Service Requirements

The Kyle Type VCS-1SX switch has been designed with
a minimum mechanical life of 15,000 operations. The
switch requires routine inspection to check for physical
damage and to verify operation.

Frequency of Inspection

Because these switches are applied under widely varying
operation and climatic conditions, service intervals are
best determined by the user based upon actual operating
experience.

High Potential Withstand Testing

Use the following procedures to perform high-potential
withstand tests at 75% of the rated 60 Hz withstand volt-
age for one minute. See Table 4.

Closed Contacts Test

1. Close the switch contacts.

2. Ground the switch.

3. Apply proper test voltage to one of the bushing

terminals. The switch should withstand the test volt-
age for 60 seconds.

Open Contacts Test

1. Open the switch contacts.

2. Ground the switch.

3. Ground the bushing terminal on one side of the switch.

4. Apply proper test voltage to the ungrounded bushing

terminal. The switch should withstand the test voltage
for 60 seconds.

5. Reverse the test and ground connections to the bush-

ing terminals.

6. Apply proper test voltage to the ungrounded bushing

terminal. The switch should withstand the voltage for
60 seconds.

Withstand Test Results

The high potential withstand tests provide information on
the dielectric condition of the switch.

If the switch passes the closed-contacts test and fails the
open-contacts test, the cause is likely to be in the inter-
rupter assembly.

If the switch fails the closed-contacts test, the cause is
likely to be a diminished electrical clearance or failed insu-
lation.

Replacement Parts

Replacement parts for Kyle switches are available
through the factory service department. Only factory
authorized parts are to be used. Contact your Cooper
Power Systems representative for additional information
and ordering procedures.

Factory-Authorized Service
Centers

Factory-authorized service centers are located through-
out North America to provide maintenance, repair and
testing services for Kyle switches. For further information,
contact your Cooper Power Systems representative.

Type VCS-1SX Solenoid-Operated Capacitor Switch Installation and Operation Instructions

8

WARNING: 

Hazardous voltage. The switchgear

and high voltage transformer must be in a test

cage or similar protective device to prevent accidental
contact with high voltage parts. Solidly ground all equip-
ment. Failure to comply can result in death, severe per-
sonal injury, and equipment damage.

T221.3

!

CAUTION: 

Radiation. At voltages up to the

specified test voltages, the radiation emitted by

the vacuum interrupter is negligible. However, above
these voltages, radiation injurious to personnel can be
emitted. See Service Information S280-90-1, Vacuum
Interrupter Withstand Test Voltage Ratings Information
for further information.

G109.2

!

SERVICE INFORMATION

P.O. Box 1640
Waukesha, WI  53187
www.cooperpower.com

©2000 Cooper Power Systems, Inc.
Kyle

®

is a registered trademark of Cooper Industries, Inc.

Printed on Recycled Paper

!

SAFETY

FOR LIFE

KA2048-500

KEP

6/00

Содержание VCS-1SX

Страница 1: ...on Procedure 6 High Voltage Connections 6 Control Wiring 6 Wiring Diagrams 7 Service Information 8 Service Requirements 8 Frequency of Inspection 8 High Potential Withstand Tests 8 Factory Authorized Service Centers 8 1 Service Information Vacuum Switches Type VCS 1SX Solenoid Operated Capacitor Switch Installation and Operation Instructions S260 15 3 June 2000 Supersedes March 2000 Contents Figur...

Страница 2: ...f this manual Improper operation handling or maintenance can result in death severe personal injury and equipment damage G101 0 WARNING This equipment is not intended to protect human life Follow all locally approved pro cedures and safety practices when installing or operating this equipment Failure to comply can result in death severe personal injury and equipment damage G102 1 WARNING Switchgea...

Страница 3: ...It is in good condition when accepted by the carrier for shipment Upon receipt of a switch inspect the switch thoroughly for damage and loss of parts incurred during shipment If damage or loss is dis covered file a claim with the carrier immediately Handling and Storage If the switch is to be stored for an appreciable time before installation provide a clean dry storage area Locate the switch so a...

Страница 4: ...E 4 Voltage Ratings Maximum Voltage Solidly Grounded Capacitor Banks 12 0 kV Ungrounded Capacitor Banks 10 0 kV Rated Basic Impulse Voltage line to ground 125 kV Open Contact BIL 95 kV Radio Noise Limit 16 4 kV 100 µV 60 Hz Withstand Dry 1 minute 50 kV Wet 10 seconds 45 kV TABLE 3 Electrical Specifications Operating Voltage nominal 120 Vac Operating Voltage range 95 127 Vac Current nominal 5 A Nom...

Страница 5: ...52 2 05 70 2 75 181 7 12 120 4 72 146 6 5 77 213 8 38 31 75 1 25 31 75 1 25 126 4 96 BUSHING TERMINAL CONNECTOR 8 SOLID TO 2 0 AWG CABLE RANGE 50 1 97 140 5 51 GROUND CONNECTOR 8 SOLID TO 2 0 AWG CABLE RANGE BUSHING TERMINAL CONNECTOR 8 SOLID TO 2 0 AWG CABLE RANGE Note All dimensions shown in mm in Dimensions are approximate Figure 2 Dimensions of VCS 1SX switch ...

Страница 6: ...single pole double throw switch three wire control supplied by the customer Any manual switch time switch voltage current or photo electric controlled switch or similar device can be used provided the con trol circuit is energized for a minimum of 50 milliseconds for each operation A connection diagram for a three wire control is shown in Figure 5 Two Wire Control With Relay The control can also b...

Страница 7: ...Interrupting Switch Coil Interrupting Switch Ratings Table For Auxiliary Switch Contact Rating 15 A 0 5 A 0 25 A Input Voltage 120 240 Vac 125 Vdc 250 Vdc 5 Pin Two wire Control B C D A E Relay Coil Open Coil Close Coil Relay Coil Interrupting Switch Coil Interrupting Switch Control Voltage Control Voltage Close Open Control Voltage Control Voltage Common Common Close Open Wiring Diagrams Schemati...

Страница 8: ... cause is likely to be in the inter rupter assembly If the switch fails the closed contacts test the cause is likely to be a diminished electrical clearance or failed insu lation Replacement Parts Replacement parts for Kyle switches are available through the factory service department Only factory authorized parts are to be used Contact your Cooper Power Systems representative for additional infor...

Отзывы: