR MOUNTING 1 Before the operator is installed verify that the door is properly operating and balanced 2 Make sure the layout of the mounting holes on the bracket is correct 3 When the operator assembly is attached to the door bracket be sure the door driven spro...

Страница 5: ...aft parallel to the door shaft It may be necessary to field brace the operator bracket Operator Drive Sprocket Door Sprocket Correct Incorrect DRIVE CHAIN ADJUSTMENT NOTE Use correct type size and proper length of roller chain 1 Adjust the drive chain by tilting or move the operator so that there is about 1 4 of slack when the chain is depressed Note The set screw included in the operator may be u...

Страница 6: ... place adjust the limit switch cam E or F until the micro switch C or D clicking sound is heard 5 If the limit switch cam cannot be rotated to its desired position release the lever and move the door away from the desired position then adjust the limit switch cam to its desired position It may be necessary to repeat this step until the exact position has been reached 6 Repeat step 3 and 4 for the ...

Страница 7: ...trol panel 6 A separate fuse line of adequate capacity is needed for the operator 7 The operator must be properly grounded The ground screw painted green is located inside the control panel 8 For an operator system or external device requiring field installed wiring between a Class 2 output of an operator and an external device the type of wiring shall be R C AVLV2 8 AWM min 22 AWG rated 60 C with...

Страница 8: ...ove floor Entrapment Device Options Sensing Module Device Manufacturer Model ELR 2 wire resistive sensing edge Miller Edge Inc End of Line resistor type edge must have model number with Suffix T2 ME110 ME111 ME120 ME123 ME112 ME113 ME116 ME117 MT21 MU21 MT22 MU22 MC22 MU33 MC271 CPT223 MEL TXYY MEL RXYY RB G K10 ASO GE225 GE125 GE245 GE F45 GE F50 GE F56 GE F65 GE F85 GE F115 IR Monitored photo ey...

Страница 9: ...power wiring 4 Any wire connected to the control panel must be protected by conduit or other means to ensure the safety and permanency of the wiring Do not use radio controls with your operator unless some type of entrapment protection device has been installed Failure to do so may result in death or serious injury to person s trapped beneath the door Changing from left hand to right hand or vice ...

Страница 10: ...se 0 Cycle A A 2 EDGE L1 L2 L3 Three phase power source See operator plate for correct voltage A 3 ON OFF ON OFF EDGE PHOTO REV 5S ON OFF ON OFF ON OFF 0 1 3 S E Reverse 1 Cycle S E Reverse 3 Cycles S10 S9 S8 S7 S11 S6 S5 Open Close Momentary Pressure Constant Pressure S4 During Alarm 1 Stop 2 Open 3 Close 4 Com 9 10 Moving 10 10A Alarm Warning Signal 24VDC 11 12 Alarm Connection N C Dry Contact 2...

Страница 11: ...00 EP SERIES REVISION 0000 DATE 04 03 2019 B Auxiliary Function R3 R2 R1 R1 R2 R3 Radio control 24VAC Push button 24VAC B 2 Open door B 1 Close door Stop door STOP CLOSE OPEN B STOP CLOSE OPEN STOP CLOSE OPEN ...

Страница 12: ...up T1 T2 C 1 C S17 S18 S16 S15 1 Timer 1 Mid open timer Timer starts counting when door leaves close limit Door stops after opening for set time Pressing open again at mid open position will cause door to open limit Timer 2 Close timer Timer is active when door stops and is not at close limit 2 Standard Mode Cycle counter ...

Страница 13: ... saved T1 T2 Min 1 Sec Set the desired time Max 99 Sec T1 T2 Mid Open Timer T1 T2 Max 99 Sec Min 1 Sec T1 T1 T1 T1 T1 4 To Set Timer 2 Reclose Timer Press T2 and hold for 5 seconds Display will flash Use or to increase or to decrease time Press T2 to save setting Without pressing no adjustment is saved Min 1 Sec T2 T1 T2 Min 1 Sec Set the desired time T1 T2 T1 T2 Timer to Close T2 T2 T2 T2 T2 Max ...

Страница 14: ...se limit switch activated OFF Close limit switch not activated LED10 SLS AUX close Limit contact ON Door at AUX close limit OFF Not at AUX close limit LED9 DEVICE Device light ON When the sensing device connected on terminal CN2 E5 E6 P5 P6 is normal OFF Sensing device disconnected failed or damaged LED30 VVS VVS Flashing Alarm warning signal or terminal CN2 1 4 not connected OFF Normal Condition ...

Страница 15: ...14 FS500 EP SERIES REVISION 0000 DATE 04 03 2019 NOTE ...

Страница 16: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 15 NOTE ...

Страница 17: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 16 ...

Страница 18: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 17 ...

Страница 19: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 18 ...

Страница 20: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 19 ...

Страница 21: ...th After adjusting either the force or the limit of travel retest the door operator s safety features Failure to adjust the operator properly may cause severe injury or death 5 For products having a manual release if possible use the manual release only when the door is closed Use caution when using this release when the door is open Weak or broken springs may cause the door to fall rapidly causin...

Страница 22: ...fer to the fire door installation instructions for connection of the release assembly or consult NFPA 80 and the authority having jurisdiction for fusible link location s and method Fusible link connection location Fusible link connection hole Remove cotter pin after installation Illustration only not drawn to scale See product for actual details ...

Страница 23: ... Removing pressure from the CLOSE key position will cause the door to stop If a sensing edge is not installed on the bottom of the door and removing pressure from the CLOSE button or key switch position does not cause the door to stop this condition must be corrected immediately Improper operation could result in serious injury or death to person s trapped beneath the door 3 Door may also be opera...

Страница 24: ...peration and full closure per NFPA 80 Do not lubricate motor Motor bearings are rated for continuous operation Inspect and service whenever a malfunction either door or operator is observed or suspected Before servicing always disconnect power supply to the operator Replace fuses only with those of the same type and rating All replacement parts must be obtained from the door manufacturer per NFPA ...

Страница 25: ...le Secondary and Third Sensing Devices connect on 1st and 2nd sensing modules Parallel connection or AND Harness Part No ADA DA111 WH001 OR Harness Part No ADA DA111 WH002 Serial connection Primary Sensing Device Connection 1 2 3 or 2 3 1 Unplug the jumper connector to add modules Plug back the jumper connector if no additional module is used QST FS EP ADAPTER 5 Warning Power OFF When Connecting ...

Страница 26: ...OPEN Key switch B2 COM Warning Please Remove Jump Pin First See A A Remove Jump pin OPEN CLOSE STOP OPEN CLOSE KEY REQUIRED TO REMOVE COVER S T O P S T O P R BK R WH OPEN CLOSE NC NO C NC NO C STOP WH WH GR KEY SWITCH COM OPEN CLOSE KEY REQUIRED TO REMOVE COVER S T O P S T O P Key Switch with Stop Button and 3 Button Stations Key Switch with Stop Button Control Wiring for Key Switch with Stop Butt...

Страница 27: ...B2 B1 OPEN CLOSE STOP KEY ON OFF OPEN CLOSE STOP KEY LOCKOUT 3 2 BUTTON B1 B2 1 2 3 4 OPEN OPEN CLOSE CLOSE B2 B1 STOP B2 STOP B1 R BK GR KEY LOCKOUT 3 BUTTON 1 2 3 4 OPEN CLOSE STOP Key switch Key switch R WH GR BK STOP CLOSE OPEN ON OFF R2 R1 RADIO R3 R2 R1 Ceiling Pull Switch Station 1 4 CLOSE OPEN CLOSE OPEN R1 R3 R2 GR WH 3 2 1 WH BK GR WH BK Control Connections Diagrams 1 2 3 4 1 2 3 4 1 2 3...

Страница 28: ...FS500 EP SERIES REVISION 0000 DATE 04 03 2019 27 APPENDIX 4 1 NO 2 OFF ON PK PK ...

Страница 29: ...08V PWR Y R FOR 230V R FOR 208V PWR R R Y REMOVE FACTORY INSTALLED FOR 230V Y CONNECT FOR 208V R Y R Insulate the wire R R BK 1L1 BK BK 1L1 BK 1L1 1L1 1L1 1 Unplug the red 230V wire connector from the red PWR wire connector Remove the insulating cap from the yellow 208V wire connector 2 Put the insulating cap on the red 230V wire connector Plug the yellow 208V wire connector into the red PWR wire ...