Cooper Lighting LRM347 Скачать руководство пользователя страница 1

Technical Data

Model # LRM347

Lighting Relay Module

Module de relais pour luminaire

Módulo de relé de iluminación

SAFETY INSTRUCTIONS

WARNING:  

 

TURN POWER OFF AT CIRCUIT BREAKER BEFORE INSTALLING. ONLY QUALIFIED ELECTRICIANS 

SHOULD INSTALL THE  LIGHTING RELAY MODULE (LRM).

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

O

O

Do not use outdoors

O

O

Do not let power supply cords touch hot surfaces

O

O

Do not mount near gas or electric heaters

O

O

Equipment should be mounted in locations and heights where it will not readily be subjected to tampering by 

unauthorized personnel

O

O

The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition

O

O

Do not use this equipment for other than intended use

SAVE THESE INSTRUCTIONS

Introduction

The Lighting Relay Module (LRM) is listed in accordance 

to UL 924 as “Emergency Lighting and Power 

Equipment.” The LRM shall be used with Greengate CKM 

Panels and iLumin SC Panels.
The LRM is a device that monitors a normal power circuit. 

Upon sensing loss of power to its monitored circuit, it 

is designed to force all relays/dimmers in the connected 

Greengate CKM Panels and iLumin SC Panels to an ALL 

ON or ALL OFF state regardless of the control panel 

status. This allows the closure of relays and forces all 

dimmers to an all on state during loss of normal power to 

allow emergency power systems to feed lighting loads. 

Once the relay senses the power returning, the panel will 

return to normal operation.
The LRM is available in a 347 VAC model.

LRM – Greengate CKM Relay Panels

ote:

N

The transformer in the connected relay panel must 

be powered from an emergency power source in 

order for the LRM to operate properly.

The LED on the mother board will show an overridden 

state when the LRM triggers a closure through the 

external connection.

IMPORTANT: Line voltage input to the LRM must be 

from the NORMAL power source.

Содержание LRM347

Страница 1: ...g Relay Module LRM is listed in accordance to UL 924 as Emergency Lighting and Power Equipment The LRM shall be used with Greengate CKM Panels and iLumin SC Panels The LRM is a device that monitors a...

Страница 2: ...into the provided contact closure terminal block Yellow and purple wires are not polarity sensitive 3 Connect the LRM to the normal power monitoring circuit Wire the neutral wire to the white wire Wi...

Страница 3: ...to the previous screen Control Wiring For Emergency Panel configurations ensure the iLumin SC panel is fed from an emergency power source The LRM provides a dry contact maintained closure to the swit...

Страница 4: ...lors d une perte de courant normal ce qui permet aux syst mes de secours d alimenter les charges d clairage D s que le relais d tecte le retour du courant le panneau revient son mode de fonctionnement...

Страница 5: ...appuyez sur le bouton iv S lectionnez l option Close puis appuyez sur le bouton ENT v S lectionnez l option Exit Emergency State puis appuyez sur le bouton ENT vi Programmez les sorties en vue des sit...

Страница 6: ...tation normale 347 V c c brun 16 AWG Pour allumer en priorit tablissez le contact sec partir du MRL jusqu aux entr es de commuta teur 1 ou 2 Au contact tous les relais etgradateurs sont pouss s intens...

Страница 7: ...e todos los rel s y fuerza a los reguladores a un estado de todos encendidos durante la p rdida de la alimentaci n normal para permitir que los sistemas de alimentaci n de emergencia env en las cargas...

Страница 8: ...ada correcta Resalte la opci n Abierto y presione el bot n ENT iii Resalte la opci n para Salir del estado de emergencia y presione el bot n iv Resalte la opci n Cerrar y presione el bot n ENT v Resal...

Страница 9: ...16 AWG Para anular el ENCENDIDO Conecte el contacto seco del LRM a la Entrada del interruptor 1 o a la Entrada del interruptor 2 Cuando se cierre el contacto Todos los rel s reguladores est n forzado...

Отзывы: