background image

P84450 F 

Sheet 2 of 4 

 

WARNING:  THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING 

FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE.  DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.  

 

 

WARNING:  CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE 

VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES.  THE 
MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.

  

 

 

CAUTION:  

Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. 

 

WARNING:  MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE 

SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NOTIFICATION APPLICIANCE CIRCUITS, SM, DSM SYNC MODULES, OR 
COOPER WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF 
ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED.  OVERLOADING POWER SOURCES OR EXCEEDING FUSE 
RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT 
IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

 

 

WIRING AND MOUNTING INFORMATION: 

 

CAUTION:  

The following figures (A-F) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option.  If 

these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. 

CAUTION:  

Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed 

multiconductor cable or 3/4" conduit fittings are used. 

 

Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Cooper Wheelock recommends use of the largest backbox 
option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the 
product from wiring. 

 

FLUSH MOUNTING

A

STD. SINGLE-GANG

BACKBOX 2" DEEP

#6-32 SCREWS 

STROBE MOUNTING

PLATE (SMP)

BEAUTY PLATE 

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       4                     4                       4                     4

FLUSH OR SURFACE MOUNT

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       4                     4                       4                     4

4" SQ. X 1-1/2" DEEP BACKBOX

OR 100m X 37.5mm

EUROPEAN BACKBOX

STROBE MOUNTING

PLATE (SMP)

B

#8-32 SCREWS

BEAUTY PLATE 

FLUSH OR SURFACE MOUNT

C

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       4                     4                       4                     4

DOUBLE-GANG X 2-1/4"

DEEP BACKBOX

#6-32 SCREWS

STROBE MOUNTING

PLATE (SMP)

BEAUTY PLATE 

 

 

#8-32 SCREWS

D

SURFACE MOUNTING

SHALLOW SURFACE

BACKBOX (SHBB)

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       4                     4                       4                     4

STROBE MOUNTING

PLATE (SMP)

BEAUTY PLATE 

E

FLUSH MOUNTING

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       8                    8                       8                     8

STANDARD 4" X 2-1/8"

DEEP BACKBOX

APPLIANCE

SURFACE MOUNTING

MAXIMUM NUMBER OF CONDUCTORS

AWG #18        AWG #16         AWG #14        AWG #12

       8                    8                       8                     8

APPLIANCE

BACKBOX (SBL-2)

F

 

Figures E and F are shown with optional 6” bell.  See Table 1A for other possible appliance combinations. 

Содержание RSS-24MCWH

Страница 1: ...LATION AND OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS SPECIFICATIONS Table 1 UL Ratings Model Regulated Voltage VDC VRMS Voltage Range Limit Per UL 1971 VDC VRMS Strobe Candela cd Mounting Options RSS 24MCWH 24 16 0 33 0 135 185 A B C D RSSP 24MCWH 24 16 0 33 0 135 185 E F Table 1A Audibles Speaker...

Страница 2: ...commodate the field wires and stresses from the wires could damage the product CAUTION Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit especially if sheathed multiconductor cable or 3 4 conduit fittings are used Although the limits shown for each mounting option comply with the National Electrical Code NEC Cooper Wheelock re...

Страница 3: ...witch to the desired candela setting The setting is indicated by a pointer and can be seen on the bottom side of the lens See Figures 3 and 4 below 7 Mount the SMP first to the backbox Next slide the beauty plate over the SMP until the 2 snaps of the beauty plate engage with the SMP 8 The beauty plate can be removed from the strobe assembly once engaged First gently insert a screwdriver into one o...

Страница 4: ...nd fire standards guidelines regulations laws and codes including but not limited to all appendices and amendments and the requirements of the local authority having jurisdiction AHJ Cooper Wheelock Inc products when properly specified applied installed operated maintained and operationally tested as provided above are warranted against mechanical and electrical defects for a period of three years...

Отзывы: