FS-150EP Series
230V, 50Hz
REVISION # 0000
DATE: 02/18/2021
A. Control Function:
IR: P5&P6 ELR:E5&E6
(ELR-End of line resistor).
Use S11 to select.
A-1.
Auto Open after
Alarm Clears
Selection
Fusible Link 10 Sec.
Delay Selection
Alarm 10 Sec.
Delay Selection
ELR Sensing
Edge
IR Photo
Eye
Momentary Pressure
Constant Pressure
0
1
3
S.E. Reverse 0 Cycle
A.
A-2.
A. OPEN
F. DLY
A. DLY
REV 5S
EDGE
M.CL
M.OP
PHOTO
ON
OFF
ON
OFF
EDGE
PHOTO
REV 5S
ON
OFF
ON
OFF
ON
OFF
0
1
3
ON
OFF
S.E. Reverse 1 Cycle
S.E. Reverse 3 Cycles
S10
S9
S8
S7
S11
S6
S5
Open
Close
Momentary Pressure
Constant Pressure
S4
During Alarm
1.Stop
2.Open
3.Close
4.Com
9 & 10 Moving
10 & 10A Alarm
Warning Signal
24VDC
11&12 Alarm
Connection
N/C Dry Contact
Non-Monitored
Sensing Devices
(N.O. Dry Contact)
24VDC
MAX 0.5A
1
2
3
4
9
10 10A 11 12 31 32 E5 E6 36 37
P5
P6
+
+
-
CN29
CN28
CN9 & CN10
JUMP FOR ENABLING
RECLOSE TIMER
CN28 & CN29
ALARM TEST JUMPER
CN9
CN10
CN26 :
Optional extra open and
close limits connector
L1 L2
Single-phase power source
See operator plate for correct
voltage.
A-3.
L1 L2 L3
Three-phase power source
See operator plate for correct
voltage.
A-3.
Door Reverse to Open Limit
Door Reverse 5 Sec.
Notes:
● If momentary contact close is desired, an entrapment
protection device must be installed. Turn Switch (S6) to ON.
● Standard 10-second delay during power failure.
● Standard one-second delay on reverse.
● During AC/DC power present and alarm gravity closing,
safety wiring is functional, including stop button and
entrapment device(s).
● During AC/DC power present and alarm gravity closing,
the brake will be engaged for 10 seconds when the door
reaches close limit.
● AC and DC powers failed gravity close.
● Per NFPA 80, during alarm, if equipped with
sensing device, door will stop on an obstruction after
attempting to close the number of times selected on
the S4 switch
Содержание FS-150EP Series
Страница 16: ...FS 150EP Series 230V 50Hz REVISION 0000 DATE 02 18 2021 15 ...
Страница 17: ...FS 150EP Series 230V 50Hz REVISION 0000 DATE 02 18 2021 16 ...
Страница 18: ...FS 150EP Series 230V 50Hz REVISION 0000 DATE 02 18 2021 17 NOTE ...
Страница 19: ...FS 150EP Series 230V 50Hz REVISION 0000 DATE 02 18 2021 18 NOTE ...
Страница 27: ...FS 150EP Series 230V 50Hz REVISION 0000 DATE 02 18 2021 26 APPENDIX 4 1 NO 2 OFF ON PK PK ...