Table 4: dBA Sound Output Level Settings 

Decibel Level 

SW1 Settings 

HIGH dBA: 

Set SW1  POS 1 on 1  (Factory Setting ) 

STD dBA: 

Set SW1  POS 1 on 0 

 

WARNING: DOUBLE CHECK THE SWITCH (SW1) SETTINGS TO MAKE SURE THEY ARE CORRECT.  IMPROPER SETTINGS 

CAN DAMAGE THE UNIT OR RESULT IN NO SOUND OUTPUT OR A dBA SOUND OUTPUT LEVEL THAT IS BELOW THE 
MINIMUM CODE REQUIREMENTS FOR PUBLIC MODE FIRE PROTECTION.   THIS COULD RESULT IN PROPERTY DAMAGE 
AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 
 
STEP 2: 

Set desired alarm tone as follows (refer to Figure 1 and Table 5). 
 
Multitone Strobe Appliances are field set for any one of eight alarm tones by setting a four-position switch (SW1) as shown in Figure 1 and Table 5.  Use 
SW1 POS 2, 3, 4 to select the desired alarm tone. 

 

Table 5:  Alarm Tone Settings 

Tone 

POS 2 

POS 3 

POS 4 

Horn 

1 1 1 

Bell 

1 0 1 

March Time Horn 

Code 3 Horn 

Code 3 Tone 

Slow 

Whoop  0 1 0 

Siren 

1 0 0 

HI/LO 

0 0 0 

 

Figure 2: 

 

 

1.  Multitone Strobe models have in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at 

each screw terminal.  Strip leads 3/8 inches and connect to screw terminals. 

 
2.  Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as shown in Figure 2.  The 

polarity shown in the wiring diagrams is for operation of the appliances.  The polarity is reversed by the FACP during 
supervision.

 

 
NOTE: 

 The Code 3 Horn and Code 3 Tone (set on HIGH dBA) incorporate the temporal pattern specified by ANSI/NFPA for standard emergency 

evacuation signaling.  They should be used only for fire evacuation signaling and not for any other purpose. 
 
 
The Horn and Bell Tones can be used on coded systems with a minimum On-Time of 1/4 second if the audible and strobe are wired to operate 
independently.  All other tones are recommended for use only on continuous (non-coded)  
 

Figure 3: 

177

 CANDELA

 POINTER

BOTTOM VIEW

1 15

 

NOTE

:  The MT Multi-High-Candela comes pre-set at 177cd. 

WARNING:  THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE 

INSTALLATION.  WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN 
PLACE.  AFTER CHANGING THE CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION.  
IMPROPER SETTING OF THE CANDELA SELECT SWITCH, MAY RESULT IN OPERATION AT THE WRONG CANDELA, WHICH 
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS 

 

 
 
 
 
 
WIRING DIAGRAMS: 

P84601 J 

Sheet 3 of 6 