Example 5:   IN>OUT SYNC MODE with External Sync Module with Audible Silence  

(CLASS B) 

 
 

POWERPATH

OUT1-4

IN>OUT SYNC

WHEELOCK SYNC

TEMPORAL

INPUT SELECT

TO NEXT 

APPLIANCE

OR EOLR

-

+

IN1

-

+

RET1

+ OUT1

+ IN1

MINUS 1

+ AUDIBLE

SM/DSM

F
A
C
P

EOLR

- AUDIBLE

EOLR

2.2K OHMS

EOLR

2.2K OHMS

+

OUT4

-

+

OUT3

-

EOLR

2.2K OHMS

-

+

OUT2

+

-

OUT1

OR EOLR
(2.2K OHMS)

TO NEXT APPLIANCE

1

2

3

4

ON

1

2

3

4

ON

1

2

3

4

ON

1 2 3

4

ON

SW7

 

 
 

NOTE

:  When using the Wheelock external Sync Module (SM or DSM), synchronization 

will only occur

 with 

Wheelock sync appliances. 

 
 

Example 6:   WHEELOCK SYNC MODE without Audible Silence (CLASS B) 

 
 

POWERPATH

OUT1-4

IN>OUT SYNC

WHEELOCK SYNC

TEMPORAL

INPUT SELECT

IN1

+

-

IN2

+

-

TO NEXT APPLIANCE
OR EOLR

+

RET2

-

P

C

A

F

RET1

+

-

-

OUT4

-

+

OUT3

+

OUT2

-

+

EOLR

2.2K OHMS

EOLR

2.2K OHMS

EOLR

2.2K OHMS

+

-

OUT1

TO NEXT APPLIANCE

OR EOLR
(2.2K OHMS)

1

2

3

4

ON

1

2

3

4

ON

1

2

3

4

ON

1 2 3

4

ON

SW7

 

 
 

• 

This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability. 

• 

If only strobes are connected to the 

POWER

PATH outputs, the initiating input to IN2 is not required.  

• 

When synchronized horns are used on the two wire output of the 

POWER

PATH, IN2 must be connected as 

shown or the horns will not operate. 

Содержание POWERPATH PS-24-8MC

Страница 1: ...0 6899 Ph 800 631 2148 Fax 732 222 8707 Web Site www cooperwheelock com e mail info cooperwheelock com A84661 001A Copyright 2007 Cooper Wheelock Inc All rights reserved Thank you for using our produc...

Страница 2: ...OPERATION 12 3 2 DIP SWITCH SETTINGS 12 3 3 CLASS B OPERATION 13 3 4 CLASS A OPERATION WITHOUT OPTIONAL PS 4CA MODULE 16 3 5 CLASS A OPERATION WITH OPTIONAL PS 4CA MODULE 20 3 6 MASTER REMOTE OPERATI...

Страница 3: ...ition or 200 mAmps constant is provided which can be manually reset The PS 24 8MC also contains a battery charger capable of charging up to 20 Amp Hour AH of battery backup Batteries larger than 12 AH...

Страница 4: ...tput can be synchronized with IN OUT SYNC mode SM DSM or 2nd PS 24 8MC is required Audible silence capability Filtered and electronically regulated output 3 5 Amp auxiliary power limited output with r...

Страница 5: ...erminals are not in use a jumper must be connected across them NOTE Wiring must remain in the same room in conduit TB6 1 2 TB6 3 4 TB6 5 6 TB6 7 8 OUT1 OUT2 OUT3 OUT4 Indicating appliances are connect...

Страница 6: ...P84662J Page 6 of 28 ASSEMBLED IN USA WITH PRIDE TB2 TB4 TB7 Figure 1 Terminal Locations...

Страница 7: ...measures 4 50 High 12 50 Wide 5 00 Deep 2 0 INSTALLATION INSTRUCTIONS NOTE The PS 24 8MC POWERPATH shall be installed in accordance with the National Fire Protection Association NFPA National Electric...

Страница 8: ...of 28 5 00 7 452 Figure 2 Mounting Dimensions DIMENSIONS H x W x D 16 70 x 12 83 x 5 00 NOTE All dimensions shown are in inches CAUTION Use care when punching out knock outs to avoid damage to intern...

Страница 9: ...on power limited wiring See Figure 3 G Connect notification appliances to desired outputs OUT1 OUT4 See Operation Section 3 0 The POWERPATH has in out wiring terminals that accept two 18 to 12 America...

Страница 10: ...f the PC board and used for transmission of local trouble annunciation The three terminals are labeled NO C and NC When the PS 24 8MC is operating normally the NC C terminals are shorted and the C NO...

Страница 11: ...P84662J Page 11 of 28 TB2 TB7 TB4 Figure 3 POWERPATH PS 24 8MC...

Страница 12: ...YNC MODE Allows ONLY a coded signal or Wheelock synchronization signal input to be utilized by the POWERPATH This signal may come from a FACP another PS 24 8MC or a Wheelock Synchronization Module SM...

Страница 13: ...LOCK SYNC TEMPORAL INPUT SELECT OR EOLR 2 2K OHMS TO NEXT APPLIANCE OR EOLR IN1 RET1 OUT1 A P C F TO NEXTAPPLIANCE OR EOLR 2 2K OHMS TO NEXTAPPLIANCE OUT2 TO NEXTAPPLIANCE OR EOLR 2 2K OHMS OUT3 OR EO...

Страница 14: ...econds CAUTION Only use audible appliances that can use a coded signal Do not use with Wheelock Series AS AH NS NH or HS4 HS appliances Example 4 IN OUT SYNC MODE with External Sync Module without Aud...

Страница 15: ...with Wheelock sync appliances Example 6 WHEELOCK SYNC MODE without Audible Silence CLASS B POWERPATH OUT1 4 IN OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT IN1 IN2 TO NEXT APPLIANCE OR EOLR RET2 P C A...

Страница 16: ...circuit 2 uses OUT2 and OUT4 When operating in Class A the two circuits must have the same switch settings for the operational mode selected Switch SW7 position 1 2 on the PC board are in the ON posi...

Страница 17: ...output set in the NORMAL MODE will provide the constant voltage for the strobe circuit Only use sounding appliances that can use a coded signal Do not use Wheelock AS AH or NS NS4 NH appliances with T...

Страница 18: ...Wheelock external Sync Module SM or DSM synchronization will only occur with Wheelock sync appliances Example 12 IN OUT SYNC MODE with External Sync Module with Audible Silence CLASS A POWERPATH OUT4...

Страница 19: ...OR EOLR OR RETURN TO FACP CLASS A TO NEXT APPLIANCE TO NEXTAPPLIANCE CLASS A TO FACP OR RETURN OR EOLR OUT1 4 IN OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT 1 2 3 4 ON 1 2 3 4 ON SW7 This mode will...

Страница 20: ...LIANCE OR EOLR IN1 RET1 OUT1 A P C F 1 2 3 4 ON SW7 RET1 RET2 RET3 RET4 OUT2 OUT3 OUT4 PS 4CA OR RETURN TO FACP CLASS A STROBE AUDIBLE LEGEND Example 16 TEMPORAL MODE CLASS A using the PS 4CA module P...

Страница 21: ...CAUTION Only use audible appliances that can use a coded signal Do not use with Wheelock Series AS AH NS NH or HS4 HS appliances Example 18 IN OUT SYNC MODE with External Sync Module without Audible...

Страница 22: ...lock sync appliances Example 20 WHEELOCK SYNC MODE without Audible Silence CLASS A using the PS 4CA module PS 24 8MC 1 2 3 4 ON OUT1 4 IN OUT SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT TO NEXTAPPLIANCE...

Страница 23: ...SYNC WHEELOCK SYNC TEMPORAL INPUT SELECT TO NEXTAPPLIANCE OR EOLR IN1 RET1 OUT1 A P C F 1 2 3 4 ON SW7 RET1 RET2 RET3 RET4 OUT2 OUT3 OUT4 PS 4CA IN2 RET2 OR RETURN TO FACP CLASS A TO NEXTAPPLIANCE OR...

Страница 24: ...RO FAULT POWER SUPPLY DC AC TB3 TB1 N G L NO C NC NO C NC TROUBLE AC LOSS TROUBLE TB6 TB7 TB4 TB5 TB9 TB6 IN1 IN1 IN2 IN2 RET1 RET1 RET2 RET2 C NC C NC AUX OUT1 OUT2 OUT3 OUT4 BATT F1 10 AMP 250V F2 1...

Страница 25: ...P 2 GND FAULT BATT MICRO FAULT POWER SUPPLY DC AC TB3 TB1 N G L NO C NC NO C NC TROUBLE AC LOSS TROUBLE TB6 TB7 TB4 TB5 TB9 TB6 IN1 IN1 IN2 IN2 RET1 RET1 RET2 RET2 C NC C NC AUX OUT1 OUT2 OUT3 OUT4 BA...

Страница 26: ...rce AC LED OFF No AC power Check AC power source No audible output in WHEELOCK SYNC MODE No input to IN2 IN2 See Example 13 and 14 for proper input connections Horn horn strobes or strobes do not sync...

Страница 27: ...herwise enter 0 00AH AH 7 Add Step 5 and 6 together for the Total Standby Battery Requirement in Amp Hours AH ALARM BATTERY CALCULATION 1 List notification appliance requirements CURRENT ALARM CURRENT...

Страница 28: ...whether a product is suitable for the user s purposes or whether it will achieve the user s intended results There is no warranty against damage resulting from misapplication improper specification a...

Отзывы: