COOPER LIGHTING SOLUTIONS

     ADX142715     Installation instructions

EBP1400NCX and EBP1400NCF Instruction Manual

INSTALLATION

WARNING:

 to prevent high voltage on Red / White, Red, 

and Yellow output terminals prior to installation, the Test 
Button / Indicator Light must be disconnected. Connect 
the Test Button / Indicator Light after installation. 

NOTE:

 Make sure that the necessary branch circuit 

wiring is available. An unswitched source of power is 
required.
1. Disconnect AC power from the fixture. Remove the

ballast channel cover. Install the emergency ballast
with grounding screws either in the ballast channel
(see illustrations 1 & 2) or on top of the fixture (see
illustration 3 / EBP1400NCX only).

2. Select the appropriate wiring diagram to connect

the emergency ballast to the AC ballast and lamp.
Make sure all connections are in accordance with the
National Electrical Code and any local regulations.
(See Illustrations 4 and 5 for terminals).

3. Refer to the lamp compatibility table for the HIGH

(Red) or Low (Red / White) connection per the lamp(s)
being illuminated by the emergency ballast.

4. Install the test button / indicator light through the

ballast channel cover of a troffer (Illustration 1 & 6)
or through the side of a strip fixture (Illustration 2 &
7). Drill or punch a 7/8” hole to install the test button
/ indicator light as shown in illustration 6. Drill or
punch a 1/2” hole to install the test button / indicator
light as shown in illustration 7. Install the test button
/ indicator light as shown in the selected illustration.
Apply the two included labels (“Charging Indicator
Light” and “Emergency Light Push to Test”) adjacent
to the test button indicator light.

5. In a readily visible location, attach the included label

“CAUTION – This unit Has More Than One Power
Connection Point. To Reduce The Risk Of Electric
Shock, Disconnect Both The Branch Circuit-Breakers
Or Fuses and the Test Button / Indicator Light Before
Servicing”.

6. In an area readily visible during relamping, attach the

included relamping label. Write in the lamp type and
wattage.

7. After installation is complete, connect the test

button / indicator light. The factory installed version
(EBP1400NCF) will have 2 twisted wires (brown and
purple) at the access plate which must be connected
for the fixture to operate in emergency mode.

8  Replace covers being careful not to pinch wires, install 

lamps, supply AC power to the emergency ballast.

9. A short term discharge test may be conducted after

the emergency ballast has been charging for one
hour. Charge for 24 hours before conducting a long –
term discharge test. Refer to OPERATION.

Emergency

           Ballast

Test Button/

Indicator Light

Ballast

Channel

   Cover

Illustration 1

Emergency

Ballast

Test Button/

Indicator Light

Illustration 2

Illustration 3

Wire Bundle

Cover

Drill 1/8˝ Hole

for Mounting 

Screws

Emergency

Ballast

Wire Bundle

Cover

1/2˝ Std. Knockout

7/8˝ Hole w/Bushing

EBP1400NCX only

Содержание Sure Lites EBP1400NCX

Страница 1: ...s Note 2 This product is for use with most 2 through 8 6W 215W single and bi pin fluorescent lamps including energy saving circline U shaped and biax For specific lamp compatibility please see the tab...

Страница 2: ...6 Drill or punch a 1 2 hole to install the test button indicator light as shown in illustration 7 Install the test button indicator light as shown in the selected illustration Apply the two included l...

Страница 3: ...X N C LINE HOT 120 277 LINE NEUTRAL AUX COM AUX N O AUX N C LINE HOT 120 24 0 277 LINE NEUT RAL RED WH RED BLUE BLUE WH YELLOW YELLOW BK TE ST BU LIG HT C Emer genc Suita ble fo Test Button Indicator...

Страница 4: ...e at 30 day intervals for a minimum of 30 seconds Depending on installation one lamp should operate at reduced illumination 3 Conduct a 90 minute discharge test once a year Depending on installation o...

Страница 5: ...NC LINE HOT LINE NEUTRAL SWITCHED OR UNSWITCHED LINE HOT UNSWITCHED 120 277 LINE NEUTRAL BLUE LINE NEUTRAL RED AC BALLAST EMERGENCY BALLAST 1 LAMP INSTANT START BLUE BLUE LINE NEUTRAL RED RED AC BALL...

Страница 6: ...CHOOSE BASED ON LAMP AUX COM AUX NO LAMP 1 AUX NC LINE HOT LINE NEUTRAL SWITCHED OR UNSWITCHED LINE HOT UNSWITCHED 120 277 LINE NEUTRAL EMERGENCY BALLAST BLUE LINE NEUTRAL RED AC BALLAST BLUE 2 LAMP I...

Страница 7: ...ED ON LAMP AUX COM AUX NO LAMP 2 LAMP 4 EMERGENCY LAMP 1 YELLOW YELLOW AUX NC LINE HOT LINE NEUTRAL SWITCHED OR UNSWITCHED LINE HOT UNSWITCHED 120 277 LINE NEUTRAL EMERGENCY BALLAST 4 LAMP INSTANT STA...

Страница 8: ...SED ON LAMP AUX COM AUX NO AUX NC LINE HOT LINE NEUTRAL UNSWITCHED 120 277 LINE NEUTRAL WIRE LAMPS USING DIAGRAM PER OF LAMPS AND BALLAST TYPE SWITCHED LINE HOT SWITCHED LINE HOT LINE NEUTRAL BI LEVEL...

Отзывы: