Safety Information........................................................ 2

Hazard Statement Definitions ...................................... 2
Safety Instructions ....................................................... 2

Product Information..................................................... 3

Introduction .................................................................. 3
Acceptance and Initial Inspection ................................ 3
Handling and Storage .................................................. 3
Description of Operation .............................................. 3

Ratings and Specifications  ........................................ 4
Dimensions
....................................................................5

Installation Procedure  .................................................6

High-Voltage Connections  .......................................... 6
Control Wiring  ............................................................. 6
Wiring Diagrams  ......................................................... 7

Service Information ..................................................... 8

Service Requirements ................................................. 8
Frequency of Inspection .............................................. 8
High Potential Withstand Tests  ................................... 8
Factory Authorized Service Centers  ........................... 8

1

Service Information

Vacuum Switches

Type VCS-1SX 
Solenoid-Operated Capacitor Switch
Installation and Operation Instructions

S260-15-3

June 2000 • Supersedes March 2000

Contents

Figure 1.
Kyle

®

Type VCS-1SX Single-Phase Vacuum Capacitor Switch.

99029KM

Содержание VCS-1SX

Страница 1: ...on Procedure 6 High Voltage Connections 6 Control Wiring 6 Wiring Diagrams 7 Service Information 8 Service Requirements 8 Frequency of Inspection 8 High Potential Withstand Tests 8 Factory Authorized Service Centers 8 1 Service Information Vacuum Switches Type VCS 1SX Solenoid Operated Capacitor Switch Installation and Operation Instructions S260 15 3 June 2000 Supersedes March 2000 Contents Figur...

Страница 2: ...f this manual Improper operation handling or maintenance can result in death severe personal injury and equipment damage G101 0 WARNING This equipment is not intended to protect human life Follow all locally approved pro cedures and safety practices when installing or operating this equipment Failure to comply can result in death severe personal injury and equipment damage G102 1 WARNING Switchgea...

Страница 3: ...It is in good condition when accepted by the carrier for shipment Upon receipt of a switch inspect the switch thoroughly for damage and loss of parts incurred during shipment If damage or loss is dis covered file a claim with the carrier immediately Handling and Storage If the switch is to be stored for an appreciable time before installation provide a clean dry storage area Locate the switch so a...

Страница 4: ...E 4 Voltage Ratings Maximum Voltage Solidly Grounded Capacitor Banks 12 0 kV Ungrounded Capacitor Banks 10 0 kV Rated Basic Impulse Voltage line to ground 125 kV Open Contact BIL 95 kV Radio Noise Limit 16 4 kV 100 µV 60 Hz Withstand Dry 1 minute 50 kV Wet 10 seconds 45 kV TABLE 3 Electrical Specifications Operating Voltage nominal 120 Vac Operating Voltage range 95 127 Vac Current nominal 5 A Nom...

Страница 5: ...52 2 05 70 2 75 181 7 12 120 4 72 146 6 5 77 213 8 38 31 75 1 25 31 75 1 25 126 4 96 BUSHING TERMINAL CONNECTOR 8 SOLID TO 2 0 AWG CABLE RANGE 50 1 97 140 5 51 GROUND CONNECTOR 8 SOLID TO 2 0 AWG CABLE RANGE BUSHING TERMINAL CONNECTOR 8 SOLID TO 2 0 AWG CABLE RANGE Note All dimensions shown in mm in Dimensions are approximate Figure 2 Dimensions of VCS 1SX switch ...

Страница 6: ...single pole double throw switch three wire control supplied by the customer Any manual switch time switch voltage current or photo electric controlled switch or similar device can be used provided the con trol circuit is energized for a minimum of 50 milliseconds for each operation A connection diagram for a three wire control is shown in Figure 5 Two Wire Control With Relay The control can also b...

Страница 7: ...Interrupting Switch Coil Interrupting Switch Ratings Table For Auxiliary Switch Contact Rating 15 A 0 5 A 0 25 A Input Voltage 120 240 Vac 125 Vdc 250 Vdc 5 Pin Two wire Control B C D A E Relay Coil Open Coil Close Coil Relay Coil Interrupting Switch Coil Interrupting Switch Control Voltage Control Voltage Close Open Control Voltage Control Voltage Common Common Close Open Wiring Diagrams Schemati...

Страница 8: ... cause is likely to be in the inter rupter assembly If the switch fails the closed contacts test the cause is likely to be a diminished electrical clearance or failed insu lation Replacement Parts Replacement parts for Kyle switches are available through the factory service department Only factory authorized parts are to be used Contact your Cooper Power Systems representative for additional infor...