     ADX142715     Installation instructions

EBP1400NCX and EBP1400NCF Instruction Manual

OPERATION

When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When 
power fails, the emergency ballast automatically switches to emergency power, operating one lamp at reduced 
illumination for at least 90 minutes.

MAINTENANCE

Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically 
to comply with local codes. The following schedule is recommended:
1. Visually inspect the charging light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30 day intervals for a minimum of 30 seconds. Depending on
installation, one lamp should operate at reduced illumination.
3. Conduct a 90 – minute discharge test once a year. Depending on installation, one lamp should operate at reduced
illumination for at least 90 minutes.

Refer any service requirements indicated by these checks to qualified personnel.

NOTE:

 After installing the test button / indicator light, mark it with the appropriate label.

Lamp Compatibility Table

Lamp Type

Number 

of Lamps

Lamps Connected to 

Low/High (Red) Output

Wattage

T5

1

HIGH (RED)

6 - 25, 39

T5

1

"LOW (RED / WHITE)"

28 - 35

T5HO

1

HIGH (RED)

24

T5HO

1

"LOW (RED / WHITE)"

54 - 80

T5 CIR

1

HIGH (RED)

22 -  55

T8

1

HIGH (RED)

15 - 32

T8

1

"LOW (RED / WHITE)"

59 - 86

T8U

1

HIGH (RED)

32

T9 CIR

1

HIGH (RED)

20 - 32

T12

1

HIGH (RED)

20 - 75

T12

1

"LOW (RED / WHITE)"

75 - 95

T12HO

1

HIGH (RED)

35

T12HO

1

"LOW (RED / WHITE)"

95 - 110

T12VHO

1

"LOW (RED / WHITE)"

215

BIAX

1

HIGH (RED)

18 - 55

Содержание Sure Lites EBP1400NCX

Страница 1: ...s Note 2 This product is for use with most 2 through 8 6W 215W single and bi pin fluorescent lamps including energy saving circline U shaped and biax For specific lamp compatibility please see the tab...

Страница 2: ...6 Drill or punch a 1 2 hole to install the test button indicator light as shown in illustration 7 Install the test button indicator light as shown in the selected illustration Apply the two included l...

Страница 3: ...X N C LINE HOT 120 277 LINE NEUTRAL AUX COM AUX N O AUX N C LINE HOT 120 24 0 277 LINE NEUT RAL RED WH RED BLUE BLUE WH YELLOW YELLOW BK TE ST BU LIG HT C Emer genc Suita ble fo Test Button Indicator...

Страница 4: ...e at 30 day intervals for a minimum of 30 seconds Depending on installation one lamp should operate at reduced illumination 3 Conduct a 90 minute discharge test once a year Depending on installation o...

Страница 5: ...NC LINE HOT LINE NEUTRAL SWITCHED OR UNSWITCHED LINE HOT UNSWITCHED 120 277 LINE NEUTRAL BLUE LINE NEUTRAL RED AC BALLAST EMERGENCY BALLAST 1 LAMP INSTANT START BLUE BLUE LINE NEUTRAL RED RED AC BALL...

Страница 6: ...CHOOSE BASED ON LAMP AUX COM AUX NO LAMP 1 AUX NC LINE HOT LINE NEUTRAL SWITCHED OR UNSWITCHED LINE HOT UNSWITCHED 120 277 LINE NEUTRAL EMERGENCY BALLAST BLUE LINE NEUTRAL RED AC BALLAST BLUE 2 LAMP I...

Страница 7: ...ED ON LAMP AUX COM AUX NO LAMP 2 LAMP 4 EMERGENCY LAMP 1 YELLOW YELLOW AUX NC LINE HOT LINE NEUTRAL SWITCHED OR UNSWITCHED LINE HOT UNSWITCHED 120 277 LINE NEUTRAL EMERGENCY BALLAST 4 LAMP INSTANT STA...

Страница 8: ...SED ON LAMP AUX COM AUX NO AUX NC LINE HOT LINE NEUTRAL UNSWITCHED 120 277 LINE NEUTRAL WIRE LAMPS USING DIAGRAM PER OF LAMPS AND BALLAST TYPE SWITCHED LINE HOT SWITCHED LINE HOT LINE NEUTRAL BI LEVEL...

Отзывы: