4800 Installation Manual 07-31-18
9
Hardware Installation
BB-48 Control Panel Enclosure Installation
Back Box
The Control Panel(s) enclosure is only offered in a flush mount configuration, made of 16 gauge cold rolled steel
that is primed and painted. The enclosure assembly consists of a separate back box and a locking hinged
Frame/Door assembly. The Back Box chassis should be mounted with the “Top of Box Arrow” pointing up, and
approximately 1/8” to 1/4” below the finished wall surface with the provided hardware.
Control Panel Enclosure
DEPTH
WIDTH
HEIGHT
WEIGHT
(INCHES)
(INCHES)
(INCHES)
(LBS)
#7330-122 Enclosure Chassis:
3.25
18.25 18.25
Rough Opening Dimension:
3.50
18.75 18.75
#7330-123 Enclosure Frame/Door:
1.50
20.00 20.00
Assembled Enclosure:
22
Installation
1. Cut an 18 ¾” square rough
opening in the approved
location.
2. Use the hardware supplied
and the (4) round holes to
mount the back box 1/8” to 1/4”
below the finished surface as
shown. Note the “Top of Box”
arrow for proper orientation.
*Additional hardware (Not
Included) may be necessary
depending on installation type).
3. Support the bottom of the
back box as required.
4. Ensure proper spacing for the
field wiring to be brought into
the top of the box thru the
supplied knockouts. Additional
knockouts can be added as
needed.
5. System wiring should be
routed behind the Control Panel
as shown on the next page.