Installation Instructions – Cruze LED Retrofit Kit
Retrofit Kit Installation Instructions for Kits with
Sensor and Emergency Options
1. While holding lens on one end, insert cable (1) into
sensor connector. Push extra cable back (2) into Main
Panel (D) until cable is tight. If Emergency option is
present, go to Step 2. Otherwise proceed to Step 3.
ote:
N
If Emergency option is present, proceed to step 2. If
Emergency option is not present, proceed directly to
step 3.
2. Emergency Option only - While holding lens on one end,
insert cable (1) into EM test switch. Push extra cable
back into Main Panel (2).
3. Install lens by attaching one side into tabs first and then
rotate lens to secure it to the tabs on opposite Side
Panel (B). Be sure lens engages all tabs.
4. Emergency Option only - Once power is applied to the
Charging Circuit for the Emergency Option, remove
EZ Key. Refer to www.cooperlighting.com for further
instructions on the proper operation and maintenance of
battery pack.
This luminaire is provided with a factory-installed
emergency lighting pack and must be serviced by a person
familiar with the construction and operation of the product
and the hazards involved.
Danger - Risk of shock disconnect all power and disable the
battery pack power before servicing ballast replacement
requires reconnection of wires that may be energized.
OPERATION
Once AC power is permanently applied to the blue wire of the
Fixture remove the EZ key and store it for later use. When AC
power is applied, the charging indicator light is illuminated,
indicating the battery is being charged. When power fails,
the emergency ballast automatically switches to emergency
power, operating its LED load at the rated output for at least
90 minutes.
ote:
N
The battery is not fully charged until 24 hours after
the AC Power is applied.