Corinex Standard Repeater I & II
CXP-UFSGX-I | CXP-UFSGX-II
11
After inserting the connector, slightly rotate the white movable part towards right by about 20
degrees, until the point where the ‘arrow’ mark comes in line with the ‘lock’ sign, as shown in
figure 11.
Figure 11: Mating connector lock
Note that phase B and neutral are used to power up the device.
CXP-UFSGX is IP65 rated and is resistant to water and dust to some extent. But this device and
all other associated accessories are recommended to be enclosed in a cabinet for a safer
operation.
4.3 Voltage sensing feature
CXP-UFSGX is equipped with a voltage sensing feature, allowing for power quality of the
distribution system to be monitored. The integrated 3 phase voltage sensor detects the upper
voltage and lower voltage events. It senses the voltage every 5 seconds. Make sure that the
three-phase power connection to the gateway is intact, so that it can sense the voltage ac-
curately. There are two levels of thresholds for both lower and upper voltage alerts and their
default settings are:
Lower voltage threshold level 1:
215V
Lower voltage threshold level 2:
210V
Upper voltage threshold level 1:
230V
Upper voltage threshold level 2:
240V
CXP-UFSGX uses an SNMP trap feature to notify the headend system (example of headend
system: Corinex Compact BPL Proxy Headend) if there is any voltage alert or imbalance be-
tween different phase voltages. The voltage thresholds are remotely configurable using SNMP
Return to Table of Contents