Section 363-719-141
July 31, 1997
Revision 01
Page 22
PairGain Engineering - Plant Series
PG-Flex FCS-719
8.3
Connect the CO Battery (Figure 5).
Connect the CO Battery (Figure 5). The FCS-719 List 4A
COTS may be powered from a single battery feed or from a split battery feed where you would
connect Battery A (-48V_A) for Systems 1 and 2, and Battery B (-48V_B) for Systems 3 and 4.
1
For split battery feed:
a
Remove and discard the jumper between TB1 and TB2.
b
Connect the wire used for the CO battery A to TB1 (-48V_A) termination point.
c
Connect the wire used for the CO battery B to TB2 (-48V_B) termination point.
d
Connect the wire for the CO battery return to TB3 (BATT RTN) termination point.
e
Connect the CO battery return wire from TB3 on the COTS to the CO battery return
termination point.
f
Connect the CO battery wires from TB1 (-48V_A) and TB2 (-48V_B) on the COTS to the
equipment bay fuse panel termination points.
2
For single battery feed:
a
Connect the wire used for the CO battery A to TB1 (-48V_A) termination point.
b
Connect the wire for the CO battery return to TB3 (BATT RTN) termination point.
c
Connect the CO battery wires from TB1 (-48V_A) on the COTS to the equipment bay fuse
panel termination points.
Figure 5. Connecting the CO Battery
Содержание 150-1319-41
Страница 32: ......