Condensing Unit Controller EC2-5X1
English
French
German
Parameter
r
Sensor Parameters
Min
Max
Unit
Def
Min
Max
Unit
Def
r0
Suction pressure sensor min. value
-1.0
50.0
bar
-0.8
-1.0
50.0
bar
-0.8
r1
Suction pressure sensor max. value
-1.0
50.0
bar
7.0
-1.0
50.0
bar
7.0
r2
Pressure offset for suction pressure
-1.0
1.0
bar
0.0
-1.0
1.0
bar
0.0
r3
Refrigerant type
0
5
-
4
0
5
-
4
EC2-511
EC2-551
r0 & r1 parameters setting value depends of the refrigerant choice “r3”.
r3 is set as default for R404A.
r3 Refrigerant
0 = no temperature conversion
1 = R22
2 = R134a (not possible for units including Copeland Digital Scroll compressors)
3 = R507
4 = R404A
5 = R407C (not possible for units including Copeland Digital Scroll compressors)
NOTE
: R134a cannot be used for Copeland EazyCool™ condensing units with two
compressors, as LP and HP switch are not set for R134a.
C6.1.3/0505-0705/E
Part no: 3125495
13