Type VCS-1SX Solenoid-Operated Capacitor Switch Installation and Operation Instructions

SAFETY INFORMATION

SAFETY FOR LIFE

Kyle Distribution Switchgear products meet or exceed all applicable industry standards relating to product safety. We
actively promote safe practices in the use and maintenance of our products through our service literature, instructional
training programs, and the continuous efforts of all Kyle employees involved in product design, manufacture, marketing,
and service.

We strongly urge that you always follow all locally approved safety procedures and safety instructions when working
around high voltage lines and equipment and support our “Safety For Life” mission.

!

SAFETY

FOR LIFE

!

SAFETY

FOR LIFE

WARNING: 

Hazardous voltage. Contact with

high voltage will cause death or severe personal

injury. Follow all locally approved safety procedures
when working around high voltage lines and equipment.

G103.2

!

WARNING: 

Hazardous voltage. This device is

not a substitute for a visible disconnect. Follow all

locally approved safety practices. Failure to follow proper
safety practices can result in contact with high voltage,
which will cause death or severe personal injury.

G112.1

!

WARNING: 

Before installing, operating, main-

taining, or testing this equipment, carefully read

and understand the contents of this manual. Improper
operation, handling or maintenance can result in death,
severe personal injury, and equipment damage.

G101.0

!

WARNING: 

This equipment is not intended to

protect human life. Follow all locally approved pro-

cedures and safety practices when installing or operating
this equipment. Failure to comply can result in death,
severe personal injury and equipment damage.

G102.1

!

WARNING: 

Switchgear must be properly

selected for the intended application. It must be

installed and serviced by competent personnel who have
been trained and understand proper safety procedures.
These instructions are written for such personnel and are
not a substitute for adequate training and experience in
safety procedures. Failure to properly select, install or
maintain switchgear can result in death, severe personal
injury, and equipment damage.

G122.1

!

Safety Instructions

Following are general caution and warning statements
that apply to this equipment. Additional statements,
related to specific tasks and procedures, are located
throughout the manual.

This manual contains two types of hazard statements:

WARNING: 

Refers to hazards or unsafe

practices which could result in severe per-

sonal injury, or death, and equipment damage.

CAUTION: 

Refers to hazards or unsafe prac-

tices which could result in damage to equip-

ment or in personal injury.

!

!

Hazard Statement Definitions

Following is important safety information. For safe instal-
lation and operation of this equipment, be sure to read
and understand all cautions and warnings.

Содержание VCS-1SX

Страница 1: ...on Procedure 6 High Voltage Connections 6 Control Wiring 6 Wiring Diagrams 7 Service Information 8 Service Requirements 8 Frequency of Inspection 8 High Potential Withstand Tests 8 Factory Authorized Service Centers 8 1 Service Information Vacuum Switches Type VCS 1SX Solenoid Operated Capacitor Switch Installation and Operation Instructions S260 15 3 June 2000 Supersedes March 2000 Contents Figur...

Страница 2: ...f this manual Improper operation handling or maintenance can result in death severe personal injury and equipment damage G101 0 WARNING This equipment is not intended to protect human life Follow all locally approved pro cedures and safety practices when installing or operating this equipment Failure to comply can result in death severe personal injury and equipment damage G102 1 WARNING Switchgea...

Страница 3: ...It is in good condition when accepted by the carrier for shipment Upon receipt of a switch inspect the switch thoroughly for damage and loss of parts incurred during shipment If damage or loss is dis covered file a claim with the carrier immediately Handling and Storage If the switch is to be stored for an appreciable time before installation provide a clean dry storage area Locate the switch so a...

Страница 4: ...E 4 Voltage Ratings Maximum Voltage Solidly Grounded Capacitor Banks 12 0 kV Ungrounded Capacitor Banks 10 0 kV Rated Basic Impulse Voltage line to ground 125 kV Open Contact BIL 95 kV Radio Noise Limit 16 4 kV 100 µV 60 Hz Withstand Dry 1 minute 50 kV Wet 10 seconds 45 kV TABLE 3 Electrical Specifications Operating Voltage nominal 120 Vac Operating Voltage range 95 127 Vac Current nominal 5 A Nom...

Страница 5: ...52 2 05 70 2 75 181 7 12 120 4 72 146 6 5 77 213 8 38 31 75 1 25 31 75 1 25 126 4 96 BUSHING TERMINAL CONNECTOR 8 SOLID TO 2 0 AWG CABLE RANGE 50 1 97 140 5 51 GROUND CONNECTOR 8 SOLID TO 2 0 AWG CABLE RANGE BUSHING TERMINAL CONNECTOR 8 SOLID TO 2 0 AWG CABLE RANGE Note All dimensions shown in mm in Dimensions are approximate Figure 2 Dimensions of VCS 1SX switch ...

Страница 6: ...single pole double throw switch three wire control supplied by the customer Any manual switch time switch voltage current or photo electric controlled switch or similar device can be used provided the con trol circuit is energized for a minimum of 50 milliseconds for each operation A connection diagram for a three wire control is shown in Figure 5 Two Wire Control With Relay The control can also b...

Страница 7: ...Interrupting Switch Coil Interrupting Switch Ratings Table For Auxiliary Switch Contact Rating 15 A 0 5 A 0 25 A Input Voltage 120 240 Vac 125 Vdc 250 Vdc 5 Pin Two wire Control B C D A E Relay Coil Open Coil Close Coil Relay Coil Interrupting Switch Coil Interrupting Switch Control Voltage Control Voltage Close Open Control Voltage Control Voltage Common Common Close Open Wiring Diagrams Schemati...

Страница 8: ... cause is likely to be in the inter rupter assembly If the switch fails the closed contacts test the cause is likely to be a diminished electrical clearance or failed insu lation Replacement Parts Replacement parts for Kyle switches are available through the factory service department Only factory authorized parts are to be used Contact your Cooper Power Systems representative for additional infor...

Отзывы: